HT BREAKER CHANGE OVER PROCEDURE - SIEMENS BREAKER

แชร์
ฝัง
  • เผยแพร่เมื่อ 21 พ.ย. 2024

ความคิดเห็น • 4

  • @Technicalcobra
    @Technicalcobra 20 วันที่ผ่านมา +1

    Independent mode ka kya kaam h?

    • @bishantkumar12589
      @bishantkumar12589  18 วันที่ผ่านมา +1

      There are 3 modes
      1.independent
      2.Manual
      3.Auto
      Independent mode is used if the bus coupler is off in the circuit.that means if 2 incomer and one bus coupler is there we can make on any two breakers manually..third one breaker is not possible to make on...
      If we are not operating 2 incomers parallel then independent switch mode is used
      Finally we can say that independent operation of perticular breaker and transformer
      2nd one is Manual means, at one stage all the three breakers are on through synchronisation .
      Third one auto is if the one bus voltage is dropped below the rated the other one is automatically changeovers

  • @Abhi_asthetics
    @Abhi_asthetics 2 ปีที่แล้ว

    Sir ye kis plant ka system h