How to Improve Power factor from 0.8 to 1.0 in tamil

แชร์
ฝัง
  • เผยแพร่เมื่อ 9 ก.ย. 2024
  • Power factor Improvement from 0.8 to 0.96 for 440 Volts, 500 Amps:
    Calculate the reactive power consumption of exiting system:
    Now consider power factor is 0.8 then lets we calculate the reactive power requirement:
    cos⁡〖∅=0.8〗
    ∅=cos^(-1)⁡0.8
    ∅=36.6 deg
    Reactive Power Drawing from the source=1.732 VI Sin∅
    Q=1.732*440*500*sin36.6
    Q=1.732*440*500*0.58
    Q=220 KVAR
    In this condition the load is drawn 220 KVR from the source.
    Now consider the power factor is 0. 96.. then calculate the required reactive power
    cos⁡〖∅=0.96〗
    ∅=cos^(-1)⁡0.96
    ∅=16.2 deg
    Reactive Power requirement=1.732 VI Sin∅
    Q=1.732*440*500*sin16.2
    Q=1.732*440*500*0.27
    Q=103 KVAR
    Hence the net reactive power compensation to be done is 220-103= 117 KVAR
    Hence to improve power factor we should contribute 117 KVAR.
    We can add at least four number of 25 KVR capacitor bank to our system.
    Read more: techdoct.com
    Download Free Electrical Calculator Best android app for Electrical Engineer and EEE student the app from play store:
    goo.gl/VPNp5h
    Subscribe this channel and Support US
    How to Get Electrical License in Tamil:
    • Electrical License in ...
    Electrical Interview Questions in Tamil: • தமிழ் What is Creepage...
    All about Transformer in Tamil:
    • Equipotential shieldin...
    Electrical in Tamil Most Useful Videos:
    • What is Hysteresis Los...
    48 types of Generator Protection in Tamil:
    • Droop CT, Droop Curren...
    Most Popular Videos:
    Why CT secondary should not be in Open Circuit in Tamil:
    • எதுக்கு CT open circui...
    What is Harmonic in tamil. What is 3rd harmonic and 5th Harmonic in Tamil:
    • Harmonics என்றால் என்ன...
    Alternator in Tamil:
    • Alternator in Tamil
    Why Transformer Rating KVA:
    • Why Transformer rating...
    How to Read Bearing Number in Tamil
    • Bearing Number ஐ புரிந...
    Standby Earth Fault Protection in Tamil:
    • What is Standby Earth ...
    Restricted Earth Fault Relay in Tamil
    • What is Restricted Ear...
    PSM & TSM Calculation in Tamil:
    • How to Calculate Plug ... Whatsapp:whatsappgroups...

ความคิดเห็น • 83

  • @SenthilKumar-fs2sp
    @SenthilKumar-fs2sp 3 ปีที่แล้ว +1

    Power Angele eppadii sir. Pargarathu

  • @kumarar745
    @kumarar745 5 ปีที่แล้ว

    Ur voice and explaining is nice

  • @BalaMurugan-tf3zd
    @BalaMurugan-tf3zd 5 ปีที่แล้ว

    Thanks bro semmaya explain pandringa...

  • @srn.raviselvan341
    @srn.raviselvan341 6 ปีที่แล้ว +2

    Itha phaser diagram vachu explain pannunaga.. because industrial load takes lagging current but capacitor provide leading current.
    Then how I can feed reactive power to load

  • @sathishkumar500
    @sathishkumar500 5 ปีที่แล้ว +2

    Sir we are using major resistive load in our plant but i need to calculate inductive load only how can calculate separately inductive and resistive load

  • @SureshKumar-zh3yx
    @SureshKumar-zh3yx 5 ปีที่แล้ว

    Great Simple method calculations. Keep it up.

  • @manikayal4068
    @manikayal4068 6 ปีที่แล้ว +3

    hi.sir Nan companyla supervisora irukkaen.c license vaithullaen HT linela inspection eppadi irukka vendum ennalam parpanga.

    • @Techdoct
      @Techdoct  6 ปีที่แล้ว

      panel insulation test papanga..athuthan mukkiyam...

    • @ibrahimsyed511
      @ibrahimsyed511 4 ปีที่แล้ว

      Thanks bro.

  • @mosesgnanasekar3627
    @mosesgnanasekar3627 5 ปีที่แล้ว +2

    Super bro nice video keep them coming

    • @Techdoct
      @Techdoct  5 ปีที่แล้ว

      Welcome Keep Supporting Us

    • @ashokkumar-mk5uo
      @ashokkumar-mk5uo 4 หลายเดือนก่อน

      Bro unga number kadaikumaa please Enku Dout kekA use erukum

  • @technicalnanba8312
    @technicalnanba8312 5 ปีที่แล้ว +1

    Unga videos ellame super nanba 👌

  • @aravintharavinth6681
    @aravintharavinth6681 5 ปีที่แล้ว +1

    Last la konjam purila jii ya last la 0.8value to 0.96 value rendum compare pandringa konjam detail ah sollunga

  • @mohanpuyalkurvin6662
    @mohanpuyalkurvin6662 4 ปีที่แล้ว

    Bro na ipo veetuku inverter vaikanum adhuku 0.6 to 08 idhuKu epdi power factor calculate pandradhu na ORU 200 wats use pandra adhuku epdi power calculate pandradhu detail a sollunga bro plz Aron idhu inverter la use pandra load poruthu power factor colculate pannanuma detail a sollunga bro plz

  • @ahilcuts7971
    @ahilcuts7971 6 ปีที่แล้ว +3

    Bro EPA nega 4 25kvr capacitor bank use pandriga namaku 117 kvr vanum ... 25 kvr 4 add panuna namaku 100kvar than na varum

    • @Techdoct
      @Techdoct  6 ปีที่แล้ว +2

      Thanks Nanba...Nanba thats..only for explanation...yes we should use 5 number of 25 kVAR

    • @ahilcuts7971
      @ahilcuts7971 6 ปีที่แล้ว +1

      @@Techdoct ok bro

  • @gobinathg3361
    @gobinathg3361 4 ปีที่แล้ว

    Nanba anda amps pathi soningla starting la amps R Y B amps varum each phase , den Kw , KVA , KVAR , am confusing , other explanation i 100% observed , very useful

  • @naarinaari9426
    @naarinaari9426 3 หลายเดือนก่อน

    1.732*440*500*0.58 multiple pannunaa 224,813.6 varuthu bro...220kvar vara enna pannanum bro

  • @mohanrajr5364
    @mohanrajr5364 4 ปีที่แล้ว

    Hi,. In one site I face a low power factor issues. Leading 0.85 without connecting capacitor bank..we don't have any fixed capacitor. TNEB charges penalty
    For low PF. Bro u have any idea to improve the pf

  • @arunkumar-sq8sj
    @arunkumar-sq8sj 5 ปีที่แล้ว

    Superb bro... Thank you

  • @OMPRAKASH-ns7ml
    @OMPRAKASH-ns7ml 4 ปีที่แล้ว

    Bro nanga load eha use pannala 10A use panrom anal 0.8 pf varuthu etha eppadi 0.9 pf konsuvarathu?

  • @thangarasuappavoo3999
    @thangarasuappavoo3999 3 ปีที่แล้ว

    Good explanation. Try to speak a little slower, so that people can understand every word of your explanation.

  • @SenthilKumar-fs2sp
    @SenthilKumar-fs2sp 3 ปีที่แล้ว

    Pr kvar ennral Enna sir antha alavu capacitor podalllama

  • @smilesyrups8175
    @smilesyrups8175 3 ปีที่แล้ว

    Angle value epdi find pandrathu theriyala Bro? U r not giving full explanation Compare other video may b lack of Maths knowledge

  • @madhanraj38
    @madhanraj38 4 ปีที่แล้ว

    Power factor 0.8 kammiya pochuna load current increase agumngna.

  • @sivageethan6920
    @sivageethan6920 2 ปีที่แล้ว

    How to see the cos-1 value check this detail

  • @VinothKumar-rk4eb
    @VinothKumar-rk4eb 5 ปีที่แล้ว

    100kvar powerbank எவ்வளவு power consume பன்னும்

  • @sivageethan6920
    @sivageethan6920 2 ปีที่แล้ว

    How to check angle

  • @vimalraj6386
    @vimalraj6386 5 ปีที่แล้ว +1

    Thanks so much bro

    • @Techdoct
      @Techdoct  5 ปีที่แล้ว

      Welcome Keep Supporting Us

  • @rajkumar-oi6im
    @rajkumar-oi6im 4 ปีที่แล้ว

    Thank you so much nanba

  • @tamilselvan8784
    @tamilselvan8784 5 ปีที่แล้ว +1

    Arumai sir

  • @kabikutty8107
    @kabikutty8107 4 ปีที่แล้ว

    Power factor Lagging Leading என்றால் என்ன Details ah Explain Pannunga bro

  • @spps1892
    @spps1892 2 ปีที่แล้ว

    Great video

  • @PraveenKumar-qd2ny
    @PraveenKumar-qd2ny 5 ปีที่แล้ว +3

    DG la epdi power factor find out pannurathu

    • @Techdoct
      @Techdoct  5 ปีที่แล้ว +1

      Using external meter only

  • @vijayarajan4282
    @vijayarajan4282 4 ปีที่แล้ว

    117 kvar use panna load amps 500 reduce aaguma bro

  • @KarthiKeyan-ig7ug
    @KarthiKeyan-ig7ug 4 ปีที่แล้ว

    Thanks brother

  • @aasaimurugesan5044
    @aasaimurugesan5044 5 ปีที่แล้ว +2

    How to find the angle value

    • @Techdoct
      @Techdoct  5 ปีที่แล้ว

      Take respective inverse...i.e sin inverse gives the angle of the value

  • @tamil0213
    @tamil0213 5 ปีที่แล้ว +1

    Good, keep posting bro....

    • @Techdoct
      @Techdoct  5 ปีที่แล้ว

      Nandri nanba

  • @manikayal4068
    @manikayal4068 6 ปีที่แล้ว +1

    hai sir electrical c license vaithu ennalam pannalam.next motor and gear box rating kandupidippadhu konjam sollunga

    • @Techdoct
      @Techdoct  6 ปีที่แล้ว

      illa....exp certificate iruntha pothum

    • @Techdoct
      @Techdoct  6 ปีที่แล้ว

      Kassu sampathikkalam...

    • @manikayal4068
      @manikayal4068 6 ปีที่แล้ว

      @@Techdoct eppadi

  • @dileepkumar-so5hd
    @dileepkumar-so5hd 3 ปีที่แล้ว

    How you get 36.6 deg sir

  • @peterjude3205
    @peterjude3205 5 หลายเดือนก่อน

    நீங்கள் சொன்ன விசயங்கள் சரிதான் . Cos , sin இது தெரியாதவர்களும் புரிந்து கொள்ளும் வகையில் ஒரு வீடியோ போட்டா நன்றாக இருக்குமே !

  • @SenthilKumar-fs2sp
    @SenthilKumar-fs2sp 3 ปีที่แล้ว

    Degree eppati sir calculate seivatu

  • @prakashksp2918
    @prakashksp2918 4 ปีที่แล้ว

    Super sir

  • @kesavanchandran1840
    @kesavanchandran1840 5 ปีที่แล้ว +1

    Megger and multimeter pathi vdo podunga nanba.....

    • @Techdoct
      @Techdoct  5 ปีที่แล้ว

      Sure nanba

  • @nandhakumar7014
    @nandhakumar7014 4 ปีที่แล้ว

    Hi bro, my company avg PF 8.5,,
    It's increase to 9or above men's ,
    Any benefit for us or nothing,,
    An also suggest me some idea for reduce EB bill

    • @rajaprabum3153
      @rajaprabum3153 3 ปีที่แล้ว

      Yeah 8.5 is a lagging pf... You should pay penalty to eb...

  • @sudheeshpillai8078
    @sudheeshpillai8078 ปีที่แล้ว

    HT bill penalty show and incentive

  • @nprabu9903
    @nprabu9903 ปีที่แล้ว

    Hi Anna nics ok Anna pf kudunalum
    Kuransalu amond kuduma anna

  • @kalimuthuprema6924
    @kalimuthuprema6924 6 ปีที่แล้ว +1

    What happened when capacitor bank connected in no load. And the cap bank connected when lighting load time may be pf was increase

    • @Techdoct
      @Techdoct  6 ปีที่แล้ว +2

      The reactive power goes to the source..because once capacitor bank is connected to the source then the capacitor starts injecting reactive power irrespective of the load. You get leading power factor,which means the source aborbe the reactive power from the capacitor bank..finally the source voltage rises abnormally...In generator one protection "Reverse reactive power protection" is used to protect such condition...

    • @kalimuthuprema6924
      @kalimuthuprema6924 6 ปีที่แล้ว +1

      @@Techdoct thank u sir

    • @Techdoct
      @Techdoct  5 ปีที่แล้ว

      You can read detailed information here:
      www.techdoct.com/why-question/what-happen-capacitor-bank-connected-in-no-load/

  • @r.s.coachingclassesbygurup7354
    @r.s.coachingclassesbygurup7354 3 ปีที่แล้ว +1

    Please make this video in English Also

  • @vimalraj6386
    @vimalraj6386 5 ปีที่แล้ว +2

    Bro nenga ean 1 power factor ku calculation podala

    • @Techdoct
      @Techdoct  5 ปีที่แล้ว

      appade illa...ungalukku priyannum la athan

  • @M.veeraragavan
    @M.veeraragavan 5 ปีที่แล้ว

    Powerfactor 1kkum Mela r 1 maintain panna Enna aagum?

  • @electrictech7996
    @electrictech7996 5 ปีที่แล้ว

    How to find digre

  • @ssdgensets
    @ssdgensets 5 ปีที่แล้ว +1

    Genset related any video pls sir

    • @Techdoct
      @Techdoct  5 ปีที่แล้ว

      Sure nanba

  • @vasanthakumars1421
    @vasanthakumars1421 6 ปีที่แล้ว

    👌

    • @Westernpiston
      @Westernpiston 5 ปีที่แล้ว

      Sir neenga neenga 500a caculation pannirukrenga itu single phase or three phase

  • @smilesyrups8175
    @smilesyrups8175 3 ปีที่แล้ว

    But Enakum maths varathu that's Different thing

  • @edisonelectricaltamil3256
    @edisonelectricaltamil3256 5 ปีที่แล้ว

    Online ups explain

  • @Dadrate
    @Dadrate 6 ปีที่แล้ว +2

    Anna unga personal no kadaikuma

    • @Techdoct
      @Techdoct  6 ปีที่แล้ว

      check the description

  • @edisonelectricaltamil3256
    @edisonelectricaltamil3256 5 ปีที่แล้ว

    Super sir