HVAC: Commercial LAARS Natural Draft Hydronic Boiler Exhaust NIGHTMARE (LAARS Boiler Exhaust Danger)

แชร์
ฝัง
  • เผยแพร่เมื่อ 18 พ.ค. 2024
  • HVAC: Commercial Hydronic Boiler Natural Draft Exhaust NIGHTMARE (LAARS Boiler Exhaust Danger) HVAC (Heating, Ventilation, Air Conditioning) HVAC Exhaust / Boiler Natural Draft Exhaust Duct Troubleshooting / Boiler Exhaust / Emergency Service Call: Commercial Hydronic LAARS Boiler Troubleshooting / Boiler Maintenance / Boiler Cleaning / Boiler Training / LAARS Mighty Therm / HVAC Technician / HVAC Tech / HVAC Boiler Troubleshooting / HVAC Boiler Training / HVAC Boiler Maintenance / Commercial Boiler Danger
    Fieldpiece Dual-Port Manometer - SDMN5
    amzn.to/3weHeOx
    Inficon 718-202-G1 Combustible Gas Detector
    amzn.to/4bfQD7u
    UEI Flue Gas Combustion Analyzer
    amzn.to/3UnQeKA
    Big Blu Subzero Micro Leak Detector 1QT (Liquid Solution)
    amzn.to/4bh05Ym
    Big Blu Brush On Micro Leak Detector (Liquid Solution)
    amzn.to/3UxUqY9
    GoPro HERO8 Black (Camera Used In This Video)
    amzn.to/3q4FmEz
    Veto Pro Pac TECH MC
    amzn.to/3gURJyZ
    Hydrayne Air Blaster 2.0
    amzn.to/4dA0S8C
    EPAuto Socket Set
    amzn.to/4crx0e2
    Wire Brush for Drill Set
    amzn.to/3VX4HhO
    Big Blu Subzero Micro Leak Detector 1QT (Liquid Solution)
    amzn.to/4bh05Ym
    Fluke 902 FC HVAC True-RMS Clamp Meter
    amzn.to/39wvwiK​​
    Fieldpiece ADK7 Deluxe Silicone Test Lead Kit
    amzn.to/3VNYXDv
    Klein Tools ET600 Megohmmeter Insulation Tester
    amzn.to/409iNvu
    Supco M500 Insulation Tester/Electronic Megohmmeter
    amzn.to/42oy0ua
    Fluke 1AC-A1-II VoltAlert Non-Contact Voltage Tester
    amzn.to/3FcWElQ
    Fieldpiece JL3KR4 HVACR Charge Kit (Digital Gauges/Probes)
    amzn.to/3E4W0Fr
    Fieldpiece SPK2 Folding Pocket In-Duct Thermometer
    amzn.to/3mi8Fih
    Fieldpiece SPK3 Folding ROD Dual Temperature Thermometer
    amzn.to/3FbDufQ
    Milwaukee M12 2-Tool Combo Kit 2598-22
    amzn.to/3CtCRNC
    Milwaukee Cut 1 Dipped GLOVES L
    amzn.to/3s8H18O​
    Milwaukee 2351-20 M12 LED Stick Light
    amzn.to/3rVJKEK
    Milwaukee 48-22-1985 Fastback Hawk Bill Folding Knife
    amzn.to/3e53ygW
    Milwaukee 48-22-1500 Fastback Compact Folding Utility Knife
    amzn.to/3qazJkC
    Milwaukee 48-22-4041 Iron Carbide Core Large-Looped Jobsite Scissors
    amzn.to/32fxC6I
    Milwaukee 4932459097 Billet Torpedo Level
    amzn.to/30Dh6Nw
    Milwaukee Wide Blade Magnetic Tape Measure 16 FT
    amzn.to/3yEN7kL
    Milwaukee Fine Pt. Markers Black
    amzn.to/3e4fH5W
    Streamlight 66604 MicroStream USB 250-Lumen Rechargable Pocket Flashlight
    amzn.to/320XiEF
    Klein Tools 11-in-1 Screwdriver / Nut Driver
    amzn.to/3s3o8ql
    Klein Tools 32561 Multi-Bit Screwdriver / Nut Driver 6-in-1
    amzn.to/3e4ur4x
    Klein Tools 32807MAG 7-in-1 Nut Driver, Magnetic Driver
    amzn.to/321n4bW
    Klein Tools 600-4 1/4-Inch Keystone Cushion-Grip Screwdriver
    amzn.to/3J11hS1
    Klein Tools 32581 4-in-1 Electronics Screwdriver Set
    amzn.to/3yEj3WC
    Klein Tools LLK12 L-Style Hex Key Caddy Set 12-Piece (Metric/Sae)
    amzn.to/3yRUiGJ
    Yellow Jacket 18975 Charge Tool
    amzn.to/3J4pfvJ
    Yellow Jacket 60613 Service ratchet Wrench
    amzn.to/3E8iYeZ
    Yellow Jacket 19173 5/16" Female Quick Couplers x 1/4" Male Flare
    amzn.to/3q0TQ4M
    Cooper Bussmann BP-FP-2 Cartridge Carded Fuse Puller
    amzn.to/3e0USrY
    Crescent 2 Pc. X6 4-in-1 Black Oxide Spline Ratcheting SAE Wrench Set
    amzn.to/3qqKlw7
    Crescent 4" Adjustable Cushion Grip Wrench
    amzn.to/3J4qsmL
    Knipex 09 08 240 SBA 9.5-Inch Insulated Ultra-High Leverage Lineman's Pliers (1000v)
    amzn.to/30EQmw5
    Knipex 09 11 240 9.5-Inch Ultra-High Leverage Lineman's Pliers with Fish Tape Puller and Crimper
    amzn.to/3H9iYAu
    KNIPEX Tools - Long Nose Pliers With Cutter, 1000V Insulated
    amzn.to/3e3IEi7
    KNIPEX Tools - Long Nose Pliers With Cutter
    amzn.to/3gUSE2i
    KNIPEX Tools 98 62 02, Flat Nose Plastic Pliers 1000V Insulated
    amzn.to/3p6lFsZ
    KNIPEX - 74 08 200 - High Leverage Diagonal Cutters, 1000V Insulated
    amzn.to/3mh8K5U
    KNIPEX - 74 01 200 Tools - High Leverage Diagonal Cutters
    amzn.to/3F1VScb
    KNIPEX Tools - Cobra QuickSet Pump Pliers, 1000V Insulated
    amzn.to/3sftr5Q
    KNIPEX Tools 3 Piece Cobra Pliers Set
    amzn.to/3FbRwy7
    KNIPEX Tools Pliers Wrench 3-Piece Set
    amzn.to/3nnRLfW
  • วิทยาศาสตร์และเทคโนโลยี

ความคิดเห็น • 43

  • @JumpermanTech
    @JumpermanTech  2 หลายเดือนก่อน +10

    Thank you all for watching & commenting! You are all very much appreciated. We sealed the entire elbows because it was falling apart and it is only temporary. Better safe than sorry! The duct specialist I picked up parts from recomended 26 guage double wall but I will confirm with the manufacturer to confim as im hearing mixed opinions. Leave a comment if you know what should be here. Follow me on Instagram @JumpRmantech. Stay tuned for new videos every week🔧⚡️

    • @vadimk89
      @vadimk89 หลายเดือนก่อน

      I heard if you wrap painters tape around the duct it would make the mastic look cleaner

  • @SoundOfResistance
    @SoundOfResistance 2 หลายเดือนก่อน +5

    What a treat, two videos ❤

    • @JumpermanTech
      @JumpermanTech  2 หลายเดือนก่อน +1

      Every weekend I try to post 2 videos and have been for a while now. Thank you for watching! Glad you fond this as a treat. Glad you are studying and learning to become the best version of yourself. Take care 🔧⚡️

  • @Eddy63
    @Eddy63 2 หลายเดือนก่อน +2

    Never seen ducts crumble like that before ... Can't wait for the replacement ... Thx

    • @JumpermanTech
      @JumpermanTech  2 หลายเดือนก่อน +1

      Me neither! Scary stuff. Facts. That will be a MUST ASAP. Thanks for watching Eddy! 🙏🔧⚡️🤙

  • @stevencossaboon3237
    @stevencossaboon3237 2 หลายเดือนก่อน +3

    Nice work Jumper man.

    • @JumpermanTech
      @JumpermanTech  2 หลายเดือนก่อน

      Thank you & thanks for watching/commenting! 🔧⚡️🙏

  • @chris66b55
    @chris66b55 2 หลายเดือนก่อน +4

    The inspector that signed off on the original job should be fired immediately.

    • @JumpermanTech
      @JumpermanTech  2 หลายเดือนก่อน +1

      Facts! Clearly should have seen that. I don't know how they passed inspection upon commission. Been like this since day 1. Thanks for watching! 🔧⚡️

  • @chrissmith513
    @chrissmith513 2 หลายเดือนก่อน +4

    L o L You gotta be a guy of all trades in any business 😊😊😊

    • @JumpermanTech
      @JumpermanTech  2 หลายเดือนก่อน

      Haha thank you! Seems to be. I don't usually do duct work but I take of this entire building so I might as well get this done too! 😂 Seemed easy enough. Thanks for watching! 🙏🔧⚡️🤙

  • @genewheeler6320
    @genewheeler6320 2 หลายเดือนก่อน +4

    Great job bro

    • @JumpermanTech
      @JumpermanTech  2 หลายเดือนก่อน

      Thank you brother! 🙏🔧⚡️

  • @jrh86
    @jrh86 2 หลายเดือนก่อน +3

    Fantastic insight into yet another poor initial installation 💯👍👍👍

    • @JumpermanTech
      @JumpermanTech  2 หลายเดือนก่อน +2

      Thank you & facts! Poor install. Now we know why the bid was cheaper🤦‍♂️ Thanks for watching! 🔧⚡️

  • @robertsimpson1824
    @robertsimpson1824 2 หลายเดือนก่อน

    if you put the second piece of duct over the other one you can draw a straight line. keep the videos comming stay safe

  • @nicolerennie
    @nicolerennie 2 หลายเดือนก่อน +2

    incredible work 🤩

    • @JumpermanTech
      @JumpermanTech  2 หลายเดือนก่อน

      Thank you!! 🙏🔧⚡️

  • @zekenzy6486
    @zekenzy6486 2 หลายเดือนก่อน +1

    Great video. Thank you for sharing

    • @JumpermanTech
      @JumpermanTech  2 หลายเดือนก่อน

      Thank you! 🙏🔧⚡️

  • @coreyr8870
    @coreyr8870 2 หลายเดือนก่อน +1

    You have to be careful. Any running boiler will let co back from that common plenum. Hopefully you were working with all boilers that feed that plenum off

  • @mmorrison6775
    @mmorrison6775 2 หลายเดือนก่อน +1

    All that should be a minimum of 26-22 GA
    as long as your in a Mech Rm single is acceptable as long as you use 24 GA or heavyr

  • @renj6531
    @renj6531 2 หลายเดือนก่อน

    my guess would be since its single wall and due to the temperature difference between the hot exaust gas and cold basement in combination with exaust gasses being corrosive it was the perfect storm for this

  • @Practicing_HVACR
    @Practicing_HVACR หลายเดือนก่อน

    Make sure you start up your combustion analyser outside. The carbon monoxide auto zeros on start up so if you start it up in the mechanical room you may have CO but a reading of 0.
    It’s definitely not good for that pipe to have such large holes. 30 gauge is a thin but I would also suggest looking for possible causes of the corrosion. Typically it’s somehow related to condensation of the flue gases. Water inlet temperature could be too cold or an exhaust fan could be running pulling in flue gases for example.
    I wouldn’t worry too much about the flue piping not being sealed. The heat of the gases causes them to rise quickly and should actually place the flue in a negative pressure. Your combustion analyser should have a draft reading you can use to verify this. Sealing them can possibly cause too much of a draft although your draft hoods are meant to prevent this. Just a few things to look into and consider.
    As far as double wall goes, which is often called B vent, it’s usually used to give you a smaller clearance to combustibles. B vent must have 1 inch clearance but single wall needs 18 inches.
    Appreciate your videos! Not too many fellow commercial techs on TH-cam.

  • @JesseDoesHVAC
    @JesseDoesHVAC 2 หลายเดือนก่อน

    Get yourself the milwaukee shears

  • @hmrody
    @hmrody 2 หลายเดือนก่อน +1

    I would be interested in NY City code specifies on flues. Great video!

    • @JumpermanTech
      @JumpermanTech  2 หลายเดือนก่อน

      Facts. Can't believe this passed inspection. Thank you & thanks for watching! 🙏🔧⚡️

  • @ayoutubewatcher7009
    @ayoutubewatcher7009 หลายเดือนก่อน

    The issue I see is condensation.. either because low flue temps. Or because the room is not conditioned. As long as the installers follow the factory specs. for the flue pipe,, then there’s no room to complain. Now, the silver tape thing is completely unacceptable and the tech should be fired. The double wall should help though. Usually, when the heaters exhaust are manifolded, there’s an external exhaust motor/barometric system.

  • @emeliojuarez3617
    @emeliojuarez3617 2 หลายเดือนก่อน +1

    Shouldn't you have replaced the last elbow, it was falling apart. Temporary or not.

    • @JumpermanTech
      @JumpermanTech  2 หลายเดือนก่อน +1

      I agree. They are in terrible shape. Thanks for watching! 🔧⚡️

  • @c21meister
    @c21meister 2 หลายเดือนก่อน +1

    Jesus Christ it’s May and hall are still running heat calls?

    • @JumpermanTech
      @JumpermanTech  2 หลายเดือนก่อน

      These boilers are for hot water for the building so it needs to run all year. We do have some chilly nights here and there though. Thanks for watching! 🔧⚡️

  • @ILoveKittys78
    @ILoveKittys78 2 หลายเดือนก่อน +1

    😻💚💜💚

    • @JumpermanTech
      @JumpermanTech  2 หลายเดือนก่อน

      🙏💜🔧⚡️

  • @poohbear4130
    @poohbear4130 2 หลายเดือนก่อน

    Can’t imagine what the sheet metal guy’s are saying watching this?

  • @scottmaz4063
    @scottmaz4063 2 หลายเดือนก่อน +1

    And I was right 😂😂

    • @JumpermanTech
      @JumpermanTech  2 หลายเดือนก่อน

      Hacks bring you stacks!! Haha 🤙🔧⚡️

  • @KyleWithStyle7
    @KyleWithStyle7 2 หลายเดือนก่อน +1

    Furst

    • @JumpermanTech
      @JumpermanTech  2 หลายเดือนก่อน

      Let's gooo!! Thank you for watching! 🙏🔧⚡️

  • @ronnym1977
    @ronnym1977 2 หลายเดือนก่อน +1

    I got tired just watching this video.