Short Circuit Fault Level Calculation

แชร์
ฝัง
  • เผยแพร่เมื่อ 13 ก.ค. 2024
  • In this video , Electrical fault level calculation for short circuit faults is shown.
    After seeing this video , concept of fault level calculation for given single line diagram will be cleared.

ความคิดเห็น • 157

  • @hijazahmad1736
    @hijazahmad1736 4 ปีที่แล้ว +1

    Nice... I was searching for this type of explanation.. Excellent

  • @charzanboo9940
    @charzanboo9940 3 ปีที่แล้ว +2

    I was asked to perform the above short circuit calculation in an interview...in my head.

  • @kachhuap3ycentre505
    @kachhuap3ycentre505 3 ปีที่แล้ว

    Beautiful video . Thank you so much sir.

  • @muhammadabduljaleel1811
    @muhammadabduljaleel1811 4 ปีที่แล้ว

    Very nice with good explanation

  • @umaid-nungshatpa
    @umaid-nungshatpa หลายเดือนก่อน

    Hi
    Informative
    New Subscriber

  • @pietervdberg7055
    @pietervdberg7055 3 ปีที่แล้ว +6

    Nice video if the questions can be explained. A number of people (including myself) asked why the factor of 1.05 comes into the equation. I still prefer the per unit method. It eliminates the need to determine what voltages should be used at different levels if you have multiple transformers.
    Also, all those motor loads will definitely contribute to increasing the Isc at point 3. Suggestion is that if you don’t want to bring motor contribution into example, don’t specify motor loads. It can confuse some readers thinking that you don’t need to add motor contribution.

    • @ratssaesquareallaboutelect5919
      @ratssaesquareallaboutelect5919  3 ปีที่แล้ว +7

      Thank you for sharing your views and thank you for the question, Answer to 1.05 question is : 1.05 is a voltage factor required in the calculation to
      account for Voltage variations in the system,if we consider voltage variation of +-6% in voltage , we have to use factor of 1.05 in the formula as per standard IEC 60909.

    • @pietervdberg7055
      @pietervdberg7055 3 ปีที่แล้ว

      @@ratssaesquareallaboutelect5919
      Thank you for your reply. Much appreciated.

    • @richhall3662
      @richhall3662 3 ปีที่แล้ว

      @@pietervdberg7055 Also note that motor contribution only occurs for 3 to 4 cycles for asynchronous or 6 cycles for synchronous machines, so not a huge factor when sizing equipment based on steady state conditions or fault levels that can exist for hundreds of milliseconds or more. Also the 1.05 takes into account the voltage factor or voltage rise that occurs on phase due to the raised neutral potential and normally relevant on single phase shorts

    • @sumitmondal548
      @sumitmondal548 2 ปีที่แล้ว

      @@richhall3662 nice

  • @atoz5950
    @atoz5950 3 ปีที่แล้ว

    Many thanks for you .. please and kindly, Re-calculate the Isc for generators

  • @vikasgupta-hl9sq
    @vikasgupta-hl9sq 3 ปีที่แล้ว

    Explained very nice

  • @ImranKhan-nu6xw
    @ImranKhan-nu6xw 2 ปีที่แล้ว

    Thanks nice vedio about short circuit study

  • @user-yd1mr6ir9d
    @user-yd1mr6ir9d 8 หลายเดือนก่อน

    one of the best

  • @ricrobertogonzales8341
    @ricrobertogonzales8341 3 ปีที่แล้ว +2

    what is the effect of the motors in the short circuit calculation?

  • @musabkanani2873
    @musabkanani2873 4 ปีที่แล้ว +1

    Iam senior electrical engineer
    Your explain is soo good so thanks

    • @walterlopez5465
      @walterlopez5465 3 ปีที่แล้ว

      Excuse me Sir, can you tell which standard support this calculation, i'd really appreciate your answer. Greetings!

  • @justinlow-thion77
    @justinlow-thion77 11 หลายเดือนก่อน

    very good video tutorail. simple explanation and easy to understsnd

  • @noname-ug2qx
    @noname-ug2qx 2 ปีที่แล้ว +1

    Why is the backup generator not included when calculating If at point 2 (Busbar)?

  • @jkj1459
    @jkj1459 4 ปีที่แล้ว +1

    BEAUTIFUL

  • @RaviShankar-sj7qs
    @RaviShankar-sj7qs 5 ปีที่แล้ว

    Very Informative video admin. Please upload video of disadvantages of harmonics and ways to arrest them.

  • @user-gk7pn2zh3x
    @user-gk7pn2zh3x 5 หลายเดือนก่อน

    Very good .
    .

  • @mthuthuzelimatsheke5422
    @mthuthuzelimatsheke5422 ปีที่แล้ว +1

    It's so meaningful and professional classes i would like to join as a mamber please admin

  • @subhendumukhopadhyay3535
    @subhendumukhopadhyay3535 9 หลายเดือนก่อน

    Nice one

  • @trimafs
    @trimafs 3 ปีที่แล้ว

    Hi,
    Thanks for informative video can you please also give the reference for formulas

  • @liewts1049
    @liewts1049 4 ปีที่แล้ว +6

    Could you also comment on the assumption made on the impedance of the power supply utility? Thank you.

  • @satishkumar-wm9yl
    @satishkumar-wm9yl ปีที่แล้ว

    please can you share and update more videos of typical calcualtions of short ckt Transformers and RMU Swithchgears, thanks

  • @ktsmurthy21
    @ktsmurthy21 5 ปีที่แล้ว +3

    If Generator(1.5 MVA) is running , Then How to Calculate Fault current.

  • @joegellido2596
    @joegellido2596 5 ปีที่แล้ว +2

    The presentation will be complete if motor contribution to fault is considered which is very important factor..

  • @prakashksp2918
    @prakashksp2918 ปีที่แล้ว

    Please upload videos on instantaneous current formula

  • @sakirdag2976
    @sakirdag2976 4 ปีที่แล้ว +1

    thx

  • @loubensoctave3986
    @loubensoctave3986 5 ปีที่แล้ว +5

    Nice video. How can I contact you? I have many questions to ask.

  • @ranjan1436
    @ranjan1436 5 ปีที่แล้ว

    please explain, how? to size the KVA of a transformer.

  • @niksontalan5803
    @niksontalan5803 3 ปีที่แล้ว

    How to calculate MVAsc on transformator and feeder

  • @mourshadhaider7361
    @mourshadhaider7361 4 ปีที่แล้ว +3

    Could you please explain number "10" in the formula for z(transformer). Where did it come from.

    • @itanongmokayengineer
      @itanongmokayengineer 3 ปีที่แล้ว

      its contant in order not to include the thousand in the kva of transformer instead using 2000000 you will use 2000

  • @coopers0218
    @coopers0218 4 ปีที่แล้ว +3

    Pls help with data sheet reference for Cable impedance value. It seems you have considered Cable resistance value instead of Impedance. Pls clarify. Thanks

    • @Nour-ds3ib
      @Nour-ds3ib 3 ปีที่แล้ว

      If you multiply kva by 1000 and kv by 1000 but undersquare and make per unit impedance 0.06
      It makes the same number

    • @devendrasharma2418
      @devendrasharma2418 3 ปีที่แล้ว

      You are right, I think data of DC resistance value has been considered here, instead of which cable impedance as per manufacturer's data should have been considered.

  • @niluv3982
    @niluv3982 ปีที่แล้ว +1

    nice

  • @jkmultimediasolutions3935
    @jkmultimediasolutions3935 2 ปีที่แล้ว

    Thanks for the video.
    Please when you mentioned number of runs; did you mean the number of cables or what ?
    Please, explain it further.
    Thanks.

  • @e-powersolution7225
    @e-powersolution7225 11 หลายเดือนก่อน

    1:41 thanks for your video, why while calculating z transformer multiple with 10

  • @tapasbarua4301
    @tapasbarua4301 2 ปีที่แล้ว +1

    Very nice video. But I did not see any contribution of motors into the fault point as a secondary source and alternator and also why you have included 1.05XV in the calculation?

  • @surendrakverma555
    @surendrakverma555 3 ปีที่แล้ว +1

    Good

  • @soumya2221
    @soumya2221 2 ปีที่แล้ว

    What is the fault current contribution from motor

  • @zainliaquat9537
    @zainliaquat9537 2 ปีที่แล้ว

    Can you please explain why you are dividing the line voltage by the square root of 3 in Isc formula (At Point 1) ? Your response will be very helpful.

    • @jay403
      @jay403 ปีที่แล้ว

      it is incorrect. There is no point dividing by root3. Any current is simply V/Z. 1.05 is form factor.

  • @shelfrobthomas449
    @shelfrobthomas449 5 ปีที่แล้ว

    is 1.05 in the equation a constant value and how about the impedance value of cable ohms per km is it also constant?

    • @ratssaesquareallaboutelect5919
      @ratssaesquareallaboutelect5919  5 ปีที่แล้ว

      1.05 is part of equation and impedance of cable can be obtained from the cable manufacturer .
      Thanks for writing

    • @rasengan9743
      @rasengan9743 2 ปีที่แล้ว

      1.05 is a voltage correction factor
      Voltage maximum/voltage minimum
      440÷410

  • @manojshukla3598
    @manojshukla3598 5 ปีที่แล้ว +3

    how 1.5 comes in this equation

  • @amritthakur9712
    @amritthakur9712 10 หลายเดือนก่อน

    Nice

  • @sunilkumarmoharana7639
    @sunilkumarmoharana7639 4 ปีที่แล้ว +5

    Please explain the factor 1.05. how it comes.

    • @mazmaz1981
      @mazmaz1981 4 ปีที่แล้ว +1

      sunil kumar moharana 5% voltage tolerance, which is very typical.

    • @ratssaesquareallaboutelect5919
      @ratssaesquareallaboutelect5919  3 ปีที่แล้ว

      thank you for the question, Answer to 1.05 question is : 1.05 is a voltage factor required in the calculation to
      account for Voltage variations in the system,if we consider voltage variation of +-6% in voltage , we have to use factor of 1.05 in the formula as per standard IEC 60909.

  • @mazmaz1981
    @mazmaz1981 4 ปีที่แล้ว +3

    What about motors contribution to the fault?

    • @Keepit-nq3id
      @Keepit-nq3id 4 ปีที่แล้ว

      Good question the reverse currents shall be calculated

  • @mudasirhashmi8907
    @mudasirhashmi8907 3 ปีที่แล้ว +2

    How do you the cable impedance as .0077 and what are the formula you are using

  • @MEOVLOGz
    @MEOVLOGz หลายเดือนก่อน

    what method is this?

  • @vijaymaurya9070
    @vijaymaurya9070 5 ปีที่แล้ว

    Z of cable where this value ,how to find catalogue or other method pl explain

  • @kritabarma
    @kritabarma 2 ปีที่แล้ว

    What about motor contributions??

  • @velusamypothiraj2300
    @velusamypothiraj2300 4 ปีที่แล้ว +2

    Where it's coming 10, in impedance of transformer, what is the fault current in 11kv side

  • @liewts1049
    @liewts1049 4 ปีที่แล้ว

    Thank you for the nice video, this considered single phase to ground fault. Would you also make a fault current calculation video for ph-ph, ph-ph-gnd, 3ph fault?

    • @fereshteh5205
      @fereshteh5205 2 ปีที่แล้ว +1

      @@yaminoshinn1473 415 v is line voltage, by dividing on sqr3, it would be phase voltage

  • @mohammedsaifullah6437
    @mohammedsaifullah6437 4 ปีที่แล้ว +1

    But what about generator current

  • @bradencutajar3301
    @bradencutajar3301 4 ปีที่แล้ว +6

    At 1:43, there is no reason to multiply by 10

    • @shuvanilmukherjee1595
      @shuvanilmukherjee1595 ปีที่แล้ว +1

      I THINK SHE DONT KNOW

    • @abcdchanchan1
      @abcdchanchan1 ปีที่แล้ว

      Maybe No need to multiply by 10, she can’t explain

    • @JDABD
      @JDABD 25 วันที่ผ่านมา

      Why it is multiplied by 10?

  • @jcazur70
    @jcazur70 ปีที่แล้ว

    Why did you not consider the contribution of the motors below and the generator above whose ratings are significant????

  • @lanzsolissiargao8477
    @lanzsolissiargao8477 4 ปีที่แล้ว +1

    What do you mean of number of runs?

  • @patelkaushik2996
    @patelkaushik2996 3 ปีที่แล้ว +1

    Medam send video for HT 11KV TO LT 415 V relay coordination method

  • @malam4883
    @malam4883 4 ปีที่แล้ว

    What should be breaking capacity of cb at point 3.

    • @kilumumahesh935
      @kilumumahesh935 3 ปีที่แล้ว +1

      Mr M.salam
      The breaking capacity of the breaker purely depends on load nature.
      Ex: if your load 80% const power & 20% const impedance. Then the SC contribution will be some value..
      Or
      If you load purely 100% constant power load, then the SC Current from the load will be some other value..
      So as per above examples the SC Current contribution from the load side may very as per the load type..
      Therefore = SC Current contribution from upstream + SC Current contribution from load end side = breaking capacity of the breaker nothing but (Ics or Icu)..

    • @kilumumahesh935
      @kilumumahesh935 3 ปีที่แล้ว

      To each and everyone ..
      First go through the video carefully ..
      Why everyone asking regarding what about load SC Current contribution..??
      Channel was created fault at the Trafo LV bus. From the upstream we can find Trafo SC current contribution and from Downstream the load SC current contribution.
      The upstream and downstream SC currents will get added up and visible to us at Bus right side..
      So channel was trying to stress the point is how to calculate the fault current contribution from the upstreams not from the load end side or downstream side..
      The channel was not stressing any point like.. this is the RMS SC current so based upon the this SC current only you have to choose breaker Ics or Icu..
      Hope everyone understood..
      Thank you...

  • @sungmopark0405
    @sungmopark0405 5 ปีที่แล้ว +1

    Could you explain why symmetrical fault
    L-L-L-G and L-L-L is same?

    • @ratssaesquareallaboutelect5919
      @ratssaesquareallaboutelect5919  5 ปีที่แล้ว

      The behaviour of LLLG fault and LLL fault is identical due to the balanced nature
      of the fault
      Three phases are equally affected in these type of faults and the system remains balanced.
      Hope your query is resolved and pl keep watching the channel for more useful videos.
      thanks.....

  • @poojap2508
    @poojap2508 4 ปีที่แล้ว +1

    Hw did u get 1.05 while calculating Isc

    • @ratssaesquareallaboutelect5919
      @ratssaesquareallaboutelect5919  3 ปีที่แล้ว

      thank you for the question, Answer to 1.05 question is : 1.05 is a voltage factor required in the calculation to
      account for Voltage variations in the system,if we consider voltage variation of +-6% in voltage , we have to use factor of 1.05 in the formula as per standard IEC 60909.

  • @crisrobersonsantos9192
    @crisrobersonsantos9192 5 ปีที่แล้ว +1

    Is the short circuit at fault 3 = 32.58 KA?

    • @ratssaesquareallaboutelect5919
      @ratssaesquareallaboutelect5919  5 ปีที่แล้ว

      thanks for writing to the channel , I Sc at point number 3 is : 33.5KA
      Pl keep on watching the Channel for other useful videos.

  • @TheSuperAboody
    @TheSuperAboody 4 ปีที่แล้ว +1

    What do you mean by Number of Runs?

    • @Keepit-nq3id
      @Keepit-nq3id 4 ปีที่แล้ว

      For example 3 cable runs means 3 number of cables

    • @TheSuperAboody
      @TheSuperAboody 4 ปีที่แล้ว

      Thank you

  • @jinishcrajan
    @jinishcrajan 4 ปีที่แล้ว +1

    can explain how 1.05 has been considered

    • @ratssaesquareallaboutelect5919
      @ratssaesquareallaboutelect5919  3 ปีที่แล้ว

      thank you for the question, Answer to 1.05 question is : 1.05 is a voltage factor required in the calculation to
      account for Voltage variations in the system,if we consider voltage variation of +-6% in voltage , we have to use factor of 1.05 in the formula as per standard IEC 60909.

  • @atmsc4nd4l
    @atmsc4nd4l 3 ปีที่แล้ว

    and why is that motor contribution is neglected?

  • @anugarg4864
    @anugarg4864 5 ปีที่แล้ว

    Dear Mam,
    Please tell me about the number of run ,What is this ?

  • @mdshamsealam4024
    @mdshamsealam4024 3 ปีที่แล้ว +1

    How number of runs between point 1 and 2 are 7 ?

  • @rolandomullasgo48
    @rolandomullasgo48 ปีที่แล้ว

    Where did you get 1.05 shown in your cakculation.

    • @ratssaesquareallaboutelect5919
      @ratssaesquareallaboutelect5919  ปีที่แล้ว

      As per standard IEC 60909 - 2001 , We have to consider the voltage factor of 1.05 in LV fault calculation (100V to 1000V).

  • @thajmulhussain4144
    @thajmulhussain4144 3 ปีที่แล้ว

    HOW YOU DETERMINED OHMS(0.0778) AT BETWEEN POINT 1 TO2)AT3.41?

  • @madhusudan6395
    @madhusudan6395 ปีที่แล้ว

    What is 1.05?
    Pl.describe

  • @lov7587
    @lov7587 3 ปีที่แล้ว +1

    Hi Sir, How did you get the figure of 1.05 in the formula? Please advice.....

    • @ratssaesquareallaboutelect5919
      @ratssaesquareallaboutelect5919  3 ปีที่แล้ว +1

      thank you for the question, Answer to 1.05 question is : 1.05 is a voltage factor required in the calculation to
      account for Voltage variations in the system,if we consider voltage variation of +-6% in voltage , we have to use factor of 1.05 in the formula as per standard IEC 60909.

    • @user-gk7pn2zh3x
      @user-gk7pn2zh3x 5 หลายเดือนก่อน

      IF the Voltagebminus side ,variation is 10% on plus sideand,what. is the factor.

  • @rkthemgil
    @rkthemgil 3 ปีที่แล้ว +1

    What is 1-05 in the formula?

    • @ratssaesquareallaboutelect5919
      @ratssaesquareallaboutelect5919  3 ปีที่แล้ว

      thank you for the question, Answer to 1.05 question is : 1.05 is a voltage factor required in the calculation to
      account for Voltage variations in the system,if we consider voltage variation of +-6% in voltage , we have to use factor of 1.05 in the formula as per standard IEC 60909.

  • @dilermehndishirazee8077
    @dilermehndishirazee8077 5 ปีที่แล้ว

    Four 20KVA generators are connected to 11 kV bus what is the Fault MVA at bus?

    • @aspiringenggs1
      @aspiringenggs1 5 ปีที่แล้ว +1

      Question is incomplete...Actual Impedance of generator is required for Fault MVA

  • @emekaesenwa387
    @emekaesenwa387 5 ปีที่แล้ว

    The contribution of the electrical motors to the fault current wasn't captured. It will supply fault current to the bus which it is connected to during a fault

    • @emilsify
      @emilsify 4 ปีที่แล้ว

      you are correct during the fault there are some contribution from the motor this method seems shortcut.

  • @haithamahmed8747
    @haithamahmed8747 4 ปีที่แล้ว

    good video but where is the motors contribution, they will raise the fault level !!!

  • @iswarmahanta6905
    @iswarmahanta6905 5 ปีที่แล้ว +2

    What is the value of 1.05

    • @wirotebua6971
      @wirotebua6971 5 ปีที่แล้ว +2

      As I guess, the prefault voltage is 105% of norminal voltage thus the factor 1.05 is used?

    • @ratssaesquareallaboutelect5919
      @ratssaesquareallaboutelect5919  3 ปีที่แล้ว

      thank you for the question, Answer to 1.05 question is : 1.05 is a voltage factor required in the calculation to
      account for Voltage variations in the system,if we consider voltage variation of +-6% in voltage , we have to use factor of 1.05 in the formula as per standard IEC 60909.

  • @deepakgrg1408
    @deepakgrg1408 4 ปีที่แล้ว

    ok

  • @keshabchandratripathy7300
    @keshabchandratripathy7300 3 ปีที่แล้ว

    Please find explain the formula used

  • @patricksalvacion8975
    @patricksalvacion8975 5 ปีที่แล้ว

    How to obtain the number of runs?

    • @Feitan0123
      @Feitan0123 4 ปีที่แล้ว

      it is the number of wire per phase.

  • @patelkaushik2996
    @patelkaushik2996 3 ปีที่แล้ว

    Medam send video for HT 11KV TO LT 415 V relay

  • @anilkumarmehta1923
    @anilkumarmehta1923 ปีที่แล้ว

    But you have not considered the incoming grid and generator connected which these will contribute

  • @Nour-ds3ib
    @Nour-ds3ib 3 ปีที่แล้ว +1

    Any one please can tell me what's meant by number of Runs????

  • @dsmahatpure8199
    @dsmahatpure8199 4 ปีที่แล้ว +1

    Mam in farmula 1.05 and 10 is coming from where?

    • @ratssaesquareallaboutelect5919
      @ratssaesquareallaboutelect5919  3 ปีที่แล้ว

      thank you for the question, Answer to 1.05 question is : 1.05 is a voltage factor required in the calculation to
      account for Voltage variations in the system,if we consider voltage variation of +-6% in voltage , we have to use factor of 1.05 in the formula as per standard IEC 60909.

  • @patelkaushik2996
    @patelkaushik2996 3 ปีที่แล้ว

    Nice pic medam

  • @DJLMGT
    @DJLMGT 3 ปีที่แล้ว +1

    what means 7 runs?

  • @pranayprakash3877
    @pranayprakash3877 4 ปีที่แล้ว +1

    No of run is 7 you said, where this come from

    • @ratssaesquareallaboutelect5919
      @ratssaesquareallaboutelect5919  4 ปีที่แล้ว

      for example, 7 parallel paths are assumed here.

    • @vinnnyvinvin
      @vinnnyvinvin 3 ปีที่แล้ว

      @@ratssaesquareallaboutelect5919 Hi, does this mean parallel paths for 3 cores (3 phases) and 1 core for neutral? any earth connection?

  • @shuvanilmukherjee1595
    @shuvanilmukherjee1595 ปีที่แล้ว

    MAM WHY CALCULATING Z YOU ARE USING MULTIPLY BY 10

  • @quirinoguillepajr3979
    @quirinoguillepajr3979 5 ปีที่แล้ว +1

    Not comprehensive it does not consider the available fault MVA at the utility and motors subtransient reactance

    • @ratssaesquareallaboutelect5919
      @ratssaesquareallaboutelect5919  5 ปีที่แล้ว +2

      This type of calculation is used for deciding the Short circuit Breaking Capacity of MCCB to be used. Other factor as mentioned can be also calculated.
      Thanks for writing

    • @shamirdebnath7407
      @shamirdebnath7407 3 ปีที่แล้ว

      @@ratssaesquareallaboutelect5919 Could you please explain how to select the required breaking capacity of individual motors?

  • @AbdulRahman-pm1nd
    @AbdulRahman-pm1nd 2 ปีที่แล้ว

    What is value of 1.05

    • @ratssaesquareallaboutelect5919
      @ratssaesquareallaboutelect5919  ปีที่แล้ว

      As per standard IEC 60909 - 2001 , We have to consider the voltage factor of 1.05 in LV fault calculation (100V to 1000V).

  • @atmsc4nd4l
    @atmsc4nd4l 3 ปีที่แล้ว +1

    why do you have 1.05? does that mean you have increased the voltage to 5%?

  • @IbrahimMA-EGY-suez
    @IbrahimMA-EGY-suez ปีที่แล้ว

    but you ignore motor reactance how could you !!!

  • @anwarhussainansari13
    @anwarhussainansari13 3 ปีที่แล้ว

    Transformer impedance already given %6=.06 ohm so why u are re calculate ?

    • @staceyksmith1095
      @staceyksmith1095 3 ปีที่แล้ว

      The transformer impedance given in percentage is used when you convert all impedances to Per Unit. She avoided the per unit conversions by calculating the Z impedance first

  • @kachhuap3ycentre505
    @kachhuap3ycentre505 3 ปีที่แล้ว

    Charnam sarnam gachammi Paramji papar paramyog p3y hamare sanatan dharm ki Ati prachin Vidya hai ye Vidya param Pawan Paramji ki hai janane ke liye reply Kare charnam sarnam gachammi.

  • @keshabchandratripathy7300
    @keshabchandratripathy7300 3 ปีที่แล้ว

    I feel for Z Tago in formula given instead of 10 we will write 1000.please clarify

  • @senthivelgopal567
    @senthivelgopal567 4 หลายเดือนก่อน

    why here u r multiplying Z% by 10 , could please explain, if anyone else also most welcome

  • @muhammadbinali6223
    @muhammadbinali6223 ปีที่แล้ว

    too complicated , instead do this, first calculate the sec current of transformer, which is Isec= rated KVA/sec voltage, incase its 3 phase (1.73 into voltage) , u will get Isec of transformer, now next step to calculate short circuit current by using the formulae , isc= Isec*100/%imp of transfomer , which will give u the short circuit curent on busbar by transformer

  • @user-hy6ju4gz6c
    @user-hy6ju4gz6c 5 ปีที่แล้ว

    how do motors affect short-circuit currents?

    • @berniesayson6612
      @berniesayson6612 4 ปีที่แล้ว +1

      for solving of short circuit current of electrical system all connected equipment's and load must be consider, in your calculation load is not considered.

  • @lemmirorissa5217
    @lemmirorissa5217 2 ปีที่แล้ว

    Could you please explain number "10" in the formula for z(transformer). Where did it come from.