WALK IN FREEZER SUPERHEAT TOO LOW

แชร์
ฝัง
  • เผยแพร่เมื่อ 5 ก.พ. 2025
  • This was a call on a walk in freezer that was not getting cold enough, i found that the expansion valve was not working properly and caused the superheat to get too low. I made a temporary adjustment and got the superheat higher until we can submit a quote to replace the valve.
    To support my videos please visit either of the links below
    For Patreon / hvacrvideos
    For Streamlabs streamlabs.com...
    TOOL LINKS
    FieldPiece JobLink probes amzn.to/2WfQTRI
    Samsung Tablet amzn.to/2EOYL1U
    Fieldpiece SC660 Wireless Swivel Clamp amzn.to/2JXji7I
    For Optimizing my videos I use Tube Buddy
    www.tubebuddy....
    Please consider subscribing to my channel and turning on the notification bell by clicking this link goo.gl/H4Nvob
    Social Media
    Facebook / hvacr-videos. .
    Instagram / hvacrvideos
    For any inquiries please contact me at hvacrvideos@gmail.com

ความคิดเห็น • 222

  • @DanO181919
    @DanO181919 5 ปีที่แล้ว +40

    I love how you look at the BIG picture. You are a very humble person and I admire that. Also, I like how you show the whole process in your videos. Keep the videos coming they are kick ass!!

    • @HVACRVIDEOS
      @HVACRVIDEOS  5 ปีที่แล้ว +2

      thanks bud,
      I will be going live on TH-cam this evening 8/19/19 @5:pm
      (pacific time) to discuss my most recent uploads and answer questions from
      TH-cam comments, the chat, and emails. Come check it out if you can th-cam.com/video/cFVJGl-KVEc/w-d-xo.html

    • @potienkalala5113
      @potienkalala5113 ปีที่แล้ว

      I like this video and explains

  • @JuanTodoli
    @JuanTodoli 5 ปีที่แล้ว +9

    TXV all the way in, all the way out, and back to the middle. Excellent procedure to (try to) clear the valve.👍

    • @HVACRVIDEOS
      @HVACRVIDEOS  5 ปีที่แล้ว

      I will be going live on TH-cam this evening 8/19/19 @5:pm
      (pacific time) to discuss my most recent uploads and answer questions from
      TH-cam comments, the chat, and emails. Come check it out if you can th-cam.com/video/cFVJGl-KVEc/w-d-xo.html

  • @dirk_diggler320
    @dirk_diggler320 5 ปีที่แล้ว +18

    Thanks for showing the flashing sight glass Chris.
    And I love the big picture diagnoses.
    I wish more techs used the same approach when diagnosing.
    My favorite is the guy who tells the customer it's going to be a quick fix cause its just a bad fuse. He acquires said fuse and to find a bad transformer or other component .....
    Customer will never have confidence in that tech again ...
    Thanks for making your videos public and sharing your knowledge and approach.

    • @HVACRVIDEOS
      @HVACRVIDEOS  5 ปีที่แล้ว +1

      I will be going live on TH-cam this evening 8/19/19 @5:pm
      (pacific time) to discuss my most recent uploads and answer questions from
      TH-cam comments, the chat, and emails. Come check it out if you can th-cam.com/video/cFVJGl-KVEc/w-d-xo.html

  • @jjjames5089
    @jjjames5089 5 หลายเดือนก่อน +1

    I enjoy your content just don't stop being detailed while you work explaining your thoughts process. Thanks

  • @shanebehm8251
    @shanebehm8251 5 ปีที่แล้ว +1

    Sooo many guys think that ice on the compressor head means that it's flooding back. Thanks for clearing this up!!👏

  • @flyinghigh5531
    @flyinghigh5531 หลายเดือนก่อน +1

    Nice work! I like the txv body’s with thread on power heads. The sporlan kit has saved me a lot.

  • @baladi921
    @baladi921 5 ปีที่แล้ว +9

    I've been binging your videos. Thank you for keeping the beer cold and the food fresh, plus even though I don't understand a lot of this I do understand about the smaller stuff you talk about. Thanks man.

    • @HVACRVIDEOS
      @HVACRVIDEOS  5 ปีที่แล้ว

      I will be going live on TH-cam this evening 8/19/19 @5:pm
      (pacific time) to discuss my most recent uploads and answer questions from
      TH-cam comments, the chat, and emails. Come check it out if you can th-cam.com/video/cFVJGl-KVEc/w-d-xo.html

  • @ΗλιαςΜπελος-σ1ψ
    @ΗλιαςΜπελος-σ1ψ 5 ปีที่แล้ว +2

    Good morning from Greece Chris.I have some castomers here that they have some junk equipment like this and it's a pain in the ass, but we're technicians and we have to fix them to,with the lowest price always! Keep on the good work my friend.

    • @HVACRVIDEOS
      @HVACRVIDEOS  5 ปีที่แล้ว

      Thanks for watching!
      I will be going live on TH-cam this evening 8/19/19 @5:pm
      (pacific time) to discuss my most recent uploads and answer questions from
      TH-cam comments, the chat, and emails. Come check it out if you can th-cam.com/video/cFVJGl-KVEc/w-d-xo.html

  • @oscarmarroquin9896
    @oscarmarroquin9896 3 หลายเดือนก่อน +1

    Thanks!

  • @didijiji918
    @didijiji918 5 ปีที่แล้ว +3

    I agree with you, there is some moisture in the refrigeration line and ice clog at the metering device, the line should be vacuumed and refilled by the fresh refrigerant. I like your video, you did a great job.

  • @texastyrannyresponseteam794
    @texastyrannyresponseteam794 ปีที่แล้ว +1

    We all find the brands/models that we have good experiences with.. Thats what we stick with because we can say with no reserve that they will do the job and serve the client well... Thats true of whatever business you are in... And the way it should be.... If you only sell what's cheap or what makes the most profit right now... That a recipe for disaster... Typically a client will trust you and when your recommendation proves true... You keep that client for life.. and equally important... they send referrals... There no better business than repeat and referrals... The cost of client acquisition is free (or cheap) and they are usually the best clients.... Once again... This is true whatever line of work you are in... Thanks for the content..

  • @dr650dualsport
    @dr650dualsport 5 ปีที่แล้ว +5

    Hey Chris! Love your videos and professionalism. Your customers could never question the approach you take. The videos prove it. Great tool for any tradesman to record his or hers service call. Cheers from Canada 🇨🇦

  • @robbygraves739
    @robbygraves739 5 ปีที่แล้ว +3

    Nice work brother. Ive never thought about running the adjuster in and out to free up a valve in a pinch. Awesome video.

    • @robanderson84
      @robanderson84 5 ปีที่แล้ว +3

      really similar to valves i deal with in plumbing/water lines at work, it is called "exercising the valve", which oddly enough an electrician contractor taught me for breakers, but he said plumbing is same, they all like to be turned on all the way and turned off all the way- back and forth a few times- at least once a year, or they get gummed up or rust or whatever, so at least once a year turn whatever valves you have folks.... it has worked wonders for the old building i take care of, saves lots of replacement work and when a pipe breaks, the valve actually shuts off the water

  • @zekenzy6486
    @zekenzy6486 5 ปีที่แล้ว +2

    I love to watch your video. I'm learning HVACR now. I wish you can post shared 2 video everyday . so I can watch and learn more HVACR . Thanks you for shared

    • @HVACRVIDEOS
      @HVACRVIDEOS  5 ปีที่แล้ว

      I will be going live on TH-cam this evening 8/19/19 @5:pm
      (pacific time) to discuss my most recent uploads and answer questions from
      TH-cam comments, the chat, and emails. Come check it out if you can th-cam.com/video/cFVJGl-KVEc/w-d-xo.html

  • @craigspicer4296
    @craigspicer4296 3 ปีที่แล้ว +1

    It was great to watch this and i pick something up i never would have thought to do. Thank you for your time and experience

  • @dieselchevette
    @dieselchevette 5 ปีที่แล้ว +4

    All this behavior makes perfect sense. You had a little extra oil in the discharge from the low superheat and gas through that stuck txv. That coil was nicely insulated with that extra oil. Damn good get it done method of cranking the valve spring to both extremes, excellent work.

    • @HVACRVIDEOS
      @HVACRVIDEOS  5 ปีที่แล้ว

      I will be going live on TH-cam this evening 8/19/19 @5:pm
      (pacific time) to discuss my most recent uploads and answer questions from
      TH-cam comments, the chat, and emails. Come check it out if you can th-cam.com/video/cFVJGl-KVEc/w-d-xo.html

    • @dennisnoone7427
      @dennisnoone7427 5 ปีที่แล้ว +2

      the box temperature wasnt satisfied because txv wasnt feeding a solid liquid once he cleared a glass the temperature should drop, but it would still be flooding compressor,
      and shorten its life.
      very nice diagnosis! I just wish the doctors would be that through

  • @slamdvw
    @slamdvw 5 ปีที่แล้ว +7

    you can tell it's happier... it's building frost after the expansion valve, and not up at the compressor. thanks for sharing!

  • @FireandFrostHVAC
    @FireandFrostHVAC 5 ปีที่แล้ว +6

    What’s wrong with negative superheat??? 🤣🤣🤣
    I prefer the Sporlan TX Valves too. And I agree with you about the wonky placement of the liquid service valve. I suppose that manufacturer installs filters that never need to be changed, so no need for a King valve then... good video, thanks Chris.

    • @44R0Ndin
      @44R0Ndin 4 ปีที่แล้ว +3

      "filters that never need to be changed" that's a good one!
      Just like you don't have to change the oil in your lawnmower anymore, just add more when it gets low.
      I still change the oil on my small engine equipment, and I bet I won't have to buy one for another 10 years (that's the secret, they can't sell more "durable goods" if they don't break, so they build them to break right after the warranty is finished!)

  • @andrewhicks6494
    @andrewhicks6494 5 ปีที่แล้ว +6

    You could always use your pinch off tool on the liquid line after the receiver outlet if you needed to change the drier. I bought one after doing a pressure switch on a Mani and have used it at least 15 times that year, mostly to weld taps onto reach ins while they’re running because the saddle taps are worthless

    • @44R0Ndin
      @44R0Ndin 4 ปีที่แล้ว +4

      I've seen one of HVACR VIDEOS vids where he used a saddle tap on a piece of equipment that didn't have service ports.
      I'm not a HVACR technician, but I do auto repair so I do have the occasional contact with vehicle AC systems. IMO, saddle taps should only ever be used to remove the charge from equipment that doesn't have service ports, and never left in place. That rubber you wrap around the pipe will degrade, and those screws are all that's compressing the rubber to seal it against the pipe, and a dirty pipe won't seal as well, and... well a leak is basically inevitable, and likely created when you install it. So it's best to use it as little as possible, and never left in the system as a permanent fitting.
      If I was working on something that didn't have service ports, and I needed access, I'd use a saddle tap. Once I was done, I'd recover the charge, then sweat in a pair of service ports. I don't like the idea of a pinch off tool on copper lines as it puts the copper thru so much stress that I'd never trust that section of pipe again (work hardening and micro cracking are likely at the corners of the pinched-off pipe). As far as I've seen from watching many videos, when I see a pinched off copper line it's also sweated shut. That's acceptable for long term use, but I only trust it because I've seen them that way from the factory.
      Even in plumbing saddle taps are a common source of water leaks, usually behind the fridge as some DIY'er decided that was the quick and cheap way to get a water line connected to the fridge's ice maker. The leak can happen any time from under a month to a couple years after installation, but it WILL eventually happen.

  • @coolezum
    @coolezum 5 ปีที่แล้ว +3

    Another top notch diagnosis and procedure, brother.👍

    • @HVACRVIDEOS
      @HVACRVIDEOS  5 ปีที่แล้ว

      I will be going live on TH-cam this evening 8/19/19 @5:pm
      (pacific time) to discuss my most recent uploads and answer questions from
      TH-cam comments, the chat, and emails. Come check it out if you can th-cam.com/video/cFVJGl-KVEc/w-d-xo.html

  • @rolandgirouard5914
    @rolandgirouard5914 5 ปีที่แล้ว +2

    Good boy I like techs that know how to make a bill.

    • @HVACRVIDEOS
      @HVACRVIDEOS  5 ปีที่แล้ว

      I will be going live on TH-cam this evening 11/25/19 @ 5:PM (pacific time) to discuss my most recent uploads, and answer questions from email’s , TH-cam comments, and the Live chat come on over and check it out if you can. th-cam.com/users/HVACRVIDEOSlive

  • @ovidiocabrera1979
    @ovidiocabrera1979 3 ปีที่แล้ว +1

    Congratulations you are a very knowledgeable technician, and well explained. I hope you are been taking care $.

  • @derekmc9580
    @derekmc9580 5 ปีที่แล้ว +19

    I really wish more residential equipment had adjustable txv’s.

    • @deseani1
      @deseani1 3 ปีที่แล้ว

      They do from my knowledge. But it's not a need to adjust them

  • @compy9123
    @compy9123 5 ปีที่แล้ว +2

    Thanks for sharing your wealth of knowledge Chris! Its rare to find honest and knowledge Tech's in this field and that's a fact.

    • @HVACRVIDEOS
      @HVACRVIDEOS  5 ปีที่แล้ว

      I will be going live on TH-cam this evening 8/19/19 @5:pm
      (pacific time) to discuss my most recent uploads and answer questions from
      TH-cam comments, the chat, and emails. Come check it out if you can th-cam.com/video/cFVJGl-KVEc/w-d-xo.html

  • @hvacrnortheastern2110
    @hvacrnortheastern2110 5 ปีที่แล้ว +4

    No I am other tech that l don't like alco valve you can't take apart like a sporlan .Great video Chris.

    • @HVACRVIDEOS
      @HVACRVIDEOS  5 ปีที่แล้ว

      I will be going live on TH-cam this evening 8/19/19 @5:pm
      (pacific time) to discuss my most recent uploads and answer questions from
      TH-cam comments, the chat, and emails. Come check it out if you can th-cam.com/video/cFVJGl-KVEc/w-d-xo.html

  • @chriscooley906
    @chriscooley906 5 ปีที่แล้ว +2

    Great instructional video Chris, Great diagnosing, keep up the stellar work bud!

    • @HVACRVIDEOS
      @HVACRVIDEOS  5 ปีที่แล้ว

      Thanks bud,
      I will be going live on TH-cam this evening 8/19/19 @5:pm
      (pacific time) to discuss my most recent uploads and answer questions from
      TH-cam comments, the chat, and emails. Come check it out if you can th-cam.com/video/cFVJGl-KVEc/w-d-xo.html

  • @tytig94
    @tytig94 5 ปีที่แล้ว +2

    Your channel makes me want to go look for another company to work for. The company I work for only does residential. I want more variety!!!

    • @thefambam9305
      @thefambam9305 5 ปีที่แล้ว

      I know right! My last day at my residential company is this Thursday, will be starting at a commercial, refrigeration company friday.got 5 years in residential

  • @larrykuzniar6204
    @larrykuzniar6204 3 ปีที่แล้ว +1

    excellent videos , you are teaching me so much. thank you

  • @jimmymwaba4693
    @jimmymwaba4693 4 หลายเดือนก่อน +1

    Thanks for the video it's really a good explanation.
    Can a superheat cause the high side of the compressor to the oil return pipe form ice when the door of an industrial coldroom open?
    How can I deal with this same problem ?

  • @lerch400block
    @lerch400block 3 ปีที่แล้ว

    Good job man. If the compressor short cycles for any reason, the contactor is feeling the pain.

  • @chriszachem2012
    @chriszachem2012 4 ปีที่แล้ว +2

    thanks
    straight forward, good learning exp.

  • @HVACRNorth
    @HVACRNorth 5 ปีที่แล้ว +2

    i love going in walk ins with you. good job bud

  • @charlesveal2715
    @charlesveal2715 3 ปีที่แล้ว

    man, you got some cool diagnostic tools!! great video as always!

  • @RobRocker09
    @RobRocker09 ปีที่แล้ว +1

    When you checked the copeland, did you check the resistance on the electrical terminals to determine it was good. .

  • @johng5295
    @johng5295 3 ปีที่แล้ว +2

    Thanks in a million. Great content.

  • @bq2appliances15
    @bq2appliances15 4 ปีที่แล้ว +1

    man your videos are so helpful thanks all the time

  • @prestigemechanical3600
    @prestigemechanical3600 3 ปีที่แล้ว

    Great video share ! I appreciate the time it takes to put the all of this together sir !

  • @wasimedoo7994
    @wasimedoo7994 3 ปีที่แล้ว

    Very good job you my friend keep it up nice information thanks looking forward

  • @jarheadshooter6452
    @jarheadshooter6452 4 ปีที่แล้ว

    If one of my guys had run that bulb like that he would be meeting me in that box! We would be discussing his career options!

  • @Muslim9414
    @Muslim9414 ปีที่แล้ว +1

    Thank you for sharing information

  • @terryj.macmullen9968
    @terryj.macmullen9968 3 ปีที่แล้ว +1

    sometimes i ve seen low superheat at compressor caused by coax heat exchangers leaking internally. liquid dumping directly into suction line.

  • @christianbacon7027
    @christianbacon7027 ปีที่แล้ว

    Impressive service

  • @Wlladdd
    @Wlladdd 3 หลายเดือนก่อน +1

    Thank you for the video. I still didn't catch one thing that you did. You added refrigerant based on side glass, but is there no leaks. Why did you see flashing glass. I am new tech. Maybe I missed something.

  • @harrydickson4575
    @harrydickson4575 5 ปีที่แล้ว +1

    Excellent video and job 👍👍👍👍

  • @TH-ji1ed
    @TH-ji1ed 5 ปีที่แล้ว +20

    “I’ve confirmed that the thermostat is working even though I don’t like that style it’s a piece of junk”...I’ve been there lol

  • @scmxrider613
    @scmxrider613 5 ปีที่แล้ว +9

    add a ball valve in front of the drier.it`ll be your king valve

    • @Niveous23
      @Niveous23 5 ปีที่แล้ว +2

      ball valves are life.

  • @omarsegovia893
    @omarsegovia893 5 ปีที่แล้ว +1

    Great videos man! Love to see passion for the trade.

    • @HVACRVIDEOS
      @HVACRVIDEOS  5 ปีที่แล้ว

      I will be going live on TH-cam this evening 8/19/19 @5:pm
      (pacific time) to discuss my most recent uploads and answer questions from
      TH-cam comments, the chat, and emails. Come check it out if you can th-cam.com/video/cFVJGl-KVEc/w-d-xo.html

  • @kingsolo6241
    @kingsolo6241 4 ปีที่แล้ว +5

    Sun ding liquid through the headers or scrolls can ruin a compressor as well. You want 100% gas going back through the compressor discharge. That’s why we take subcool and super-heat. Same goes the other way. If we have a sub-cool that is off with a flashing sight glass we are ruining the TXV since the TXV needs 100% liquid to work correctly. When gas goes though the TXV the valve body will jump more than needed to. It can destroy the TXV. Especially the way they are made these days.

  • @jacquesdaoud4263
    @jacquesdaoud4263 4 ปีที่แล้ว +1

    Thank you .you just answered my question

  • @ninamcclure2193
    @ninamcclure2193 3 ปีที่แล้ว +1

    Great video guy, I know you put in a lot of time and effort into making these and it is appreciated. I wonder if you have ever set up a
    white board and explained how the refrigerant flows through the system. This may not be your thing but you do have a good teaching skill. Working with auto a/c is so much easier as in less parts and it's just basic. When I'm watching you work with these systems I'm like damn I cant keed up with all the stuff that's added. Defrosting and a/c power and all these switches everywhere. Lol. I'm starting to pick it up though thanks to you.

  • @alexx-ie1hk
    @alexx-ie1hk 2 ปีที่แล้ว

    Good solid work very helpful

  • @latenitehvac868
    @latenitehvac868 5 ปีที่แล้ว +1

    Very good video man!!

  • @donavanheadley3103
    @donavanheadley3103 3 ปีที่แล้ว

    Cool video very educational

  • @steevydance
    @steevydance 2 ปีที่แล้ว +1

    You are the best ❤🙏🏿

  • @flyinbrianvids
    @flyinbrianvids 5 ปีที่แล้ว +3

    Hey, I just heard that the SMAN380/480 will link up to measurequick now.

    • @HVACRVIDEOS
      @HVACRVIDEOS  5 ปีที่แล้ว +1

      yep that is confirmed!
      I will be going live on TH-cam this evening 8/19/19 @5:pm
      (pacific time) to discuss my most recent uploads and answer questions from
      TH-cam comments, the chat, and emails. Come check it out if you can th-cam.com/video/cFVJGl-KVEc/w-d-xo.html

  • @phillipstyles6400
    @phillipstyles6400 ปีที่แล้ว +1

    Good stuff bro

  • @RobRocker09
    @RobRocker09 8 หลายเดือนก่อน +1

    Absolutely awesome videos and recaps. I been in the residential AC 5yrs When I worked with my old boss we did single evp and condensers. Recently got a lead to go see a customer. He had a parallel Hussmann cabinet. The guy who worked on it move so he says. Had 4 compressors. 1999. Only one compressor was working, he wanted a new and wanted to replace one compressor, 3 were bad. Customer gave me a hard time about adding freon, 55lb system 404A. It had 4 cases and one walkin chill box. But anyway. Do you have any videos on multi compressors systems or multi evp running off of one condenser. I couldnt find you email, the website wouldn't load

  • @Eddy63
    @Eddy63 5 ปีที่แล้ว +2

    Your voice sounds like the lead singer in the band Sister Hazel ... Just an observation ... The song is All for you ... Good vid also ...

    • @HVACRVIDEOS
      @HVACRVIDEOS  5 ปีที่แล้ว

      Ha Ha I loved that band and song, too bad I cant sing to save my life.........
      I will be going live on TH-cam this evening 8/19/19 @5:pm
      (pacific time) to discuss my most recent uploads and answer questions from
      TH-cam comments, the chat, and emails. Come check it out if you can th-cam.com/video/cFVJGl-KVEc/w-d-xo.html

  • @jonathankipps9061
    @jonathankipps9061 5 ปีที่แล้ว +6

    I'm a newbie at this, so confirm if I'm thinking this through correctly.
    The flashing sight glass was because the faulty expansion valve was flooding the evaporator and suction line with liquid refrigerant. With too much refrigerant now on the suction side, the liquid line receiver ran low on refrigerant. Is this correct?

    • @joshuapellerito1341
      @joshuapellerito1341 5 ปีที่แล้ว +4

      That is correct. Most freezer TXVs are pressure limiting, so as the evaporator is flooded and the liquid refrigerant is flooding back to the compressor, it fills the suction line with refrigerant causing the system to appear long on charge when in fact its perfectly fine.

  • @lizards7777
    @lizards7777 3 ปีที่แล้ว

    I was wondering the effect of taking loose the bulb of txv to increase sh and open valve or even heating bulb.

  • @LC-qi5ff
    @LC-qi5ff ปีที่แล้ว +1

    Do thermostats have a built-in differential, in this case 6F?

  • @johntaylor4854
    @johntaylor4854 ปีที่แล้ว

    I’m not sure if it’s been mentioned in the above comments so i apologise if I’m repeating anyone else. The equaliser line is positioned incorrectly, when the valve & orifice are sized correctly (hopefully always) that will cause you problems every time. Obviously there is some liquid Cary over through the equalising line and when your bulb is positioned down circuit from that your creating a false superheat causing the valve to shat down equivalent initially then behave IRAtic with the fluxeration and what not.

  • @antonalderliesten1421
    @antonalderliesten1421 11 หลายเดือนก่อน +1

    So there was potential floodback to the compressor but the TXV was only feeding vapor? Is there something i am missing cuz that seems wrong..

  • @OscarRodriguez-ik3vm
    @OscarRodriguez-ik3vm ปีที่แล้ว +1

    Hello just a question, is there any reason you put the other pressure probe closer to the evaporator instead of putting in closer to the condenser? I see you had a T

  • @asgordon74
    @asgordon74 2 ปีที่แล้ว

    Very helpful video, thx.

  • @josecabello7285
    @josecabello7285 2 ปีที่แล้ว

    Thanks for the info .

  • @ricardoroa3345
    @ricardoroa3345 2 ปีที่แล้ว

    Great video

  • @julianfigueroa9525
    @julianfigueroa9525 5 ปีที่แล้ว +2

    Why does the ceiling of a walk in freezer box is always frosted? Is it bad door gaskets? If not what other things you look for to cause frost in the ceiling of freezer hope it’s not a dumb question?

  • @DWAYNE2ism
    @DWAYNE2ism 4 ปีที่แล้ว +1

    Great video
    The oil concern youu had. About compressor did you charge with oil?

  • @sampathravindra8676
    @sampathravindra8676 4 ปีที่แล้ว

    Hi Good day sir..i Have learned liquid is worst enemy for compresure..but i can see u adding liquid to the suction line..may i know is it correct...Thanks for video..

  • @jonjordan6606
    @jonjordan6606 3 ปีที่แล้ว +1

    I’m a newbie, and I have a walk-in cooler that is running off a halfhorsepower Compressor and it does not seem to get below 50° the charge seems fine, should I adjust the TXV before trying something else or should I get a bigger condensing unit

  • @hookedup9424
    @hookedup9424 4 ปีที่แล้ว +2

    Have a 404a reach-in freezer the evaporator is icing up real bad I think it's the TXV

  • @larryboy4905
    @larryboy4905 5 ปีที่แล้ว +1

    Good job

    • @HVACRVIDEOS
      @HVACRVIDEOS  5 ปีที่แล้ว

      thanks, I will be going live on TH-cam this evening 8/19/19 @5:pm(pacific time) to discuss my most recent uploads and answer questions from
      TH-cam comments, the chat, and emails. Come check it out if you can th-cam.com/video/cFVJGl-KVEc/w-d-xo.html

  • @heavens_heathen8164
    @heavens_heathen8164 5 ปีที่แล้ว +1

    Nice videa buddy!

  • @coreybomhoff4784
    @coreybomhoff4784 ปีที่แล้ว +1

    Sure would like an opportunity to work with you guys if I come to cali!

  • @tolsonsmith9121
    @tolsonsmith9121 3 ปีที่แล้ว +1

    Since your recovering the charge, do you plan on installing a king valve at the accumulator so you can change the drier in the future?

  • @levy5867
    @levy5867 5 ปีที่แล้ว +1

    What else to say than excellent video!

  • @emptech
    @emptech 5 ปีที่แล้ว +1

    I understand the industry likes to see a compressor superheat of 10 plus or minus a couple (F). The system SH is measured from the suction line 8 inches or so before the suction input of the compressor. What system superheat would you like to see as a minim?

    • @HVACRVIDEOS
      @HVACRVIDEOS  5 ปีที่แล้ว

      I will answer your question on my stream tonight, I will be
      going live on TH-cam this evening 8/19/19 @5:pm (pacific time) to discuss my
      most recent uploads and answer questions from TH-cam comments, the chat, and
      emails. Come check it out if you can th-cam.com/video/cFVJGl-KVEc/w-d-xo.html

  • @workinprogress008
    @workinprogress008 4 ปีที่แล้ว +1

    1.9° subcooling you mean? In the suction line

  • @sterlingc107
    @sterlingc107 2 ปีที่แล้ว

    What size reefer wrench do you need for the TXV adjustment screw? Is it 3/16ths? Thanks for the videos.

  • @cshin58
    @cshin58 ปีที่แล้ว

    Hi, Chris, just watching your video and I think I’m having similar issues wit subway sandwich maker , R404 and pressure looks good, but temperature is staying at 47 , 35 low 225 high condenser coil is clean , made turn few to the left and more to the right , but no changes on pressure at all, took out all refrigerant and weigh charged of 25 oz. But temperature maintains 48 degrees, would it be the TXV ?
    Thank you in advance!

  • @brandonunderwood4224
    @brandonunderwood4224 3 ปีที่แล้ว

    Have a new WI Frz installed in NOV 2020. 2 weeks ago I got my first call saying box temp 20°. Bubbles in sight glass so I cleared it with 1lb 404. My diagnosis was that whoever installed it did not properly charge it and are just now seeing a problem due to higher ambient temps. I've done a leak check as well. Am I on the right track?

  • @alicepet1994
    @alicepet1994 5 ปีที่แล้ว +1

    Can you use Pinch off tool to change the filter drier without have to recovery?

    • @HVACRVIDEOS
      @HVACRVIDEOS  5 ปีที่แล้ว +1

      yeah you could but it will look like crap

  • @yoyofd
    @yoyofd 5 ปีที่แล้ว +2

    Do you do the same calc from ac to get that target sh ? Thanks

    • @yoyofd
      @yoyofd 5 ปีที่แล้ว

      Can you ad it to your next video?

  • @phareztrinimand
    @phareztrinimand 3 ปีที่แล้ว

    Hello question, my country is mostly summer, I have two choices of TXV, one with 4 superheat and the next with 8, would the 4 produce cooler air at the evaporator than the 8?, It`s r134a

  • @victorleon1563
    @victorleon1563 3 ปีที่แล้ว +1

    Why would you think its under charged when it's freezing back to the compressor. I would have gone straight to the tev ❓

  • @ferozkhan9735
    @ferozkhan9735 4 ปีที่แล้ว +1

    Sir I requested you to make a video on plate freezer

  • @stephenramsey9304
    @stephenramsey9304 5 ปีที่แล้ว

    Why didn’t you check the sub cooling ?

  • @chenjonathan9622
    @chenjonathan9622 5 ปีที่แล้ว +1

    Thank u so much that how I learn how to fix my equipment in my store save lot of money

  • @Karnol428
    @Karnol428 2 ปีที่แล้ว

    How do you know what target superheat to go for?

  • @HVACChillin
    @HVACChillin 5 ปีที่แล้ว +3

    Why would you go back with a flare style drier? Just preference?

    • @HVACRVIDEOS
      @HVACRVIDEOS  5 ปีที่แล้ว +3

      Yeah preference, I'm lazy and dont want to have to bring my torches up on the roof next time to change the drier......

  • @FamilyChannelfun32
    @FamilyChannelfun32 4 ปีที่แล้ว +1

    Any ideas on what unit I can use for a food cart. I want to build a walk in freezer inside of it. I am a plumber and have done some hvac. By no means am I a pro!

  • @bcbottoms
    @bcbottoms 7 หลายเดือนก่อน

    What mfg and model digital thermostat do you recommend for medium temp systems (+35° holding temp).

  • @hendrawan1968
    @hendrawan1968 4 ปีที่แล้ว +1

    Good Jobb

  • @CoffeeQuilava
    @CoffeeQuilava 5 ปีที่แล้ว +3

    @HVACR VIDEOS I have a question, I have a heat pump that is not keeping my house cool. I hade someone come out and I have a low super heat, and flooding the A coil, I have the correct charge, clear site glass, and clean coils. the condenser is discharging warm air, the tech could not figure it out, any recommendations. ps love the vids

    • @whitesheatingairappliancer7101
      @whitesheatingairappliancer7101 5 ปีที่แล้ว +3

      Dave your residential heat pump has a sight glass? I did not know that would benefit the equipment.

    • @Josh-px6xb
      @Josh-px6xb 5 ปีที่แล้ว +1

      Could it be the txv?

    • @CoffeeQuilava
      @CoffeeQuilava 5 ปีที่แล้ว +2

      @@whitesheatingairappliancer7101 installer added it wean he installed the system, he said it helps diagnosing future problems. I thought the same thing, but It didn't cost me anything for him to add it that I know of

    • @CoffeeQuilava
      @CoffeeQuilava 5 ปีที่แล้ว +1

      @@Josh-px6xb I don't think I have one. I think its a orface tube.

    • @HVACRVIDEOS
      @HVACRVIDEOS  5 ปีที่แล้ว +1

      I will answer your question on my stream tonight, I will be
      going live on TH-cam this evening 8/19/19 @5:pm (pacific time) to discuss my
      most recent uploads and answer questions from TH-cam comments, the chat, and
      emails. Come check it out if you can th-cam.com/video/cFVJGl-KVEc/w-d-xo.html

  • @Fishing570
    @Fishing570 ปีที่แล้ว

    i have a question. We have a quadruple-door Supera freezer that has been running a lot colder than it is currently set to run. What would be the main cause of this?

  • @noticiasdigitalhilder1226
    @noticiasdigitalhilder1226 2 ปีที่แล้ว

    Hi Mister
    I have wall in freezer is working + 10 F have to work -05 I have manifold regular yellow jaket hi presusure 325 psi on low 20 psi.
    What presure is normal on Hi?
    What presusure in low?
    Thanks for help me

  • @James_Bowie
    @James_Bowie 5 ปีที่แล้ว +1

    Why suggest changing all of those other parts when it seems that a TXV and contactor change out will do the job?

    • @sighpocket5
      @sighpocket5 5 ปีที่แล้ว

      James Bowie longevity!

    • @akhermit5213
      @akhermit5213 5 ปีที่แล้ว +1

      So the other potential issues don't come back to bite you in the ass after repairing the immediate issues.

    • @James_Bowie
      @James_Bowie 5 ปีที่แล้ว

      @@akhermit5213 A number of those items were a case of "I don't like this particular brand/model". To me, simply not liking something that is working OK (such as the thermostat) doesn't justify replacing them, but it's his customer.

    • @akhermit5213
      @akhermit5213 5 ปีที่แล้ว +1

      @@James_Bowie Sometimes OK is not good enough. I agree, it depends on the customer. After the repair, the customer not having issues for a long period of time is the goal. If I foresee possible future problems, I will proactively pursue them, rather than take the chance of the customer being unhappy with my work if one of those items fails shortly after I repair the obvious issues. Everyone has different views, but personally, I try to improve equipment when possible, and keep the customer as happy as can be. A customer that has equipment in good working condition is a happy customer. YMMV Have a great day!

  • @marriagepartnersministry5942
    @marriagepartnersministry5942 5 ปีที่แล้ว +2

    They get a second quote and that guy says the TXV is working fine, temp controller and solenoid are working fine, the contractor is dark but it working. So, the client doesn't want to spend a thousand bucks if he doesn't have to. If it keeps working what the client feels is fine then they assume you were wrong or trying to dip them off. A month to three later if it acts up again and the client uses garage logic and pegs you as an over do it sort of guy. How do you counteract client misjudgment like I just outlined above? My outline is a common occurrence in misjudgment around my part of the country.

    • @HVACRVIDEOS
      @HVACRVIDEOS  5 ปีที่แล้ว +2

      I agree that they will often say but it's working......... all I can do is give them my honest opinion and let them make that decision.... luckily at this point and time i have a very good customer base that trusts me..... i say me because they often don't trust my employees and that is something i am working on....