Daikin VRV | How to resolved error code PJ after replacing outdoor main PC Board.

แชร์
ฝัง
  • เผยแพร่เมื่อ 12 ก.ย. 2024
  • Brand : Daikin VRV 3
    model : RXQ14PAY13
    Error code: PJ / U3
    1)Error PJ
    Outdoor unit: Faulty field setting after replacing main PCB or faulty combination of PCB.
    Method of Malfunction Detection
    The Malfunction is detected according to communications with the inverter.
    Malfunction Decision Conditions
    Make judgment according to communication data on whether or not the type of the inverter PCB is correct.
    Supposed Cause
    *Faulty (or not)field setting after replacing man PCB.
    2)Error U3
    Outdoor unit : Check operation not executed.
    Method of Malfunction Detection
    Check operation is executed or not.
    Malfunction Decision Condition
    Malfunction is decided when the unit starts operation without check operation.
    Supposed Cause
    Check operation is not executed.
    #bonmj #daikin #vrv

ความคิดเห็น • 74

  • @karaors8970
    @karaors8970 2 ปีที่แล้ว +1

    hi bon
    nice job good video
    This is inaccessible information.

    • @BonMj
      @BonMj  2 ปีที่แล้ว

      Thanks bro.

  • @anbasellamuthu3658
    @anbasellamuthu3658 2 ปีที่แล้ว +1

    Hi bon, very usefull video thanks

    • @BonMj
      @BonMj  2 ปีที่แล้ว +1

      Thanks bro

  • @karimchiu7527
    @karimchiu7527 ปีที่แล้ว +1

    thanks sir Bon

    • @BonMj
      @BonMj  ปีที่แล้ว

      Welcome 🙏

  • @electrolatif
    @electrolatif ปีที่แล้ว +1

    Great video

    • @BonMj
      @BonMj  ปีที่แล้ว

      Thanks

  • @jrbfyp7065
    @jrbfyp7065 หลายเดือนก่อน +1

    Hi sir Bon
    Do I need to set controll PCB setting according to manual if the controll PCB I replaced is slave unit and not master unit.

    • @BonMj
      @BonMj  หลายเดือนก่อน

      New Pcb need to do setting at dip sw

  • @johnnyroxannebautista2063
    @johnnyroxannebautista2063 2 ปีที่แล้ว +1

    Wow really love your tutorial sir Bon but pardon me for asking question everytime i watch your video hehe
    When the test run mode is done?
    will it go back to the normal operation mode wherein only H3P light is on and Hap Led is flashing?
    How long does a test run mode last?

    • @BonMj
      @BonMj  2 ปีที่แล้ว +1

      Test run mode, wait until the cu stop running and Led 3 On only.
      How long test run, more than 20 minutes. (In between 1hr)

    • @johnnyroxannebautista2063
      @johnnyroxannebautista2063 2 ปีที่แล้ว +1

      @@BonMj thank you so much sir Bon.

    • @BonMj
      @BonMj  2 ปีที่แล้ว

      @@johnnyroxannebautista2063 welcome

  • @mubaraksk772
    @mubaraksk772 2 ปีที่แล้ว +1

    I am an AC mechanic. What kind of person do you need?

  • @shirazahmad1615
    @shirazahmad1615 ปีที่แล้ว +1

    I am fan sir

    • @BonMj
      @BonMj  ปีที่แล้ว

      Thanks

  • @willybareno1506
    @willybareno1506 2 ปีที่แล้ว +2

    Fantastic information Bom! Thanks for your kind help!
    I'm having this error *PJ* with a model not listed there *RXYQ18PAYL8* , could you please help me get this manual for solving this error? It appears after a failure in power supply. I appreciate very much! God bless you!!

    • @BonMj
      @BonMj  2 ปีที่แล้ว

      Do you reset and running in test mode?

    • @willybareno1506
      @willybareno1506 2 ปีที่แล้ว +1

      @@BonMj good morning my friend! Thank you for your reply! Actually I haven't since the board was removed, só then I thought it would need the specific settings configuration for this model. Can you please help me with that? Thank you!!! 🙏🏻

    • @willybareno1506
      @willybareno1506 2 ปีที่แล้ว +1

      Tried resetting but didn't do anything. After pressing Test, all yellow lights get bright for about 7 min, then turn back to inicial automátic test.

    • @willybareno1506
      @willybareno1506 2 ปีที่แล้ว +1

      Do you hace an email/WhatsApp to contact you Sir? Thank you!

    • @BonMj
      @BonMj  2 ปีที่แล้ว +1

      @@willybareno1506 bonmj81@gmail.com

  • @goparismail9727
    @goparismail9727 2 ปีที่แล้ว +1

    sukses selalu bosku bon mj good👍👍👍👍👍👍👍

    • @BonMj
      @BonMj  2 ปีที่แล้ว

      Terima kasih master

  • @thenjithua5782
    @thenjithua5782 2 ปีที่แล้ว +1

    Hi, any idea why vrv3 accumulator freezing? Sensor reading all normal, and system only running inv compressor, 18hp,std 1 and std2 no running

    • @BonMj
      @BonMj  2 ปีที่แล้ว +2

      May be evaporator coil choke or EEV not functioning well

  • @princemuzammilkhan9127
    @princemuzammilkhan9127 9 หลายเดือนก่อน +1

    OUTDOOR MODEL NO...RXYTQ8T7YF . MAIN PCB NEW INSTALL what setting to put DIP SWITCH ..

  • @user-rh3mt7df4m
    @user-rh3mt7df4m 7 หลายเดือนก่อน +1

    Please i don't understand how make start up 😢

  • @allanacebartican7715
    @allanacebartican7715 2 ปีที่แล้ว +1

    Can i ask for accu model RXYQ18PAYL the correct setting is DS2 1,2,3,4 all on Yes or No?

    • @BonMj
      @BonMj  2 ปีที่แล้ว

      I only got RXYQ18PAY1
      DS2 all On

  • @alonsoacosta8545
    @alonsoacosta8545 2 ปีที่แล้ว +1

    Gracias

    • @BonMj
      @BonMj  2 ปีที่แล้ว

      Welcome

  • @numanmirza9584
    @numanmirza9584 2 ปีที่แล้ว +1

    Sir your company name..??

  • @jiezhang730
    @jiezhang730 ปีที่แล้ว +1

    Hi, Sir. Can you please tell me how to fix this PJ on Daikin RZP100DV1 after installing new outdoor PCB?

    • @BonMj
      @BonMj  ปีที่แล้ว

      Do you try press reset and test run

    • @jiezhang730
      @jiezhang730 ปีที่แล้ว +1

      @@BonMj thank you for reply. I checked the manual, and bought the capacity adapter, now it’s resolved

  • @tyronyuen_96
    @tyronyuen_96 ปีที่แล้ว +1

    I got a vrv 3 here RXQ12(master) RXQ12(slave 1) RXQ10(slave 2) now the slave 1 control pcb faulty already change deep switch already done but can’t run still under error PJ.. may I know how to solve it 🙏🏻🙏🏻🙏🏻🙏🏻🙏🏻🙏🏻

    • @BonMj
      @BonMj  ปีที่แล้ว

      Do you try dun set the dip switch.

    • @tyronyuen_96
      @tyronyuen_96 ปีที่แล้ว +1

      @@BonMj already done..I try to do setting hold and press H1P & H3P set 38 times return set returnx2 no any response

    • @MsJain123
      @MsJain123 หลายเดือนก่อน

      Hi I have same issue did you solve the issue, if yes can you tell me

  • @ManojKumar-zu2yz
    @ManojKumar-zu2yz 11 หลายเดือนก่อน +1

    Sir vrv 3 error code pj replesh tha 18 hp same model ds1 factory settings not working ok.replesh tha working machine 18 hp Cheng error code pj.invater PCB tester current show

    • @BonMj
      @BonMj  11 หลายเดือนก่อน

      Check your model settings

  • @Raam1977
    @Raam1977 2 ปีที่แล้ว +1

    Mr. Bon I have some vrv questions

    • @BonMj
      @BonMj  2 ปีที่แล้ว

      Hi

  • @anbukannanrudhramoorthy3351
    @anbukannanrudhramoorthy3351 ปีที่แล้ว +1

    Bro..the error is JC.what is the main problem in vrv..

    • @BonMj
      @BonMj  ปีที่แล้ว +1

      Check high/low pressure sensor

  • @manikandanmani646
    @manikandanmani646 2 ปีที่แล้ว +1

    Hi Bro please upload compressor change video in VRV

  • @Raam1977
    @Raam1977 2 ปีที่แล้ว +1

    And how I contact you

  • @bageshwardham1523
    @bageshwardham1523 11 หลายเดือนก่อน +1

    Daikin VRV 3 CU Model RXYQ10P7Y1K , PCB SEB0890 C how to do dip switch setting

  • @karthikmurugan8622
    @karthikmurugan8622 2 ปีที่แล้ว +1

    RXYQ18PAY6 model setting pls

  • @jjjbossjjj
    @jjjbossjjj 2 ปีที่แล้ว +1

    Hi bro, how to contact u to engage ur service in SG?

    • @BonMj
      @BonMj  2 ปีที่แล้ว

      Your aircon any problem

  • @welcometomydreamworld6812
    @welcometomydreamworld6812 2 ปีที่แล้ว +1

    🙏🙏👍

    • @BonMj
      @BonMj  2 ปีที่แล้ว

      Thanks

  • @MohammedHassan-ld3ei
    @MohammedHassan-ld3ei ปีที่แล้ว +1

    Sir please I just want work with you

  • @karthikmurugan8622
    @karthikmurugan8622 2 ปีที่แล้ว +1

    Sir I tried this but not working sir
    U4 showing after I changed same model outdoor another unit pcb interchange and then test run ..it's on and working but after 10 min it's off and h2p and h3p blinking and indoor remote was UF showing what's the problem sir

    • @BonMj
      @BonMj  2 ปีที่แล้ว +1

      UF
      1)comunication problem
      2)if one unit blinking UF,check indoor thermistor

    • @karthikmurugan8622
      @karthikmurugan8622 2 ปีที่แล้ว +1

      @@BonMj dear sir checked all indoor communication wire it's normal .
      Then UF showing all idu

    • @karthikmurugan8622
      @karthikmurugan8622 2 ปีที่แล้ว +1

      @@BonMj fully confused yesterday full night checking still not rectified sir .pls help me

    • @BonMj
      @BonMj  2 ปีที่แล้ว +1

      @@karthikmurugan8622 the pcb uou take from other unit ?same model?

    • @karthikmurugan8622
      @karthikmurugan8622 2 ปีที่แล้ว

      @@BonMj yes sir

  • @user-vx8kq2sx6m
    @user-vx8kq2sx6m 11 หลายเดือนก่อน +1

    Mayowa Andrade

  • @sarfarajshaikh4582
    @sarfarajshaikh4582 2 ปีที่แล้ว +1

    Nice brother 👍
    Please make video on
    AJ error :- indoor capacity settings error

    • @BonMj
      @BonMj  2 ปีที่แล้ว

      Thanks

  • @karthikmurugan8622
    @karthikmurugan8622 2 ปีที่แล้ว +1

    Pls upload the chart

  • @Raam1977
    @Raam1977 2 ปีที่แล้ว +1

    And that how much you charge I will pay for you

    • @BonMj
      @BonMj  2 ปีที่แล้ว

      Where is your location

  • @juruteknik6436
    @juruteknik6436 2 ปีที่แล้ว +1

    tq bos

    • @BonMj
      @BonMj  2 ปีที่แล้ว

      Thanks bro

  • @ciaranmcmahon1991
    @ciaranmcmahon1991 2 ปีที่แล้ว +1

    Daiken are a pain in the hole 🤣