How to Install a Lawn Sprinkler Backflow Preventer

แชร์
ฝัง
  • เผยแพร่เมื่อ 31 ธ.ค. 2024

ความคิดเห็น • 143

  • @Iscaper
    @Iscaper  11 ปีที่แล้ว +4

    I've had lots of trouble with PVC male and female adapters connecting to galvanized pipe and fittings, but no trouble with a bushing glued into a coupling. It makes the transition point much stronger.

  • @Iscaper
    @Iscaper  12 ปีที่แล้ว +8

    Yes, a reduced pressure backflow preventer was required by the city and they inspected the installation. I ended up rotating the backflow preventer so the vent was pointing down (not shown in video).

  • @Iscaper
    @Iscaper  11 ปีที่แล้ว +1

    Yes, in going from PVC to galvanized there a weak point at the connection. That's why I used a coupling with a bushing to make that transition point stronger. Galvanized pipe and fittings start corroding the minute you install them, but you need the galvanized for strength. PVC doesn't do well above ground.

  • @georgechang861
    @georgechang861 9 ปีที่แล้ว +1

    Good works and excellent demo, i study point at 1 1/4" bushing instead of 1" coupling, enforce connection even thought, very good and thanks.

    • @Iscaper
      @Iscaper  9 ปีที่แล้ว

      +George Chang
      Thanks George for the feedback.

  • @Iscaper
    @Iscaper  12 ปีที่แล้ว +2

    Good question. I'm not sure I have a definitive answer. Backflow preventers are different from vacuum breakers in that they have double check valves in the backflow assembly. Elevation isn't a requirement, they simply need to be installed between the stop & waste valve and the first set of valves in the sprinkler system. Vacuum breakers and anti-siphon valves do have the elevation requirement of being 12" higher than the highest sprinkler head.
    (continued)

  • @attilahooper
    @attilahooper 8 ปีที่แล้ว

    I liked the bit about reinforcing pvc connections with the bushings.

    • @Iscaper
      @Iscaper  8 ปีที่แล้ว

      +attilahooper
      Thanks, I had to learn that trick the hard way.

    • @attilahooper
      @attilahooper 8 ปีที่แล้ว

      +iScaper1 Thanks for the talk-back. I also took notice of the galvanized lines and unions. I'm installing a new sprinkler system myself in freeze zone with double backflow reqs by code. I want a strong install, pipes mounted to foundation with minimal to no pvc outside. - my manifold goes out to black pipe.So your visuals were quite helpful how I would come out of house with copper - turn to galv into the ground. Cheers ! and thanks

    • @Iscaper
      @Iscaper  8 ปีที่แล้ว

      +attilahooper
      Thanks, I'm glad the video was helpful.

  • @theRileyHamilton
    @theRileyHamilton 2 ปีที่แล้ว

    wow i can't wait to do this later this week!!! thanks for posting, detailed and clear

    • @Iscaper
      @Iscaper  2 ปีที่แล้ว

      Good luck!

  • @Iscaper
    @Iscaper  11 ปีที่แล้ว

    I have a stop & waste valve in the yard that tees into the main supply to the house. This backflow preventer is cut into the sprinkler supply from the stop & waste valve. Code here requires it be installed before the first set of sprinkler valves.
    If your sprinkler supply is in the basement you might be able to install a different backflow preventer there. You could contact the city water department in your area and see what is required.

  • @vinnygoombatts1458
    @vinnygoombatts1458 8 ปีที่แล้ว +17

    The backflow discharge hole also needs to point down. You have the whole assembly sideways.

  • @flsinder
    @flsinder 12 ปีที่แล้ว +1

    Nice. Thanks for the good guidance, particularly using unions, etc., to make later repairs, if needed, easier.

  • @asgplumbing781
    @asgplumbing781 9 ปีที่แล้ว +11

    Use Teflon tape in irrigation not pipe dope. Pipe dope will get into the valves and malfunction the operation as an obstruction in the diaphragms .

  • @Iscaper
    @Iscaper  12 ปีที่แล้ว

    Thanks for the comment.

  • @chrisdubeau33
    @chrisdubeau33 8 ปีที่แล้ว

    I like to put a ball valve right before the back flow to serve as a main shutoff. I also like to have brass ball valves on either side of the back flow preventer too.

  • @heroknaderi
    @heroknaderi 5 ปีที่แล้ว +2

    I enjoyed watching this thanks 🙏

  • @aaronbaraiya3692
    @aaronbaraiya3692 2 ปีที่แล้ว

    great install, thanks, how the backflow preventer now?

  • @Iscaper
    @Iscaper  11 ปีที่แล้ว

    Where I live requirements were a Reduced Pressure Backflow Preventer installed a minimum of 12" above grade and before the first set of sprinkler valves. Installation had to be inspected by the city before backfilling. You would need to contact your local water department to see what codes are required where you live.

    • @joeadams2959
      @joeadams2959 6 ปีที่แล้ว

      12" above the highest sprinkler head. !! That is important

  • @Iscaper
    @Iscaper  11 ปีที่แล้ว +2

    I ran into this catch 22 when I was working construction. I joined the union and was on the C list. I went and got a job on my own driving 50 ton rock trucks. The next day someone on the A list complained and I lost my job. They told me I needed more hours to get on the A list. So I needed more hours to get on the A list but couldn't get the hours I needed because I was on the C list and wouldn't be called out if someone on the A or B list wanted the job first.

  • @JustinMayfield
    @JustinMayfield 4 ปีที่แล้ว

    This is the video I was looking for! Thank you!

  • @Iscaper
    @Iscaper  12 ปีที่แล้ว

    So what do you do if you have a sloping yard where a number of sprinkler heads are higher in elevation than the sprinkler valves? This is where I see a flaw in the requirement of installing anti-siphon valves and vacuum breakers. I have lived where cities install a meter yoke with backflow preventer to protect their main lines. To me this is the preferred method, but where I currently live no one does it.
    In your case I would contact the local water department and see what they will let you do.

  • @vinnygoombatts1458
    @vinnygoombatts1458 8 ปีที่แล้ว +15

    The Plumbing code does not allow for the combination of two different metals. You cannot combine galvanized and copper or brass and have water run through it. It will cause major corrosion in every little time.

    • @Milosz_Ostrow
      @Milosz_Ostrow 8 ปีที่แล้ว +6

      Faucets are usually made of brass and they are routinely used in galvanized iron plumbing systems. When was the last time you encountered a galvanized iron faucet? They don't exist.

  • @BackFishing
    @BackFishing 8 หลายเดือนก่อน

    Good video. How do you decide which back flow preventer to use? Do you ask the city?

    • @Iscaper
      @Iscaper  8 หลายเดือนก่อน +1

      Yes, the city's water department will tell you what they require.

    • @BackFishing
      @BackFishing 8 หลายเดือนก่อน

      @@Iscaper Thank you.

  • @baileyslip
    @baileyslip 11 ปีที่แล้ว +1

    Hay Leo this code is required only if you have a system that's run to yard from your home supply. If you have a water supply separate from a home supply then this setup is not necessary. In other words if you have a system hooked up to your home you sir need to do this. What say you? Linda from Ga.

  • @MRrwmac
    @MRrwmac 5 ปีที่แล้ว

    Do you have a video showing how the main supply line is plumbed in or off a faucet?

  • @rvchoudhary
    @rvchoudhary 3 ปีที่แล้ว

    thanks for the video demo. Can you suggest from where to buy the back flow preventer ? I had Watts 1 inch 009 and during winter it just broke and need a replacement.

    • @Iscaper
      @Iscaper  3 ปีที่แล้ว +1

      Amazon or Lowe's carry them.

  • @spelunkerd
    @spelunkerd 12 ปีที่แล้ว

    Somehow I missed this video but I found it from your feed. Tell me, if some sprinkler heads are higher than the height of the backflow preventer, would you have to raise the preventer higher to get that 15" clearance?

  • @RogerPack
    @RogerPack 3 ปีที่แล้ว

    Thanks saved me a lot of money. Sorry if this is a duplicate comment. Anyway in the case of the multiple pipes you might could sometimes "figure out" by turning the incoming valve on and off and feeling for pressure, or running it through some distant valve and feeling for water flowing/coldness. Also on the transition from galvanized to pvc, it appears that's a "screw in bushing" followed by a grey union (or that's what home depot calls them) followed by another bushing out of the union, sound right? Thanks!

  • @allencapps1491
    @allencapps1491 ปีที่แล้ว

    Pretty work, but the drain is required to face down here in North Carolina

    • @Iscaper
      @Iscaper  ปีที่แล้ว

      Yeah, the city inspector never notified me of this. After talking to my plumbing supplier about the orientation of the vent I turned it facing down.

  • @cspill99
    @cspill99 2 ปีที่แล้ว +1

    What schedule PVC was used here? I live in Michigan.

    • @Iscaper
      @Iscaper  2 ปีที่แล้ว +1

      Schedule 40.

    • @cspill99
      @cspill99 2 ปีที่แล้ว

      @@Iscaper even with connection to the pvb? I have to move mine outdoors, so just redoing that area. Can I send you pics?

    • @Iscaper
      @Iscaper  2 ปีที่แล้ว

      @@cspill99 You can email me at kerry@iscaper.com

  • @celmol.j282
    @celmol.j282 10 ปีที่แล้ว

    beautiful work

    • @Iscaper
      @Iscaper  10 ปีที่แล้ว

      Thanks Selmo.

  • @Iscaper
    @Iscaper  11 ปีที่แล้ว

    Good points.

  • @garyb5889
    @garyb5889 2 ปีที่แล้ว

    Fantastic!

    • @Iscaper
      @Iscaper  2 ปีที่แล้ว

      Many thanks!

  • @rafaelreza9030
    @rafaelreza9030 ปีที่แล้ว

    Is ok to combine galvanized whit brass?

    • @Iscaper
      @Iscaper  ปีที่แล้ว

      Yes, galvanized to brass is okay, galvanized to copper is not.

  • @johnkosheluk1041
    @johnkosheluk1041 11 ปีที่แล้ว

    hi kerry i allways like watching your videos i have a question what is the best way 2 tie into city water 4 a sprinkler sys gal pipe and ware after the meator or before it goes in the house if a comp fitting is used on gal pipe is that strong

    • @Iscaper
      @Iscaper  11 ปีที่แล้ว

      Hi John. I have used PVC dresser coupling and dresser tees to tap into galvanized supply lines with no problems. If your nervous about using PVC dresser couplings and tees, Champion makes brass dresser couplings and tees in IPS sizes which work good also.

  • @Iscaper
    @Iscaper  11 ปีที่แล้ว

    So you can't do installs because you're not a member of a union? What does the regulating authority care if someone is a member of a union or not, as long as an installation meets code requirements it should pass regardless of who does the installation.

  • @gaitpierce7342
    @gaitpierce7342 4 ปีที่แล้ว

    Like how you used sch 40 bushings on a sch 80 Union

  • @leodeboca
    @leodeboca 4 หลายเดือนก่อน

    excellent!

    • @Iscaper
      @Iscaper  4 หลายเดือนก่อน

      Thanks!

  • @AlabanzasyAdoración7
    @AlabanzasyAdoración7 ปีที่แล้ว

    If my water line supply is 3/4 should my back flow preventer be 3/4 also?

    • @Iscaper
      @Iscaper  ปีที่แล้ว +1

      Yes.

    • @AlabanzasyAdoración7
      @AlabanzasyAdoración7 ปีที่แล้ว

      @@Iscaper thanks! Appreciate it your answer.

    • @Iscaper
      @Iscaper  ปีที่แล้ว

      @@AlabanzasyAdoración7 You're welcome 🙂

  • @Iscaper
    @Iscaper  11 ปีที่แล้ว

    When we bought our house there was no backflow prevention either on the sprinkler system. The city recently required it be put in or we couldn't use water for the sprinkler system.

  • @harveystephens6115
    @harveystephens6115 ปีที่แล้ว

    Nice job

    • @Iscaper
      @Iscaper  ปีที่แล้ว

      Thanks!

  • @Iscaper
    @Iscaper  11 ปีที่แล้ว

    No requirements on using brass over galvanized. Galvanized is much cheaper than brass. Either would work fine in this installation.

  • @everythinghomerepair1747
    @everythinghomerepair1747 8 ปีที่แล้ว +9

    why did you put your backflow preventer sideways?

  • @WetCoaster
    @WetCoaster 3 ปีที่แล้ว

    RPBA requires 2 pipe diameters or 2", which ever is greater, from the spill level of the rim to the bottom of the RPBA. 12" is lots. I would pay the extra to plumb in something besides galvanized. Tuberculation will cause you grief with the RPBA.

  • @cryptogenik
    @cryptogenik ปีที่แล้ว

    I wonder what that backflow preventer looks like today?

  • @culayta
    @culayta 11 ปีที่แล้ว

    where exactly did you splice the backflow preventer into. I also tap into the copper off the water main in the basement but code requires in your area 12" about sprinkler.

  • @2013ebruggeman
    @2013ebruggeman 8 ปีที่แล้ว +8

    you have that all wrong! the assembly needs to be moved 90 degrees so the "dump" is facing down

  • @vinnygoombatts1458
    @vinnygoombatts1458 8 ปีที่แล้ว

    also you can buy dielectric fittings to make the transition.

  • @Kevin-yc9hy
    @Kevin-yc9hy 6 ปีที่แล้ว

    They can be installed sideways but not the one in this video. It's a rp and should be upright and not sideways. On centain double check assemblys in ground they have to be sideways to access the 2nd check for repair. Good job piping it together and what u have will work fine. I see worse every day trust me. Good job

  • @thomaslabantt6625
    @thomaslabantt6625 ปีที่แล้ว

    What direction the arrow

    • @Iscaper
      @Iscaper  ปีที่แล้ว

      You want the direction arrow pointing downstream.

  • @pepsifan8504
    @pepsifan8504 4 ปีที่แล้ว

    does your current house have a backflow preventer installed on your sprinkler system

    • @Iscaper
      @Iscaper  4 ปีที่แล้ว

      No, but if I upgrade my sprinkler system I'll have to install one.

  • @Iscaper
    @Iscaper  11 ปีที่แล้ว

    If I remember right my backflow preventer was over $200 just for the preventer.

  • @jn3750
    @jn3750 2 ปีที่แล้ว

    my guy didn't use galvanized pipes, only PVC. should I replace the PVC with galvanized pipe

    • @Iscaper
      @Iscaper  2 ปีที่แล้ว +1

      I would. PVC pipe above ground turns brown and gets brittle in the sunlight. Any bumping with a lawnmower or foot traffic will cause the pipe to crack or break.

  • @BBQGrills
    @BBQGrills 12 ปีที่แล้ว

    Great video. I was wondering if the city identified what type device was required (double check or reduced pressure)? It appears the one you installed was a Watts Series 009 which is a reduced pressure zone assembly (RPZ). If so, the vent between the two checks must be pointed down so it is able to discharge once the pressure drops.

  • @johnkosheluk1041
    @johnkosheluk1041 8 ปีที่แล้ว

    Kerry were do you get the t 4 the glue cans

    • @Iscaper
      @Iscaper  8 ปีที่แล้ว

      I bought mine at a local plumbing distributor.

  • @razbo1963
    @razbo1963 11 หลายเดือนก่อน +1

    Galvanive going into brass will oxidize and corrode through time, quicker when under the ground due to electrolysis. If that is a dump on the bottom of backflow it should face down. Always wipe your solvent weld joints with a rag.

  • @bonsummers2657
    @bonsummers2657 8 ปีที่แล้ว +1

    Great technique duct-tapping the primer and glue together! Keeps them more stable, less likely to tip over.
    But, make the overall presentation quicker, including the talking, reasonably of course.

  • @wken123
    @wken123 11 ปีที่แล้ว

    Metal into pvc is gambling on breaking the pvc, also galvanized pipe is going to start corroding below ground (galvanic action with the brass).

  • @MRrwmac
    @MRrwmac 5 ปีที่แล้ว

    So what did you do to hide the piping and preventer? Plants to cover it or a box of some sort?

    • @Iscaper
      @Iscaper  5 ปีที่แล้ว +1

      I installed a wishing well lawn ornament.

    • @MRrwmac
      @MRrwmac 5 ปีที่แล้ว

      iScaper1 That’s even better! Great idea. Could you attach a picture or link to a similar one online? Thanks!

    • @Iscaper
      @Iscaper  5 ปีที่แล้ว +1

      @@MRrwmac Here's a link: www.amazon.com/Best-Choice-Products-Wishing-Planter/dp/B01CIPDKPG/ref=asc_df_B01CIPDKPG/?tag=hyprod-20&linkCode=df0&hvadid=193139379506&hvpos=1o2&hvnetw=g&hvrand=11657242834007334148&hvpone=&hvptwo=&hvqmt=&hvdev=c&hvdvcmdl=&hvlocint=&hvlocphy=9029757&hvtargid=aud-801381245258:pla-310199228301&psc=1
      The trick is to find one big enough so the backflow preventer sits inside.

  • @armandomadrigal9793
    @armandomadrigal9793 4 ปีที่แล้ว +1

    you cant put unions in the dirt, they need to be accessible

  • @asgplumbing781
    @asgplumbing781 9 ปีที่แล้ว +3

    Galvanized Pipes and fittings Rust. All Plumbing To any irrigation system should be Schedule 80 PVC or Copper, Especially Brass. Brass in does not corrosive , non - rust , nor oxidize . Brass is the best metallic in plumbing aside from copper itself. Galvanized is bad. I always replace it because it leaks, rusts, and obstructs deposits and debris and enters in the diaphragms of the solenoid valves creating a series and number of mechanical failure.

    • @Iscaper
      @Iscaper  9 ปีที่แล้ว

      Anthony Sean
      Brass is nice, but it's triple the cost.

    • @macsrule94
      @macsrule94 9 ปีที่แล้ว

      +iScaper1 most people use either l or m copper not brass. anytime galvanized is used the device is usually older.

  • @renejulianromero439
    @renejulianromero439 3 ปีที่แล้ว

    The relief valve is suppose to point DOWN......I’m surprised the inspector didn’t catch that.....oooops, not really 😂😂😂

    • @Iscaper
      @Iscaper  3 ปีที่แล้ว +1

      Yeah, the inspector missed that. A plumber friend informed the vent should point down so I rotated it after the video was made.

  • @bradhirter8619
    @bradhirter8619 10 ปีที่แล้ว +16

    Hire an educated licensed contractor. This assembly has not been installed per manufacturer specification, and is not designed to protect against Backflow laying on its side. The city should not have approved this installed in this matter if they knew what they were looking at.

    • @Iscaper
      @Iscaper  10 ปีที่แล้ว +8

      Good point. I ended up rotating the backflow preventer to where the vent was pointing down.

    • @bradhirter8619
      @bradhirter8619 10 ปีที่แล้ว +3

      Your the man. God bless.

  • @asgplumbing781
    @asgplumbing781 9 ปีที่แล้ว +8

    Any backflow valve should be in the upright position. It should never be installed sideways EVER

    • @Iscaper
      @Iscaper  9 ปีที่แล้ว

      Anthony Sean
      I did turn the vent to where is was pointing down but didn't show that step in the video.

    • @joeadams2959
      @joeadams2959 6 ปีที่แล้ว

      Any backflow. Not true. Only p.v.b Type

  • @jamesballiet5862
    @jamesballiet5862 ปีที่แล้ว

    OCN, only use galvanized, going to mess up BFA, in do tome, a No no.

  • @Super4WheelDrive
    @Super4WheelDrive 11 ปีที่แล้ว

    where exactly is this code required?

    • @RogerPack
      @RogerPack 3 ปีที่แล้ว

      depends on city i think

  • @Iscaper
    @Iscaper  11 ปีที่แล้ว

    Wow. Doesn't seem quite fair. Are you going to join the union?

  • @newtuthis1
    @newtuthis1 8 ปีที่แล้ว +2

    Sorry but if that was my house you would of been fired for that job. Putting a back flow in the yard it would of been ran to the house and properly mounted with supports. And then mixing metals with pipe dope you should tape and dope them. It was a good video just teach it properly and to meet code and look good for the customer.

  • @kennethdifilippo3801
    @kennethdifilippo3801 7 ปีที่แล้ว

    well in Ohio, you need to be state licensed / certified to install and test back flows

  • @Sticknmove8
    @Sticknmove8 7 ปีที่แล้ว

    🤦🏽‍♂️ this man called the manifold a "valve cluster" done w the video after 1:03

  • @mongo_N_machines
    @mongo_N_machines 10 ปีที่แล้ว

    Ahhhhh! No dielectric unions between the galvanized and brass? Nooooo!

    • @Iscaper
      @Iscaper  10 ปีที่แล้ว

      In our area if you're going from copper to galvanized, you need a dielectric union. If you go galvanized to brass, you don't.

    • @mongo_N_machines
      @mongo_N_machines 10 ปีที่แล้ว

      iScaper1 Physics is physics regardless of where you live. Brass is usually around %65 copper. It'll still carry the current that makes corrosion possible. We carried jumper cables in our trucks in order to jump the water meter setting if current was grounding to the pipes during replacement. Up to you though. Good luck.

    • @Iscaper
      @Iscaper  10 ปีที่แล้ว

      mongo586
      All the plumbers I know around here use galvanized not because of physics but because of economics. Galvanized nipples and fittings are much cheaper than brass nipples and fittings.

  • @vinnygoombatts1458
    @vinnygoombatts1458 8 ปีที่แล้ว +3

    your backflow is sideways and must have the test ports upright. also your backflow is brass and your fittings are galvanized. can't mix metals and have water run through them. national Plumbing code

    • @mcroley591
      @mcroley591 7 ปีที่แล้ว

      Vinny Gumbats. Not correct, the RPZ is brass. Galvanized to brass is fine.

  • @adamchou9123
    @adamchou9123 3 ปีที่แล้ว

    You should be using a male pvc to go into metal female. Less likely to crack the male pvc. Male metal will be much more likely to crack female pvc if you over tighten.

    • @Iscaper
      @Iscaper  3 ปีที่แล้ว

      PVC male and female adapters don't do well when transitioning to brass or galvanized fittings. I had to learn this the hard way. That's why I used a PVC threaded bushing glued into a slip coupling. It makes the transition joint much stronger.

  • @seanduncan6121
    @seanduncan6121 11 ปีที่แล้ว +1

    10:18 Ice cream truck

  • @XIANBLACK
    @XIANBLACK 7 ปีที่แล้ว

    this BFP is way overkill for your sprinkler system. smh

    • @joeadams2959
      @joeadams2959 6 ปีที่แล้ว

      Not if your grade is too high above where you can put protection. You need pvb .12" above highest head.

  • @bashucker1
    @bashucker1 7 ปีที่แล้ว

    So many things wrong with this installation. Please refer to your AHJ. Don’t know which state you are in but unfortunately this would never pass inspection. Did city supply you with RPBA.

  • @epcortek11
    @epcortek11 7 ปีที่แล้ว

    Galvanized on a potable water system !!! How you dont get cancer bro.

  • @malkerian
    @malkerian 3 ปีที่แล้ว

    Wth that doesn't look right.

  • @mickeyphillips741
    @mickeyphillips741 6 ปีที่แล้ว

    As a licensed CSI, I found many problems with this video. For starters a licensed plumber should be performing the installation of the backflow assembly, and a licensed bpat person should test the device upon installation and annually thereafter with copy of test reports being submitted to your water utility provider, I wouldn’t use galvanized pipe for water lines due to rapid corrosion rates, your rpz assembly is also installed improperly being turned sideways. Also if this is just for a residential irrigation system, I wonder why your utility provider called for the more expensive rpz assembly when a double check valve assembly would have served the purpose and been more economic.

    • @Iscaper
      @Iscaper  6 ปีที่แล้ว

      Installation was inspected twice by the city. I did turn the vent on the backflow preventer down (not shown in video). The city required the reduced pressure backflow preventer which was around $200 more than the regular double check assembly.

    • @jamey9758
      @jamey9758 4 ปีที่แล้ว

      A double check valve doesn't do the trick, because you can't see when it fails. Works when dealing with non-hazardous water, like fire suppression, but not with hazardous water, like irrigation.

  • @eddieserna5494
    @eddieserna5494 5 ปีที่แล้ว

    Lmao..he’s wearing gloves.

    • @TheOmarbravo9
      @TheOmarbravo9 5 ปีที่แล้ว +1

      eddie serna what’s wrong with wearing gloves huh?

    • @residentmanager3088
      @residentmanager3088 4 ปีที่แล้ว

      He must not love cancer as much as you do.

    • @eddieserna5494
      @eddieserna5494 4 ปีที่แล้ว

      Resident Manager or maybe he doesn’t have a set of balls like I do lol..

  • @naturalhealing9970
    @naturalhealing9970 7 ปีที่แล้ว

    You voice is so soft I cannot follow you!

  • @jonathanbielert9165
    @jonathanbielert9165 6 ปีที่แล้ว

    I have this video a thumbs down because your using galvanized pipe, which is cancer for irrigation. They rust and corrode causing issues with your backflow, your control valves and clogs nozzles. Also galvanized unions swell from corrosion and are an issues removing and resealing. I would prefer you remove this video because it's giving bad advise. I'm an irrigation professional and been doing it for almost 10 years. If you would of done this in sch 80 pipe, copper or even brass would of worked but galvanized is horrible.

    • @Iscaper
      @Iscaper  6 ปีที่แล้ว +2

      The installation was inspected and passed by the city. Schedule 80 pipe fades in sunlight and will snap off if bumped by a lawn mower. Copper doesn't do well exposed to the elements either. Brass is the best solution but most homeowners don't want the added cost when the city will approve galvanized. Probably 95% of the above ground BF preventers I see in this valley are plumbed with galvanized.

    • @jamey9758
      @jamey9758 4 ปีที่แล้ว

      @@Iscaper Whether it's approved or not will be the least of your worries. Saving by using galvanized is penny-wise and dollar-foolish. I've had to rebuild backflows because of premature wear from this "pipe cancer" you're going to get from using galvanized, not to mention what it will do to your valves, nozzles, check valves, etc. Sorry, chum.

  • @stupidutubeletmein
    @stupidutubeletmein 11 ปีที่แล้ว

    My city has extensive backflow prevention requirements, but it turns out that it doesn't apply to residential properties. I have a 60 year old sprinkler system and no backflow prevention. So when I replaced the supply line with PEX I threw in a dual check valve. It was simple and compact, and could be put down in the shutoff valve vault.

  • @JediMasterHilljr
    @JediMasterHilljr 2 ปีที่แล้ว

    What kind of pipe thread compound do you use? I assume it isn’t to cement the pieces together but to seal and stop leaks, correct?

    • @Iscaper
      @Iscaper  2 ปีที่แล้ว +1

      I've been using Oatey Great White teflon paste.