- 8
- 46 798
Pratik bhatt
เข้าร่วมเมื่อ 27 ก.พ. 2015
Electrical Protection Guruji ⚡⚡⚡
CT testing with Omicron CT Analyser with connections & Troubleshooting
CT testing with Omicron CT Analyser kit along with an explanation on how to do connections to CT, parameters settings of each core (Metering & Protection) & both core testing, CT ratio-polarity testing, CT winding resistance testing, CT ratio error results, CT knee point testing & value check of leakage current (magnetisation current), Troubleshooting if not getting results,Etc.
#CTtesting #currenttransformer #omicron #ctanalyser #ratiotest #polaritytest #error #kneepoint #magnetisationcurrent #leakagecurrent #connections #troubleshooting #testing #electrical
Contact us: pratikbhatt95@gmail.com
copyright Disclaimer.
Disclaimer- Some contents are used for educational purpose under fair use. Copyright Disclaimer Under Section 107 of the Copyright Act 1976, allowance is made for 'fair use" for purposes such as criticism, comment, news reporting, teaching, scholarship, and research. Fair use is a use permitted by copyright statute that might otherwise be infringing. Non-profit, educational or personal use tips the balance in favor of fair use. All credit for copyright materiel used in video goes to respected owner.
#CTtesting #currenttransformer #omicron #ctanalyser #ratiotest #polaritytest #error #kneepoint #magnetisationcurrent #leakagecurrent #connections #troubleshooting #testing #electrical
Contact us: pratikbhatt95@gmail.com
copyright Disclaimer.
Disclaimer- Some contents are used for educational purpose under fair use. Copyright Disclaimer Under Section 107 of the Copyright Act 1976, allowance is made for 'fair use" for purposes such as criticism, comment, news reporting, teaching, scholarship, and research. Fair use is a use permitted by copyright statute that might otherwise be infringing. Non-profit, educational or personal use tips the balance in favor of fair use. All credit for copyright materiel used in video goes to respected owner.
มุมมอง: 7 148
วีดีโอ
Schneider micom P143 relay Communication,setting changes,alarm/fault/led reset & import/export by PC
มุมมอง 7Kปีที่แล้ว
Schneider Easergy Micom P143 relay communication to Easergy studio software, relay Data model/driver download, relay setting backup/extract, send/receive setting & PSL logic file from/to relay, relay password, CT ratio & other parameter setting changes by software, relay logic online/real time monitoring, live status of BI(Binary input), BO(Binary Output), Led, reset alarm/ fault/led manually &...
SEL-710 Motor protection relay Navigation, parameter settings, alarm/ fault/led reset, password
มุมมอง 5Kปีที่แล้ว
Schweitzer Engineering Laboratories/ SEL-710 motor protection relay, connection understanding, Password Enter, Navigation, Manually change parameter settings(CT-PT ratio setting), relay basic configuration, Feeder name setting, how to view Fault record/events, alarm/ fault/led reset, Relay reboot; etc. #SEL #motor protection #relay #SEL password #relay configuration #Schweitzer Enginnering Labo...
Siemens 7SJ6001 relay Navigation, Manual programming, relay testing, manually parameter changes,Etc.
มุมมอง 6Kปีที่แล้ว
Siemens 7SJ6001 relay Navigation, Basic parameter settings CT ratio setting, Overcurrent & Earth fault setting/relay basic configuration), basic relay testing, View Fault record its time, alarm/ fault/led reset, Manually change CT ratio, manually change settings/parameter, manually changes/configure/programming BI, BO & LED, Etc. #Siemens #relay #relay testing #relay configuration #7SJ600 #CT r...
Siemens compact 7SJ8081 relay Navigation, parameter settings,relay testing, alarm/ fault/led reset
มุมมอง 10Kปีที่แล้ว
Siemens 7SJ80 Siprotec compact relay Navigation, Basic parameter settings(CT-PT ratio setting, Overcurrent & Earth fault setting/relay basic configuration), basic relay testing, View Fault record its time, alarm/ fault/led reset, communication with digsi, CT ratio change, manually change setting/parameter, manually check BI, BO & LED, Etc. Note: For almost all Siprotec compact series relay, all...
Schneider Micom P141 relay Navigation, parameter settings, relay testing, alarm/ fault/led reset
มุมมอง 9K2 ปีที่แล้ว
Schneider Easergy Micom P141 relay Navigation, parameter settings(CT-PT ratio setting, Overcurrent & Earth fault setting/relay basic configuration), relay testing, how to view Fault record & its time, alarm/ fault/led reset.,etc. #p141, #relay #relay testing #relay configuration #schneider
VTT11 Definite Time Relay Testing
มุมมอง 1.5K4 ปีที่แล้ว
VTT11 Definite Time Relay Testing #Relay Testing, #VTT #Electromechanical Relay
Heat shrinkable 11 KV HT cable end termination jointing kit of 3M
มุมมอง 1.5K5 ปีที่แล้ว
HT cable end termination kit jointing demonstration
Excellent Sir 🎉
Very nice
❤❤❤❤❤ zabardast
Kya hum Schneider p143 ko s1agile main kholsaktr hain?
@@bikramkumardash7414 No
Very well explained. Refreshed my memory quite a bit. Thankyou . God bless. Please keep up the Good work ❤
Sir ji fault kaise dekhte hai
ello, I'm very sorry to disturb you on the weekend. I have a question that has been bothering me: after changing the settings of the protection relay, do I still need to conduct a test? For example, the overcurrent protection has been changed from 5A to 6A. Do you still need to test the relay protection? Thank you.
@@风景这边独好-g4k No. If you change some logic and you want to ensure functionality then only require.
@@pratikbhatt95 Thank you very much. So, how can I ensure that the modified value is correct?
@@风景这边独好-g4k U're having relay & u can navigate right?
@@pratikbhatt95 I do not understand
We need MICOM E1 Battery Box
Please can you make a vedio about distance relay test by doble software?please
please I need to explain for doble tester software specially distance relay test by doble tester software
Sir G what is the reason why this show phase to phase current ?I in normal condition current is zero
Once again think you Sir ❤
Hi Pratik…How much time will it take to complete the test including the preparation for the tests on a single core CT for all theee phases
45 seconds
For one c. T. only S1 and S2, how to connect?
Good information for study, thanks
No idea what you said but the wiring connection helped me verify that what I was doing was correct. Thank you, please always show how you wire connections to the test set🙏🏼
what is the function of poledead in undervoltage on P142
If Voltage-current goes below set threshold value or CB open status through logic then it will be pole dead condition.
Sir, is input DC IN 1 and 2 is 24 volt? Best regards
No, this model is for 60-250V DC & 115-230V AC. For 24V you will have to choose different MFLB number
@@pratikbhatt95 Thanks a lot
Please to explain in English.
Please send the link to download drivers
How can I transfer old ALSTOM make micom 143 settings file to new Schneider make 143 relay
Please provide the link for downloading this easergy studio software
www.se.com/in/en/download/document/Easergy_Studio_Installer/
Thank you
Great job
Thank
7sk8012 model
Sir, I've DIGSI software to Access siprotec series such relay. Would you please tell me - what interface port is used to establish connection with laptop for build up access, please.
To connect 7sj600 series you will have to connect RS485 converter +ve to relay terminal 29 and -ve to terminal 28. Then using Siprotec 3 option in digsi, u'll able to connect. Make sure interface selection should be digsi v3 in relay. For Siprotec 4 communication related information please go through my 7sj8081 relay video 👇 th-cam.com/video/x9tH6mtwBBE/w-d-xo.htmlsi=bZywDpoa7X_lg4ZZ
Sir, PSL kaise banate hai ? Video banake share kiji ye
Sir, It'll be available soon.👍
Very well thanks brother 😊
Very nice information
I have to set the first earth chain threshold to 2A with TO 100/1 but the minimum value is 0.05 of the nominal value. come what should I do?
Sir, how to copy relay settings to spare relay through Digsi software
I got your mail, i replied over there...👍
Nice explanation sir
Sir,I have a problem. how can i leave monitor mode? Which is ''SIEMENS intern'' password?
First try to initialise proper programme, or default programme with basic settings. If not working then contact me on pratikbhatt95@gmail.com
Sir, is there ny Institute where i get training of such equipment like ct analyzer kit, testrano 600,cpc 100? Plz help
Actually fact is different, once you understand testing concepts these kits are so easy to use, sometimes there will be some queries which can be easily get clear from manual. Ofcourse there are some courses available in market but looking at cost & outcome, i suggesting u to do not waste money in it. Do understand concepts, read manual & learn yourself. Still you need to learn fast by someone, i am providing personal coaching with nominal cost at online & offline both platforms.
Hi how to check relay has 1 A or 5A CT input? Waiting for reply.. Thanks in advance
Salam Can I ask you for information? I have a problem with micom p142 when I inject the current I > the circuit breaker reacts and opens but when I inject the fault current the circuit breaker is in the open position it closes greetings
Check PSL if there any closing logic mistake, if necessary check real time monitoring, so u can check live status changes. If nothing there from relay side then you need to check external wiring.
Think you very much
can I send you PSL to check
Why it is required to short 2s1- 2s2.? If three core is there, then while testing 1s1-1s2 , is it required to short 2s1-2s2 and 3s1-3s2
Omicron CT Analyser works on voltage injection method, so it can be done without shorting as well, i've also tried same, and it works fine. However it is standard practice for primary injection that CT secondary cannot kept open as it will create burden on CT, also mentioned in omicron CT Analyser manual to short other cores.
@@pratikbhatt95 ok Thank u
What digsi version are you using? Everytime i tried to connect it to digsi v4.92 it says cannot connecy
You should have device drivers for same model & same or higher P-set version, which you can free download from siemens website.
Sir how to communicate this relay via ethernet port
There is no ethernet port available in these type of compact series, you can communicate with printer cable only...
how i can download new virgin 4.79 to digsi 4 because the devise dont conaction ??
If you are having no driver installed then you have to download from siemens website. It's available free. It will just ask you to register then you will able to download.👍
Very nice sir... Psl kete banate hey... Ek panels drawing dekh k ..plz make a video on that
Soon, It will be available...
Great... Plz make a video on relay configuration
How Can we read kw and kwh ,?
In this version only current percentage value & amps value can be seen.
Hi
Sir, can you provide software to me.
Software is available free on internet but you will have to get the key from somewhere...
kindly 🙏 make vdo of siemens differential relay , oc relay communication and logic file
It will be available soon...👍
Haw to adjust relay display cotrast please explain.
7sj6001 relay not having any screen light. So, no any contrast adjustment option.
Thanks sir for relay training video..we expect more relay videos from u..plz
Make video on seimens and micom relay
You already have commented on micom relay video. For siemens relay visit th-cam.com/video/x9tH6mtwBBE/w-d-xo.html
Mashaallah please very good and informative