Sir, I've DIGSI software to Access siprotec series such relay. Would you please tell me - what interface port is used to establish connection with laptop for build up access, please.
To connect 7sj600 series you will have to connect RS485 converter +ve to relay terminal 29 and -ve to terminal 28. Then using Siprotec 3 option in digsi, u'll able to connect. Make sure interface selection should be digsi v3 in relay. For Siprotec 4 communication related information please go through my 7sj8081 relay video 👇 th-cam.com/video/x9tH6mtwBBE/w-d-xo.htmlsi=bZywDpoa7X_lg4ZZ
Give 2 times or multiple times current of thermal set value, if u need to match timing, set time constant (tau) value to 1min & inject current 2 times of set value, your tripping time will be around 17.26 sec.👍
Mashaallah please very good and informative
Nice video pratik...
Thanks for watching 👍😊
Sir, I've DIGSI software to Access siprotec series such relay. Would you please tell me - what interface port is used to establish connection with laptop for build up access, please.
To connect 7sj600 series you will have to connect RS485 converter +ve to relay terminal 29 and -ve to terminal 28. Then using Siprotec 3 option in digsi, u'll able to connect. Make sure interface selection should be digsi v3 in relay. For Siprotec 4 communication related information please go through my 7sj8081 relay video 👇
th-cam.com/video/x9tH6mtwBBE/w-d-xo.htmlsi=bZywDpoa7X_lg4ZZ
Sir ji fault kaise dekhte hai
Haw to adjust relay display cotrast please explain.
7sj6001 relay not having any screen light. So, no any contrast adjustment option.
How to test thermal overload protection in this relay
Give 2 times or multiple times current of thermal set value, if u need to match timing, set time constant (tau) value to 1min & inject current 2 times of set value, your tripping time will be around 17.26 sec.👍
How Can we read kw and kwh ,?
In this version only current percentage value & amps value can be seen.