Change voltage settings of growatt inverter by shine phone application

แชร์
ฝัง
  • เผยแพร่เมื่อ 14 ต.ค. 2024
  • Normally, when there will be fluctuation in grid side voltages. No one can predict when voltages will increase or decrease but when increases inverter will go into error mode " AC V outrange" because standard voltage setting will fixed in manufacturing unit.
    To avoid this error, make sure before changing voltages check grid voltages in acdb by turning off inverter. If everything looks fine then for
    1phase :
    Low Voltage : 170v
    High voltage: 280v
    3phase :
    Low voltage :320v
    High voltage :480v
    Low frequency : 47hz
    High frequency : 52hz

ความคิดเห็น • 37

  • @moosasyed1011
    @moosasyed1011 2 หลายเดือนก่อน +1

    Brother. After 20th June, my inverter power output is fluctuating so much, sometimes even goes to standby mode. It used to produce 65kwh per day on sunny days (model 10kt3lx) with 11kw panels. But now after every few minutes it goes from producing 8kw to 2kw then 3kw then 0kw then again 6kw... Etc and sometimes error history show AC frequency out of range. It already is 47.5 to 52.6 something but now total output on sunnay day is max 35-40 kwh. I m very concerned, please help. Should I reset? It all happened that on 1st day I got Relay Fault error 405. But after restarting it worked but since then this is happening

    • @Gosach796
      @Gosach796  2 หลายเดือนก่อน +2

      @@moosasyed1011 if inverter fall into error mode then it will effect the generation. It is better to contact ur solar installer and check earthing properly . As u mentioned that error is relay fault it means it is telling that ac side earthing is having issues. Check ac side Neutral to ground voltage value how much it is showing in multimeter. It should be below 5v

  • @dariuszdrogowski4168
    @dariuszdrogowski4168 หลายเดือนก่อน

    Hi, where i can find a production date? I think i have to decipher serial bimber, but how?

  • @antongeospl
    @antongeospl 2 หลายเดือนก่อน

    I have installed 3phase 25KW. Afternoon - During peak hours the inverter stops and restarts to recover continuously giving only half output (10kw to 18kw). Then production runs normally with minimal downtime. This problem occurs when 252v is available in a single phase during peak hours. Please specify the parameter setting the changes for this purpose

  • @Noor-vr4xj
    @Noor-vr4xj 3 หลายเดือนก่อน

    My growatt ongrid 10kv inverter has 14 panels of 580 watt attached which is 8kv system in total. But it's only producing 20 to 23 units per day instead of it should actually produce more than 40 units per day. Please guide what settings should I fix or what should I do?

    • @Gosach796
      @Gosach796  3 หลายเดือนก่อน

      @@Noor-vr4xj plz check any shadow is there or not on panels, panels were clean or not, panel to panel looping, date and time setting in inverter

    • @chillbanda3157
      @chillbanda3157 3 หลายเดือนก่อน

      Is working ok now?

  • @ABDULLAHILYAS00
    @ABDULLAHILYAS00 หลายเดือนก่อน

    In my Area Grid voltages 260+ maximum 270 but My Gro watt 10kw giving error when Voltages up to 260 how i can fix ?😊

    • @Gosach796
      @Gosach796  หลายเดือนก่อน

      @@ABDULLAHILYAS00 contact Growatt engineer he will increase voltage settings but even though same issues exists then u have to contact grid people and ask to reduce voltage levels

  • @waleedmalezai
    @waleedmalezai 3 หลายเดือนก่อน

    Bro i have Growatt 10 KV Inverter with 3 phase electricity meter it works fine but after 2 PM grid voltage falls to 170 to 180 and inverter trips and shows error 300 AC Voltage Outrage is there any solution?

    • @Gosach796
      @Gosach796  3 หลายเดือนก่อน

      @@waleedmalezai as it is 3phase inverter, grid side phase to phase voltage should be balanced and should be with in range . It should not be above the range or below the range. In ur case it is below the range. For this u have to contact grid people . Growatt engineer can't do anything for this grid side issue

    • @waleedmalezai
      @waleedmalezai 3 หลายเดือนก่อน +1

      @@Gosach796 ok thanks bro

    • @Gosach796
      @Gosach796  3 หลายเดือนก่อน

      @@waleedmalezai subscribe to the channel if u like the content bro

    • @waleedmalezai
      @waleedmalezai 3 หลายเดือนก่อน

      @@Gosach796 subscribed.
      I checked settings of my growatt inveter “set grid voltage lower limit” is 332.5 should i change it to 320 or not?

    • @Gosach796
      @Gosach796  3 หลายเดือนก่อน

      @@waleedmalezai no use bro issue is in grid side

  • @roz6829
    @roz6829 3 หลายเดือนก่อน

    sir please advise me i have growatt SPH 10KW 3 Phase but now show anything correct as u show the list its not show me please advise

    • @Gosach796
      @Gosach796  3 หลายเดือนก่อน

      This isnfor on grid inverter . For your type of inverter model contact regional growatt service engineer. If possible if I get the data i will post you

    • @roz6829
      @roz6829 3 หลายเดือนก่อน

      @@Gosach796 sir its hybrid 10kw SPH TTLL3B3BHH--UUP

  • @chillbanda3157
    @chillbanda3157 3 หลายเดือนก่อน

    I have 3kw on grid solar system but it generates only 4 unit per day what to to ?

    • @Gosach796
      @Gosach796  2 หลายเดือนก่อน

      @@chillbanda3157 contact ur solar installer for this issue

  • @musicfeelsfmlines47
    @musicfeelsfmlines47 2 หลายเดือนก่อน

    My growatt showing 405 relay error...from past 6 months....i have done everything but still no solution

    • @Gosach796
      @Gosach796  2 หลายเดือนก่อน

      @@musicfeelsfmlines47 have to check earthing thoroughly mainly ac side neutral to earth should be below 5v

  • @roz6829
    @roz6829 3 หลายเดือนก่อน

    i want to shear with you my growatt if you can set please its SPH 10KW

    • @Gosach796
      @Gosach796  3 หลายเดือนก่อน

      @@roz6829 plz share I will try to change

  • @ashuagarwal9449
    @ashuagarwal9449 3 หลายเดือนก่อน

    Hi, plz tell the setting for three phase parameter

    • @Gosach796
      @Gosach796  3 หลายเดือนก่อน

      For 3phase
      high voltage will be 480v and low voltage will be 320volts
      High frequency will be 53,low frequency will be 47

  • @swarajmankar
    @swarajmankar 2 หลายเดือนก่อน

    My growatt datalogger does not reconnect to internet everyday in morning.. i have to go and remove dattalogger and reinstall it then it starts working tried both methods of connecting.. what is the issue?

    • @Gosach796
      @Gosach796  2 หลายเดือนก่อน

      @@swarajmankar what is the network of ur wifi?

    • @swarajmankar
      @swarajmankar 2 หลายเดือนก่อน

      I just shifted from channel 8 to channel 6 2.4ghz lets see tomorrow.. thanks for ur help

    • @swarajmankar
      @swarajmankar 2 หลายเดือนก่อน

      I tried but it didn’t work also my data logger is not having battery and battery holder is missing on the pcb why?

  • @ashirwadhospital.vinchiya3451
    @ashirwadhospital.vinchiya3451 3 หลายเดือนก่อน +2

    Good work

  • @ReemaWahab
    @ReemaWahab 3 หลายเดือนก่อน

    Hi, growaat 10kw,3 phase settings please

    • @Gosach796
      @Gosach796  3 หลายเดือนก่อน +1

      For 3phase
      high voltage will be 480v and low voltage will be 320volts
      High frequency will be 53,low frequency will be 47

  • @suntech18
    @suntech18 3 หลายเดือนก่อน

    My growatt not connecting to internet

    • @Gosach796
      @Gosach796  3 หลายเดือนก่อน

      Didn't understood ur issue plz elobrate the issue