@@TanweerAhmed sir i am looking for a job if you have any opportunities plz help me out I hv almost 10 year's of Indian experience I am handling individual sites of high rise building
Hello Mr. Tanveer, Can u pls let me know why v do not use anti vortex plate in domestic water pump suction line like the firefighting pump suction line?
Thanks for giving valuable information. 2 more information i would like to add in this. There is need of puddle flanged when pipe is penetrated through rcc wall. And second thing. The pipe should be 10 Dimension for the suction line to the pump
Hello Mr.Tanweer ,I have a doubt if you are using pressure relief valve in situations we don't have tank ,whether we can connect the outlet pipe of relief valve to suction pipe of the pump, requesting your advise
I have watched your video on fire pump , but i want to know about all kind of pipes connect to all pumps what is the function of all pipes like suction & header pipes
Hi sir, You are videos are much helpful and informative. Can you make video on following topics. 1) explaining parts or components of diesel fire pump 2) explaining fire pump control panel inside parts and its function. Thank you so much
Assalamualaikum.bhai Kya Hal ha.hazrat aik vedeo bnyn jis main fire fighting ka Jo kam ha.pipe ko kas napa jay or elbow ho ya tee ho dono ka thread kasy plus minas kasy krin gain .or naqshy k motabiq kasy sary peace tyar krin gain.as per aik video bna dain . please.....many pahly b aap sa request ke thee.Allah aap ko jazy khir ata frmyn
Reservoir/storage tank is connected in fire pump suction line to deliver water for fire sprinkler and standpipe hose connection system in case of fire.
In wet firefighting system has water in pipelines but some air mixed with water which rises the pressure inside pipelines and also create other problems, therefore air vent is installed on top of pipe to air release from water pipelines.
Assalam o Alaikum Tanveer Bi, make a video only for commissioning of fire fighting system & HVAC also design method for ducts and piping & equipment selection
Pressure reducing valve: If inlet pressure is high then according to setting, it decrease the pressure and provide the required reduced pressure in pipeline or system. Pressure relief valve: It remove excessive pressure from pipeline or system for safety point of view.
Fire Main electric pump and Diesel pump capacity should be same because diesel pump is used as a standby pump in case of unavailability of electric power. Further technical reason should be checked as per technical documentation and practical condition.
@@TanweerAhmed sir what are the possible technical reasons or practical conditions , but practical conditions is same for both the pumps i.e line leakages
Check both pumps name plates technical data or approved technical submittal for comparing point of view. If same then traceout pump's rpm and impeller condition
Jab pump pani ko suction karta hay, us wakat tank ka pani cyclone ki tara ghoomta hay, us soorat maay air mix hoti hay water kay sath. Result ye nikalta hay k pump oar pipes maay vibration oar sound paida hota hay, jisay cavitation kahtay hay. Usay khatam karnay k liay pump k suction line maay Vortex plate lagatay hay.
Main components of firefighting pump room, Part-2: th-cam.com/video/vBEe-nKNSIs/w-d-xo.html
Allah apku salamat rakhe...
Mashallah khoob andaaz mein apne samjhaya
Thanks 😊
Tanveer bhai I m learning from ur videos zajakallah khair
MashaAllah great 👍
Best channel of the world in fire safety
Thanks
One of the best MEP channels i came across so far on TH-cam !!!
Thanks 🙏 for ur efforts Tanveer Saab!
From Peshawar.
Thanks
nice
thanks sir ji. This video lecture helped me to understand in a easy way.
Welcome
nice
It helped me very much sir. After watching your video i came to know the functioning of each and every component of fire pump room. Thank you 🙏.
Welcome
nice
Great video sir. It was very easy to understand especially in the last diagram which was like a revision of the whole video all summed up.
Thanks for appreciation
best information..we cant get any where other than this chaneel.thanks
Thanks
Jazakallah, bahut accha kam kar rahe ho aap.
Thanks
Appreciate your efforts....so simple and easy to understand.......
Thank you
Thank you so much Sir.
I'm from india Mumbai Maharashtra 🇮🇳
Welcome
Good knowledge sharing
Thank you
Great job Tanveer bhai
Thank you
Love from India... Keep it up dear sir
Thank you
Zabardast vdo h jazakallah khair
Thanks
@@TanweerAhmed sir i am looking for a job if you have any opportunities plz help me out
I hv almost 10 year's of Indian experience
I am handling individual sites of high rise building
I belong to Pakistan therefore It is difficult for me
Oh i think u r in UAE dats y
Hello Mr. Tanveer,
Can u pls let me know why v do not use anti vortex plate in domestic water pump suction line like the firefighting pump suction line?
You can use, I think no problem
Reminder with request, please make videos about elevators, Yr all previous videos are very nice, we are waiting for the same
Ok I will start work on this topic also. Thanks for your interest and feedbacks.
Thanks for giving valuable information. 2 more information i would like to add in this. There is need of puddle flanged when pipe is penetrated through rcc wall. And second thing. The pipe should be 10 Dimension for the suction line to the pump
Thanks
very Knowledgeable video
Thanks
Sir, Please make videos on Pump shaft alignment and Room integrity test for FM200 enclosures.....
Noted
Love from India , Thankyou very much for Teaching sir
Thank you
nice
Bahut sandar videos bnaya
Thanks
Sir you chanal is very good
Thank you
Very nice informetion thank you sir
Welcome
Really Appreciated. Great Work.
JazakaAllah
Superhit sir...
Thanks
Hello Mr.Tanweer ,I have a doubt if you are using pressure relief valve in situations we don't have tank ,whether we can connect the outlet pipe of relief valve to suction pipe of the pump, requesting your advise
Mostly pressure relief valve is used with suction tank or drain.
@@TanweerAhmed Dear Mr.Tanweer, thanking for your kind reply 👍
Very nicely presented, thank you so much
Thank you
nice
Bohat aala.
JazakaAllah
very good video
Thank you
Thank you very much... Sir... Expecting more videos from you.... GOD bless you.
Welcome
Thank you very much, very informative and helpful with detailed explanation. Kolkata, India.
nice
Glad it was helpful!
दोस्त आप bhout समझाते हो
Nice mere Bhai
Thank you
Bhai, detail explanation videos. Excellent. thanks.
Welcome
شکریہ سر بہت خوب م
مھربانی
Sir ji building hight ke nusar pump kitne hp ke lagenge ispe ek video banai ya fir reply kare
Ok noted
thank you so much Mr Tanveer very informative video
You are welcome
Great job
Thanks
Nyc information
Thanks
OS&y valve screw down type valave hota hai kya sir?
Basically it is gate Valve but it's spindle (screw type) visible up or down when on or off. Search on Google it's pictures and details
Please make short video on maintenence of Fire fighting and fire alarm system..
Ok noted
Wonderfully explained.. 👍👍
Thank you
I have watched your video on fire pump , but i want to know about all kind of pipes connect to all pumps what is the function of all pipes like suction & header pipes
Suction= Water intake of pump
Header= It is like junction point where more than one pipe connect
Hi sir,
You are videos are much helpful and informative. Can you make video on following topics.
1) explaining parts or components of diesel fire pump
2) explaining fire pump control panel inside parts and its function.
Thank you so much
Ok I will ... In future
Excellent
Thanks
Nicely explained
Thanks 😊
2:28 water k sath pani mix hojata h jisse vibration hoti h..? Kya mtlb iss baat ka
Cavitation problem happened therefore vibration produced in pipes and pump.
@@TanweerAhmed sir it was mistake you should have spoke "paani ke saath air mix ho jata hai"
Assalamualaikum.bhai Kya Hal ha.hazrat aik vedeo bnyn jis main fire fighting ka Jo kam ha.pipe ko kas napa jay or elbow ho ya tee ho dono ka thread kasy plus minas kasy krin gain .or naqshy k motabiq kasy sary peace tyar krin gain.as per aik video bna dain . please.....many pahly b aap sa request ke thee.Allah aap ko jazy khir ata frmyn
Ok noted, Insha'Allah prepare video
Why set up the receiving tank in pump suction line.
Plz! explain me ,Sir
Reservoir/storage tank is connected in fire pump suction line to deliver water for fire sprinkler and standpipe hose connection system in case of fire.
Very well explained sir....
Thanks
Fabulous work
Thanks 😊
Very good description...Thank you!
Welcome
air release valve and pressure release valve require in fire pump.ya air release valve require for both work
In wet firefighting system has water in pipelines but some air mixed with water which rises the pressure inside pipelines and also create other problems, therefore air vent is installed on top of pipe to air release from water pipelines.
nice, thank you sir...
Welcome
Good bro I appreciate
JazakaAllah
Sir, Please make videos about Foam System & FM200 System
Insha'Allah will prepare
Thank you so much bhai...
Welcome Bhai
Thanks sir nice video
Welcome
The bonus round ...
Specs of equipment and municipality well capacities
😊
Tanveer Sir ,At what pressure sprinkler do off please tell me
What means by Sprinkler do off?
Anti vortex tank plate ko replace kr k footvalve use kr skte h suction mw
Anti vortex plate remove turbulent flow or air in water or vortex in water. While Foot valve restain the water in suction pipe line of pump.
Mostly we use anti vortex plate with foot valve for firefighting pumps when suction take from vertical wall bottom side
Both (Anti vortex plate and foot valve) function is different
I understand that but where we use Anti vertex in fire fighting plz explain
Anti vortex install inside the reservoir tank and connected with fire pump suction pipeline
Sir what is the function of this diesel pump
If electric power is not available from WAPDA or KElectric then in emergency we will use Diesel pump
Informative
Thanks
Excellent way of explaination & informative video, please make one video on Elite software Fire fighting hydraulic calculation
Thanks
Thank you so much sir
Welcome
Asscalamualiku sir, Please help me. Fire fighting pump how to Operating system. And Start time did not be problem.
Your question is not clear
@@TanweerAhmed Sir, how to run a fire pump. And what problems to deal with when running the pump.
Ok noted
I suggest to watch Part-2 video. Pumps are automatically start stop except diesel pump.
thank you sir
Thanks.jazakallah
Welcome
Please provide the link for fire hydrant system details & how it is connected through HDPE external & sprinkler system
Join my Telegram group "HVAC|MEP Engineering" for technical discussion and documents
I am an Engineer but your information is excellent
Thanks
Assalam o Alaikum
Tanveer Bi, make a video only for commissioning of fire fighting system & HVAC also design method for ducts and piping & equipment selection
W.Salam,
Insha'Allah
Firefighting good detailed video
Thanks
Good information video
Thanks
Assalamualaikum.. the location of flow meter mentioned in this video found not correct. For your information.
You are right. Flow meter pipeline shall be installed between check valve and gate valve of pump discharge without pressure relief valve.
@@TanweerAhmed yes.. so that we shall conduct flow and performance tests.
@@jmr6041 right
Excellent Mr. Tanveer, you explained the components very nicely. Thank u so much.
Welcome
Sir...pani ke saat water kaise mix hota ..wo humko samajye
Ya aap ko samaj nahi aahay ga 😀
@@TanweerAhmed Agar instructer me Daamm hi gadha ko bhi samja dega
Wo baat aap ki Durst hay magar tanz or mazak Karna sahi Nahi hay. Insan say ghalty may ghalat alfaz Nikal jatay hay.
@@TanweerAhmed thanks sir..
Main mechanical engineer hu..or right knowledge ke tash le hu..wanna to talk with me.
Great video
Thanks
Kindly share any suppliers of antivortex plates
Kindly check at your end
nice information
Thanks
Great job sir😍
Thanks
sir what is difference between pressure reducing valve and pressure relief valve
Pressure reducing valve: If inlet pressure is high then according to setting, it decrease the pressure and provide the required reduced pressure in pipeline or system.
Pressure relief valve: It remove excessive pressure from pipeline or system for safety point of view.
Thanks sir😊
Paani ke sath water mix ho jata he????
Thanks for criticism
Really i like yOur channel sir,, __!
Thanks
nice
Very nice
Thanks
Sir thank you
Welcome
Sir hmare pump house mai electric pump 1500 rpm par 10 kg pressure derha hai but Diesel pump same Rpm par 5-6 kg pressure derha hai aisa kyu???
Fire Main electric pump and Diesel pump capacity should be same because diesel pump is used as a standby pump in case of unavailability of electric power. Further technical reason should be checked as per technical documentation and practical condition.
@@TanweerAhmed sir what are the possible technical reasons or practical conditions , but practical conditions is same for both the pumps i.e line leakages
Check both pumps name plates technical data or approved technical submittal for comparing point of view. If same then traceout pump's rpm and impeller condition
pani k sath water mix hojataye iska matlab kya he 2.25 sec
Jab pump pani ko suction karta hay, us wakat tank ka pani cyclone ki tara ghoomta hay, us soorat maay air mix hoti hay water kay sath. Result ye nikalta hay k pump oar pipes maay vibration oar sound paida hota hay, jisay cavitation kahtay hay. Usay khatam karnay k liay pump k suction line maay Vortex plate lagatay hay.
sprinkler system ko fit karte hai to kya use hota hai fiting me sir
Aap Ka sawal samj Nahi aaya
good job
Thank you
thank you, very good video.
Welcome
Very informative... 🙂
Thanks
Good
Thanks
👍👍👍
Thanks
Sir ya ppt mil sakta ha kiya ?
I can forward in pdf, send email address
sanmahanty1234@gmail.com
Sir aap ka paas fire hydrant pump house ka block diagram with part identification ha kiya
Plz sir send me too at chandrakantthakur011@gmail.com
zeeshanktk127@gmail.com.
Pls share pdf or ppt if possible
Sir can you please share ppt as in video it is not visible so that we can memorize plz
Share email
Mashallah bahut acchi knowledgeable video hai aur Aise video banaaiye aur Logon ke sath Shahar kijiye😍 Saath Saath Mere ko bhi support kijiye
Insha'Allah
Ek pump se kitna riser nikal skte hi aur ek riser se kitna zone aur kitna FHC nikal skte hi,, __!
It is detail design.... but I will come later on these topics
ThankOo sir,, __! ❤️
There is no 2 part ??
Yes, link is given in comment box
Thank you sir
Welcome
Can you provide training
Not started yet