How to diagnosis multi-outdoor-unit error using monitor mode 14 | Daikin VRV3

แชร์
ฝัง
  • เผยแพร่เมื่อ 25 ก.ค. 2024
  • Brand : Daikin VRV3
    model : RXQ14PAY13 RXQ10AYM
    Error code: E2
    Remote controller display = E2
    Applicable Models
    VRV3, VRV3-Q
    Method of error Detection
    Failure is to be detected by using leak detection PCB assy.
    Error Decision Conditions
    Leakage is detected under the conditions outside of the scope of high pressure switch operation.
    Supposed Causes
    Defective compressor.
    #bonmj #daikin #vrv

ความคิดเห็น • 66

  • @hossainurrahman6700
    @hossainurrahman6700 2 ปีที่แล้ว +2

    finally i get a great teacher
    thank you so much sir
    thanks from india

    • @BonMj
      @BonMj  2 ปีที่แล้ว

      Welcome

  • @JuanTodoli
    @JuanTodoli 2 ปีที่แล้ว +1

    Oh my God... this was The Big Party of The Faulty Thermistors! 🥳 One after another!

  • @kashibaba521
    @kashibaba521 ปีที่แล้ว +1

    Bon sir lot of thanks 💓

    • @BonMj
      @BonMj  ปีที่แล้ว

      Welcome

  • @RamKrishna-zb5ng
    @RamKrishna-zb5ng ปีที่แล้ว +1

    Very nice sir,from India, ,

    • @BonMj
      @BonMj  ปีที่แล้ว +1

      Thanks 🙏

  • @khim1jivit691
    @khim1jivit691 ปีที่แล้ว +1

    Hello sir bon😍I like you ..i’m from Cambodia

    • @BonMj
      @BonMj  ปีที่แล้ว

      Thanks

  • @hanyaberbagi9124
    @hanyaberbagi9124 2 ปีที่แล้ว +1

    Hi sir bon , i love your explanation . 🙏 . Im beginner in Daikin VRV .
    Say hello from BALI

    • @BonMj
      @BonMj  2 ปีที่แล้ว

      Thanks

  • @janshaw5472
    @janshaw5472 ปีที่แล้ว +1

    very nice teach....

    • @BonMj
      @BonMj  ปีที่แล้ว

      Thanks 🙏

  • @sarfarajshaikh4582
    @sarfarajshaikh4582 2 ปีที่แล้ว +1

    Great job brother

    • @BonMj
      @BonMj  2 ปีที่แล้ว

      Thanks

  • @boonyeun2056
    @boonyeun2056 2 ปีที่แล้ว +1

    Thx's for ur explaination :)

    • @BonMj
      @BonMj  2 ปีที่แล้ว

      Welcome

  • @karaors8970
    @karaors8970 2 ปีที่แล้ว +2

    Hi, it's a very explanatory video again bro.👏👏👏🙏

    • @BonMj
      @BonMj  2 ปีที่แล้ว

      Thanks

  • @peramaraj2763
    @peramaraj2763 2 ปีที่แล้ว +1

    Thanks for your update sir i would like to expert Mitsubishi outdoor function settings video sir

  • @asangajayalath1665
    @asangajayalath1665 2 ปีที่แล้ว +1

    Good job

    • @BonMj
      @BonMj  2 ปีที่แล้ว

      Thanks

  • @m.haslam8495
    @m.haslam8495 ปีที่แล้ว +2

    Hi everyone, I've working on Daikin VRV for many years. I have one question, why does the Daikin VRV have a lot more problems with their systems than any other equivalent VRF Systems, like Mitsubishi Electric, Mitsubishi Heavy, Fujitsu, Toshiba, plus many others. Just the parts department of Daikin are so extensive and very busy., especially here in the UK 🇬🇧. One example, replaced many, many compressors for Daikin VRV, but for other manufacturers, just a few in my time. What I have personally found that if a Daikin VRV System is professionally installed and commissioned and well maintained afterwards, there will be a lot less breakdown and thus less repairs. We have installed Daikin VRV Systems and they have been running trouble free for many years. Anyway, it keeps me very busy especially working on Daikin VRV Systems.

  • @theluunguyen1234
    @theluunguyen1234 ปีที่แล้ว +1

    Good jop

    • @BonMj
      @BonMj  ปีที่แล้ว

      Thanks

  • @sahiljuned3762
    @sahiljuned3762 2 ปีที่แล้ว +1

    Please one video uj 01 urgent explain daikin vrv 4

  • @arunachalammk743
    @arunachalammk743 ปีที่แล้ว +2

    Dear sir,
    I am Arunachalam from Chennai, Tamilnadu, India. Glad to chat with you. Now I am servicing rxyq 18 pay6 +rxyq 18 pay6 +rxyq 10 pay6 Daikin VRV. rxyq18pay6 is a master. When on the unit rxyq 10 pay6(master) runs for 10 min without error. After 10 min it gave a u4 error and the unit stopped. When I clear the error in the remote control it will start again. Sometimes slave one inverter compressor starts. But, only one fan starts running for 10 seconds, stops, and again starts after 30 seconds and stops within 10 seconds. slave condenser coil gets high heat. slave gas flow gives more sound. slave 2 is dead silent. total 40 indoor units. when I load more than 10 units it will give a u4 error. Please suggest an idea to rectify it.

  • @theluunguyen1234
    @theluunguyen1234 ปีที่แล้ว +1

    You have video setting of normal to emergency mode for inveter for singer unit. Thank you.

    • @BonMj
      @BonMj  ปีที่แล้ว +1

      Same setting

  • @davecoolaircon
    @davecoolaircon 2 ปีที่แล้ว +1

    Hi Mr Bon ,like to check with you .What does the acceptable range of ohms reading of the thermistor when ambient at 30°c?

    • @BonMj
      @BonMj  2 ปีที่แล้ว +1

      Daikin 16K ohm for gas pipe thermistor

  • @CCL13984
    @CCL13984 ปีที่แล้ว

    In this case,need to bypass the master unit?

  • @bhaveshsapat7032
    @bhaveshsapat7032 ปีที่แล้ว +1

    Who error of outdoor control pcb faulty

  • @shahnawazalam3081
    @shahnawazalam3081 ปีที่แล้ว +1

    Sir please provide us to pdf & image of how toh rest pcb and all sitting

  • @user-bq7hs2qy2p
    @user-bq7hs2qy2p ปีที่แล้ว +1

    Sand pdf sir vrv3 mode satting

  • @noelreyes2771
    @noelreyes2771 2 ปีที่แล้ว +1

    Sir we changed ah bord from ah single deep switch to a new board double deep switch sir can't you please help me how to install this.sir this is the model RXMQ8AYL VRV4

    • @BonMj
      @BonMj  2 ปีที่แล้ว

      I need to check.
      I only got RXYQ, RXQ, RZYQ, RZUR, RXUQ,

  • @allanacebartican7715
    @allanacebartican7715 2 ปีที่แล้ว +1

    Can you help me for PJ error vrv3 but install of sub parts accu Fan pcb 2 pcs. For master and 2 pcs. For Slave.. I also replace accu main pcb with correct dip switch settings

    • @BonMj
      @BonMj  2 ปีที่แล้ว

      Check inverter and fan driver
      Any wire connections wrong.
      PJ is improper combination between inverter and fan driver

  • @johnnyroxannebautista2063
    @johnnyroxannebautista2063 2 ปีที่แล้ว +1

    Sir Bon i just notice that
    red to black is 96 ohms
    red to white is 5 mega ohms
    what about white to black?
    is there a resistance reading fo that?

    • @BonMj
      @BonMj  2 ปีที่แล้ว

      Red Black = 96K ohm
      Red white = 5M ohm
      Normally white and black i never measure, next time i get the reading in the video too.

    • @johnnyroxannebautista2063
      @johnnyroxannebautista2063 2 ปีที่แล้ว +1

      @@BonMj thanks sir Bon.

  • @DanielRomero-cu1ht
    @DanielRomero-cu1ht 2 หลายเดือนก่อน +1

    Hola será q me pueden ayudar no consigo la configuración de los ds de la placa a1p. Vrv4 RXYMQ8AY1. NO VINO con el papel y no los consigo

    • @BonMj
      @BonMj  หลายเดือนก่อน

      Your email?

  • @uyexdu4646
    @uyexdu4646 ปีที่แล้ว +1

    Sir bon how are you

    • @BonMj
      @BonMj  ปีที่แล้ว

      I m good.Thanks bro

  • @VinodKumar-ix7rt
    @VinodKumar-ix7rt ปีที่แล้ว +1

    thans sir do you have any group

    • @BonMj
      @BonMj  ปีที่แล้ว

      FB

  • @tabresztabu562
    @tabresztabu562 2 ปีที่แล้ว +1

    Hi brother

    • @BonMj
      @BonMj  2 ปีที่แล้ว

  • @Mj-iu6yx
    @Mj-iu6yx 2 ปีที่แล้ว +1

    Hi Bon, how do you recognise how much the reading of thermistor or sensor should be, tq

    • @BonMj
      @BonMj  2 ปีที่แล้ว

      16K ohm(temperature sround 30°c?)

    • @Mj-iu6yx
      @Mj-iu6yx 2 ปีที่แล้ว +1

      @@BonMj one more thing, where can I get the vrv combination, what is the resources, thank you.

    • @BonMj
      @BonMj  2 ปีที่แล้ว

      @@Mj-iu6yx from manufacture

    • @Mj-iu6yx
      @Mj-iu6yx 2 ปีที่แล้ว +1

      @@BonMj hi Mr Bon, I need to do troubleshooting on cassette, the problem is, after working for 2 hours, the aircon causes to NCB trip, what do you think the problem is, please help me on this, thank you so much.

    • @BonMj
      @BonMj  2 ปีที่แล้ว

      @@Mj-iu6yx check compressor ampere. May be over current or wire poor contact,also can be MCB got problem

  • @velikarakaya8620
    @velikarakaya8620 ปีที่แล้ว +1

    Merhaba Daikin Vrv 4 error L1_U3 veriyor
    Problemi nasıl çözülür

    • @BonMj
      @BonMj  ปีที่แล้ว

      Check inverter pcb,fan motor, compressor

  • @shadowtv7814
    @shadowtv7814 2 ปีที่แล้ว +1

    Sir bon can i apply in your company im filipino

  • @mohdmaqsoodshaikh5234
    @mohdmaqsoodshaikh5234 2 ปีที่แล้ว +1

    Sir Daikin vrv3 salev1 on but master unit not working salev on continue but master not on sir rigen on errors no problem but master unit not start

    • @BonMj
      @BonMj  2 ปีที่แล้ว

      Why master not working? Error?

  • @noelreyes2771
    @noelreyes2771 2 ปีที่แล้ว +1

    Sir how to set double deep switch to ah new board?

    • @BonMj
      @BonMj  2 ปีที่แล้ว

      Follow the list.
      This list inside new pcb box

    • @noelreyes2771
      @noelreyes2771 2 ปีที่แล้ว +1

      @@BonMj sir there's no list inside the box only pcv sir if it's ok too you can't I get your email.add so that I can't sent it on your messenger

    • @BonMj
      @BonMj  2 ปีที่แล้ว +1

      @@noelreyes2771 bonmj81@gmail.com