80% Goodman Furnace - Furnace Won't Light | Shop Troubleshooting (Gas Valve outlet pressure too low)

แชร์
ฝัง
  • เผยแพร่เมื่อ 31 พ.ค. 2024
  • My co-worker has decided to put problems into the units we have installed in the shop. I guess my part is to go out and see if I can use my own troubleshooting "teachings" to figure out and properly diagnose the issue.
    This is the first round of problems and it happens to be on a 80%, single stage, Goodman furnace. We have it set up on a natural gas supply line. There isn't really anything fancy with the unit. We are just looking at diagnosing the furnace today and maybe the a/c sometime in the future. I plan on trying to put out one of these types of videos every week but something always happens to that plan. I hope you learn the generic sequence of operation for a furnace and are able to use it in your service calls.
    I know that we are on the tail-end of the winter season but there will be a few of these videos coming up and if nothing else it will serve as a reminder for someone in the next heating season. I hope you enjoy.
    00:00 Intro
    04:22 Finding the Problem

ความคิดเห็น • 104

  • @jdub976
    @jdub976 6 หลายเดือนก่อน +5

    I know nothing about furnaces but was able to figure out my own problem last night. No click from gas valve. Found condensate clogged and would not let pressure switch close with the water backed up. These simple steps really do help figure out basic operations. Cleared and drained the clog I have heat now thank you.

    • @johnjennings487
      @johnjennings487  6 หลายเดือนก่อน

      Awesome. Glad to hear you fixed it.

    • @Jack51971
      @Jack51971 2 หลายเดือนก่อน

      Condensate clogged? What is that?🤔

  • @bills6946
    @bills6946 8 หลายเดือนก่อน +11

    If you don’t get ignition of burners, you don’t check gas pressure first. You check voltage at the gas valve at the moment of ignition. No voltage, bad board. Voltage present? Then check for gas pressure and suspect a bad valve.

    • @johnjennings487
      @johnjennings487  8 หลายเดือนก่อน +2

      Different techniques maybe but we hope to get to the same place in troubleshooting down to the root cause.

    • @miltlance3654
      @miltlance3654 6 หลายเดือนก่อน +1

      Adjust your camera. We can't see s#¡+ when you adjust/check had pressure.

    • @miltlance3654
      @miltlance3654 6 หลายเดือนก่อน +1

      Also, in your notes you show are way too brief

    • @DetroitDieselMMA
      @DetroitDieselMMA 6 หลายเดือนก่อน +3

      I had a similar.problem but found the propane copper line outside feeding the unit was crimped ..hence low pressure..it builds up and works for a while then won't work next time a call for heat comes in..

    • @johnjennings487
      @johnjennings487  6 หลายเดือนก่อน +1

      I had a terrible camera and even worse cameraman operating it! It is under new management now...

  • @fred306801
    @fred306801 4 หลายเดือนก่อน +1

    Not everyone can teach but this guy seems to be very good at it. Most everything I have learned I have learned on my own. Just saying I do not know a whole lot. I have watched many videos here on youtube. Mostly how to videos, it seems the hardest thing about fixing anything is tracking down what is wrong. Seems so many things can cause the same problem. And when you are not sure what to look for you end up buying parts that you do not need, and it can get really expensive. This list of what should happen next and what to look for is a must know. Wish I had seen this video before I started screwing around with my POS furnace. At first, I thought it was the flame sensor. On this unit the flame sensor and ignitor are made together. I did not know the ignitor was so fragile. As I was cleaning the flame sensor I brushed against the ignitor, and it fell apart. And the local parts house wants $106 for a new one. Now I am thinking it may be the gas valve. Just like in this video the ignitor starts to glow and then Nothing. No flames, just shuts down. Once the new parts arrive and I get them installed I can get my voltmeter out and start doing some checking.

    • @johnjennings487
      @johnjennings487  4 หลายเดือนก่อน

      Never heard of that brand...POS? Must be a new one! 🤣

  • @laurenschlicht7031
    @laurenschlicht7031 5 หลายเดือนก่อน +2

    Great video. Now I can fix myself and not have a $400 service call. The flame sensor rod apparently gets covered in soot and stops working in 3-5 years (imaging my surprise when my 3 year old brand new furnace wouldn't work), As an electrical engineer who designs semiconductors - it is a major design flaw by Goodman! So if the furnace start then stops - check the Flame sensor first!

    • @johnjennings487
      @johnjennings487  4 หลายเดือนก่อน

      You might have to do a collaboration with them to develop a better flame sensor!

    • @frankjones3073
      @frankjones3073 หลายเดือนก่อน +1

      $400? Where do live? Beverly Hills?

    • @johnjennings487
      @johnjennings487  หลายเดือนก่อน

      Could be Malibu but honestly when you pay a $100 just to have someone show up it could get to be $300 to 400 easy.

  • @bills6946
    @bills6946 8 หลายเดือนก่อน +6

    The whole key to accurately troubleshooting, is to remember the full sequence of operation. Don’t just replace parts . Understand the reason the furnace isn’t working and let your training and experience kick in.

    • @johnjennings487
      @johnjennings487  8 หลายเดือนก่อน

      100% couldn't agree more. Getting that sequence down is and has to be the most critical thing. Without it, just like you said...just changing parts. I had a young lady who works in the field here locally tell me about a job she was on and during the story she said "cause that is the way my supervisor does it". When she paused I asked her if she knew why he did "whatever" because if you don't then you are just memorizing it and not understanding it. Good point...I like it!

  • @daniel64697
    @daniel64697 5 หลายเดือนก่อน +2

    Beautiful video, well done. One of thee best videos for beginners/technicians out there.

    • @johnjennings487
      @johnjennings487  5 หลายเดือนก่อน

      Thank you. I appreciate it.

  • @beverlydixon6947
    @beverlydixon6947 2 หลายเดือนก่อน +1

    Omg new homeowner blues. This language I don’t speak!!

    • @johnjennings487
      @johnjennings487  2 หลายเดือนก่อน

      It isn't too bad! But definitely some learning involved.

  • @clovertechdev4243
    @clovertechdev4243 ปีที่แล้ว +3

    Great chronological thought of sequence. It would be nice if you can show us how to adjust the outlet gas pressure valve.

    • @oshitomaha
      @oshitomaha 7 หลายเดือนก่อน +1

      Exactly… like why not show that part? Lol

    • @johnjennings487
      @johnjennings487  7 หลายเดือนก่อน

      My bad, i'll get it in the next one!

    • @bradeskysantos9598
      @bradeskysantos9598 6 หลายเดือนก่อน

      True 🤦🏻‍♂️

  • @onerbfromtn4320
    @onerbfromtn4320 ปีที่แล้ว +1

    Field tech in different field - my jumpers are numbered 1-6 (I keep 6 in hand with wire stickers on them) and all have a 1/2" x 3" fire resistant, fluorescent yellow/green fabric tag with an embroidered "Jumper" in bright red on them fastened in the middle of my jumpers. I use the little tool bag system in my kit, and they have their own little bag. When putting my tools up, I set the jumper bag out and count them in while in use, count them out when done, verified 6 of 6 when putting tools up. Had a forner Navy electrician share that with me, based off of the "Remove Before Flight" tags on the carrier aircraft. I bit much, I know - but I work on some really expensive systems some of which have incorporated safety systems in them also so I'm a bit paranoid. Thanks for the video.

    • @johnjennings487
      @johnjennings487  ปีที่แล้ว

      That's pretty awesome if I may say so. We all have our ways and I try to pick up something from everyone. Something good to do or something bad not to do. I appreciate the input. Sounds like something good.

  • @simmonsjr25
    @simmonsjr25 2 ปีที่แล้ว +2

    It looks like something someone taught us in our first year. That sounds about right, sir.

    • @johnjennings487
      @johnjennings487  2 ปีที่แล้ว

      Don't forget about furnaces. I am a lttle late putting these out but better late than never I guess.

  • @adeptheatingair
    @adeptheatingair ปีที่แล้ว

    great video I love the fieldpiece Manometer.

    • @johnjennings487
      @johnjennings487  ปีที่แล้ว

      Thanks. It is a good manometer. Especially with the pressure switch tester.

  • @josuevazquez8394
    @josuevazquez8394 ปีที่แล้ว +1

    I like using a piece of ziptie and jam in into the doorswitch to keep it closed, quick and easy. It alsolets you put the door back on without shutting off the furnace

    • @johnjennings487
      @johnjennings487  ปีที่แล้ว

      I think I have heard of that from someone. I had someone take a screw and "lightly thread" it in...might as well buy the Supco door switch magnet!

  • @repairman4life362
    @repairman4life362 2 ปีที่แล้ว +1

    Good video for the beginner thanks for sharing Cheers

  • @robertc.6441
    @robertc.6441 2 ปีที่แล้ว +2

    Very informative!

  • @soloch69
    @soloch69 2 ปีที่แล้ว +1

    Great video like always thank you 🙏🏻

  • @aux1z11
    @aux1z11 ปีที่แล้ว +2

    my goodman 90% ran out of propane in the spring so I left it empty all summer and a few days ago I got propane delivered and the furnace wouldn't light but everything else seemed to work and the light was blinking code one so looked that up and couldn't get a clear answer so I was thinking the gas valve might have something wrong with it but I didn't have pressure checker so few days go by and watching all kinds of videos on it and go try looking at it again and decide to pull off the gas line to the valve and turned the knob back on and nothing came out so then I knew what it was , the idiot that delivered the propane forgot to turn the valve back on on the tank, but then again he was probly in a hurry to get out of here as I have 4 attack roosters that run loose and go after anyone who inters my property and a barking dog inside the fence. so it fired right up after that and learned alot about my furnace.

    • @johnjennings487
      @johnjennings487  ปีที่แล้ว +1

      I needed this...thanks for sharing. I know that 1 attack rooster is enough so 4 is definitely something to fear. I once ran a call and the customers furnace wouldn't light either...long story short...she hadn't paid her bill in over a year and they took her entire natural gas meter. I stubbed my toe on the gas company line as I was walking around the house. She said "oh yeah, I forgot about that bill!"

  • @FirstUPdaGREAT
    @FirstUPdaGREAT 9 หลายเดือนก่อน +1

    Looks like the same one I have in my attic. My ac suddenly isant working 😪 well, now my wife is telling me my thermostat was off so it’s probably not the unit.

    • @johnjennings487
      @johnjennings487  9 หลายเดือนก่อน

      Listen to your wife! At least at first...

  • @ittech7967
    @ittech7967 7 หลายเดือนก่อน

    I have Trane XB80 f.a.g.heater flashing codes say bad hight limit but the 3 thermostats have continuity & it wont fire up, Help!

  • @girlface5943
    @girlface5943 3 หลายเดือนก่อน

    I need to know how to change the igniter on the first Goodman you worked on

    • @johnjennings487
      @johnjennings487  3 หลายเดือนก่อน +1

      A lot of the Goodman ignitor are the same. They are held in with a 5/16 inch hex head screw. Just unplug the ignitor at he plug that is about 6 inches away from the ignitor and unscrew that screw with a nut driver. Should be fairly easy.

    • @girlface5943
      @girlface5943 3 หลายเดือนก่อน

      @@johnjennings487 if the igniter doesn't even light up and the gas is running. I'm hoping that's the problem

    • @johnjennings487
      @johnjennings487  3 หลายเดือนก่อน +1

      @girlface5943 very good possibility. The ignitor should definitely be glowing before the gas valve opens to turn on the gas and if the gas valve does open then the board must be thinking it already had the ignitor ready. If it was working before and now it isn't then it is very possible. But there may be another issue. Hard for me to day without being there of course. For the cost of the ignitor, it is probably the cheapest route to start with if you DIY.

  • @ashleygreen2738
    @ashleygreen2738 หลายเดือนก่อน

    Goodman gms80 furnace. Furnace randomly turns on blower fan. Furnace thermostat (nest smart) set to system off. Still randomly turns on at times. Pulled the nest off the mount. It still will run the fan randomly. Any suggestions?

    • @johnjennings487
      @johnjennings487  หลายเดือนก่อน

      Maybe the fan is set to "circ" at the tstat so it comes on sometimes? Or maybe when it happens again, go check the furnace board for a error code flashing? If the furnace board is turning on the blower it is probably trying to get your attention so you will notice an error code.

    • @ashleygreen2738
      @ashleygreen2738 12 วันที่ผ่านมา

      Thanks for the message back!! I shut the system off at the switch for about an hour many weeks ago and it didn't turn back on for weeks and weeks then today randomly it ran the fan for about 15 mins then shut off. If I pull the nest right off the wall it still runs. And the nest system is set to 100% off as it's been mild here in the Midwest no reason for heat or ac. I did pull the panel off the furnace and there was no error codes. I got to it right before it randomly shut off again.

  • @mark33545
    @mark33545 5 หลายเดือนก่อน

    Why not use a spring clip for the door sensor? Then there is no chance to leave it bypassed with tape or with the jumper. You will hit the clip when you put the door back on.

    • @johnjennings487
      @johnjennings487  5 หลายเดือนก่อน +1

      I can see that working depending in what shape/size it is...i am gonna have to look into that method.

    • @mark33545
      @mark33545 5 หลายเดือนก่อน

      awesome, thanks for the great videos. learning a lot. I actually have that 80% goodman in the video, is it possible to take the burners out to clean without having to break the union and remove the entire gas manifold? I am trying to learn enough to do my own regular maintenance. My previous house was a steam boiler and i learned to maintain it well but a completely different beast. thanks!@@johnjennings487

  • @onemoreboat
    @onemoreboat ปีที่แล้ว

    Just curious where you find the limits for all the checks that you do.

    • @johnjennings487
      @johnjennings487  ปีที่แล้ว

      Just looking up different manuals, sometimes they are in the installation manual and sometimes it is in a product specifications manual. I look up parts manuals and get things like temperature switch ratings, etc. In some cases I don't look up the make of the whole unit (like Goodman or Carrier) I will look up a specific part model number. So say for something like a gas valve in a Goodman unit, I might look up the Honeywell gas valve model # "XYZ" that is actually in it. But basically looking info up but sticking with manufacturers info.

  • @abrahamfawaz5080
    @abrahamfawaz5080 ปีที่แล้ว +1

    is this sequence for all furnaces? like carrier lennox etc.

    • @johnjennings487
      @johnjennings487  ปีที่แล้ว

      It is a generic sequence for gas furnaces of most every brand. Some minor tweaks on timings between them maybe...

  • @vernonsalzman2454
    @vernonsalzman2454 ปีที่แล้ว +2

    This is exactly the problem I need to fix, but unfortunately i had a view of the bottom of the furnace and not the view of what you did to fix the problem, come on. Your sequence of troubleshooting led me the problem at least.

  • @emanuels.6541
    @emanuels.6541 ปีที่แล้ว

    If the valve was new, wouldn’t come somewhat set to 3.5 in of WC straight from the factory?

    • @johnjennings487
      @johnjennings487  ปีที่แล้ว +1

      Seems like no matter how much I think I can be "reasonably sure"...I still have to check it! Not saying that I am/have aleays been perfect, but I learned real quick that if you want to know for sure - you have got to check for yourself.

    • @marioluzano7178
      @marioluzano7178 ปีที่แล้ว

      @@johnjennings487 how about for LPG? what would be the inlet and outlet pressure? where to connect the hose for the manometer on the gas valve?

    • @johnjennings487
      @johnjennings487  ปีที่แล้ว

      Should be a "boss plug" on the inlet side of the gas valve and also the outlet side of the valve. Depending on the model of valve it takes a larger hex wrench (3/16) or a smaller (3/32). I think I got those sized right! For most gas valve I have seen it tells you that it should be no more than 14" W.C. (1/2 psi) inlet to the valve from a regulator and the outlet is generally 10 to 11" W.C.

    • @bills6946
      @bills6946 8 หลายเดือนก่อน

      Usually comes set a little higher so it works all the time. You must check it and adjust to the manufacturer’s label on the furnace. It tells you the correct water column. Don’t guess. Too high and you waste gas and overheat the heat exchanger. Too low, and it may not ignite every cycle.

  • @RoyalCanadianMountedGambler
    @RoyalCanadianMountedGambler 2 หลายเดือนก่อน

    My good man is weird… if I power cycle it the furnace will run but once it needs to come back on to reheat house induce motor comes on and clicks but nothing… any advice?

    • @johnjennings487
      @johnjennings487  2 หลายเดือนก่อน

      After the inducer motor comes on, it should generate enough draft (through the heat exchanger) to close the pressure switch. If that switch isn't closing then you could have a few issues. Bad inducer motor wheel, bad pressure switch, clogged flue pipe, crack in your heat exchanger, etc. Tough to say from here. The 'click' is curious to me. If that click is the gas valve then that changes everything. Do you see a glow from the ignitor or hear a spark "sparking" before the click?

  • @user-fy8ko6ur3b
    @user-fy8ko6ur3b 7 หลายเดือนก่อน

    Hello, I had to turn my main gas off and now I need to turn my furnace back on. How do I know if I need to manually light my pilot? How do I turn it back on?

    • @johnjennings487
      @johnjennings487  7 หลายเดือนก่อน

      I haven't seen a whole lot of pilot lights on furnaces in a while. You can look at the main gas valve and it is say ON and OFF then you don't have a pilot light! It will say OFF, Pilot, and ON. If you have a pilot then you will have to hold down the button on the gas valve while you light the pilot and let the thermocouple warm up. If you got a furnace made in this century it likely doesn't have a pilot though.

  • @roqueherrera2692
    @roqueherrera2692 ปีที่แล้ว +1

    How about heat pump wiring wit heat strips at air handler and thermostat

    • @johnjennings487
      @johnjennings487  ปีที่แล้ว

      Sorry. Don't have that one yet. I have a couple planned for a month or so. One just a plain heat pump and one with an outdoor thermostat installed.

  • @googlereviewsyt
    @googlereviewsyt 5 หลายเดือนก่อน

    If anyone can answer this please. Ever since we got in the house, the air feeder, never had a filter. I put one and after that the problem started,the ignition turns on, the burners clicks but doesn't stays on, it keeps attempting to turn on, I removed the filter feeder. Not even 1 hour later but now still does it, the only way it starts and still on is leaving it off for 10 minutes and then starts fine. Is the filter incident a coincidence? Is an air flow problem if that exists? Or it can be the little green build up around the copper fitting? Thanks in advance

    • @johnjennings487
      @johnjennings487  5 หลายเดือนก่อน

      The filter kinda seems like a coincidence. An airflow issue would probably not allow the unit to even get that far in the startup sequence after an initial starting. BUT...if you never had a filter before you may indeed have some issues with the evaporator coil being dirty because if you don't use a filter the coil will act as one! Maybe try to see what error code the circuit board is flashing. That would probably be the beat place to start.

  • @roosterroo2794
    @roosterroo2794 5 หลายเดือนก่อน

    I just installed a new goodman furnace it is giving me a code of 7P1. Any suggestions on what could be my issue

    • @johnjennings487
      @johnjennings487  5 หลายเดือนก่อน

      Got a model.number for it?

  • @ronzek3207
    @ronzek3207 ปีที่แล้ว

    What was the amp draw on blower motor?

    • @johnjennings487
      @johnjennings487  ปีที่แล้ว

      That is a X13 blower motor. I think the amp draw was something in the 1.5 to 1.75 amp range.

  • @dagripper77
    @dagripper77 6 หลายเดือนก่อน

    I have the exact same unit. It will light and the fan will start blowing then it just shuts off after about 2 mins.

  • @armandogomez1934
    @armandogomez1934 ปีที่แล้ว

    How do you replace the gas valve?

    • @johnjennings487
      @johnjennings487  ปีที่แล้ว +1

      Short version...cut off the gas and remove wiring, use 2 pipe wrenches to break the union that should hopefully be in the main line going into the gas valve - once done then use same wrenches to take the gas line out of the inlet to the gas valve and repeat to take gas valve off of the manifold piping. Gas valve is now out! Make sure you look at the new valve for the flow direction arrow that tells you which way to put it in correctly. Basically it is a reverse process now but with a little pipe dope/thread sealant or gas rated thread tape on the pipe threads (not union though). Turn the gas on and check for leaks using liquid gas detector. If no leaks then let it run.

  • @CHRISTINARODRIGUEZ
    @CHRISTINARODRIGUEZ 3 หลายเดือนก่อน

    Furnace isn't working ATM and light is steady on but nothing is ignition or turning on at all

    • @johnjennings487
      @johnjennings487  3 หลายเดือนก่อน

      If it isn't blinking or the red led fashing a code then it sounds like it may not realize you want the heat on! Steady light on means it is most likely ready to turn on amd is waiting for the signal from the thermostat. This might sound crazy but make sure the thermostat is set to heat and has a set point higher than the room. Do you have an electrical test meter?

  • @margritski
    @margritski 6 หลายเดือนก่อน

    My red light is off completely which states control failure how do I check that ?

    • @johnjennings487
      @johnjennings487  6 หลายเดือนก่อน

      First things first, verify high voltage and low voltage to the board. I had one the other day that had an issue with a bad transformer (no 24v output) and the red light was not on because it didn't have that 24v power. Otherwise you just might have a bad board and need to replace it. But i would verify power before buying a new one.

  • @Jack51971
    @Jack51971 2 หลายเดือนก่อน

    So what was the problem? What did you replace? This exactly what the guy charged me $129 for nothing aweek ago. $129 to tell me I needed a new furnace. How did you solve the gas pressure issue? What did you change or replace?🤔

    • @johnjennings487
      @johnjennings487  2 หลายเดือนก่อน

      Replaced nothing. Only had to adjust the gas pressure higher using the adjustment screw on the gas valve itself. It is under thae brass looking cap with a flat head screwdriver slot. Took off the cap and there is a plastic adjustment screw underneath. I honestly haven't seen that problem very often but I guess it could happen on a brand new valve sent from the factory. Most of the time I change a gas valve it is not a perfect pressure for the output pressure and may need a slight adjustment but it is usually close.

  • @DannyObscura
    @DannyObscura 9 หลายเดือนก่อน

    Hey I know this is an older video but where does the filer go on this unit? Does it slide into the very bottom?

    • @johnjennings487
      @johnjennings487  9 หลายเดือนก่อน +1

      Sorry for taking so long. The furnaces son't necessarily have a filter rack for them to slide in like an air handler. Some furnace would have a spring/wire that would hook in place to hold a filter in the blower compartment but I haven't seen that in a while. Most furnaces I have seen had a separate filter rack attached to the furnace.

    • @DannyObscura
      @DannyObscura 9 หลายเดือนก่อน

      @@johnjennings487 no worries, thank you !

    • @TheItalianStallion13
      @TheItalianStallion13 4 หลายเดือนก่อน

      @@DannyObscura Did you ever find your filter rack? I have a Goodman Furnace not this model but a taller one with 1 panel and I can't seem to find a filter ANYWHERE. 8 years in this house and all I can find is the return air handler filter.

  • @ninganpgh
    @ninganpgh ปีที่แล้ว

    My 80%Goodman runs well, but the code F02 and 9H won’t go away, any help will be greatly appreciated!!!

    • @johnjennings487
      @johnjennings487  ปีที่แล้ว

      Do you have a model number? There are so many choices of furnaces out there...

    • @ninganpgh
      @ninganpgh ปีที่แล้ว

      @@johnjennings487
      GM9S801005CN thank you so much for your kindness to look into my problem.

    • @ninganpgh
      @ninganpgh ปีที่แล้ว

      Is that possible that these F02 and 9H are NOT error codes, instead they are just status codes? F02 for blower fan setting and 9H for single stage of gas heat?
      I paid for an online tech helper to make sure they are not an error codes, but the technician said he is not sure. This control board is Goodman’s newly commissioned integrated control. Just some of my thoughts, once again THANK YOU John !

    • @johnjennings487
      @johnjennings487  ปีที่แล้ว

      I just pulled the manual off of Goodman'a website. It does indeed look luke status codes the F02 seems to say that the fan is using the 2nd tap of the fan for its speed and the 9H is dealing with the singe stage heating...you sure you aren't a heating and air professional??!!

    • @johnjennings487
      @johnjennings487  ปีที่แล้ว

      I'll keep reading in the manual but I think you are right on the money. If I see anything that says different I'll let you know.

  • @chillios2222
    @chillios2222 7 หลายเดือนก่อน

    My Goodman will not light the gas , the emergency heat when the top door is closed

    • @johnjennings487
      @johnjennings487  7 หลายเดือนก่อน

      Is this a dual fuel system? Usually emergency heat and gas furnace don't go together.