Derating of Conductors Explained

แชร์
ฝัง
  • เผยแพร่เมื่อ 1 ม.ค. 2025

ความคิดเห็น • 128

  • @danieljudkins7974
    @danieljudkins7974 11 หลายเดือนก่อน +4

    Craig, I have been watching your videos since I started my apprenticeship. I take my JW exam next week and am brushing up on some things by watching your videos. Thank you so much for posting your videos.

  • @meilissawang2807
    @meilissawang2807 ปีที่แล้ว +2

    You’re a excellent teacher body your explanations your tone of voice everything I feel very easy to catch everything you’re teaching

  • @izdagrimeyone
    @izdagrimeyone ปีที่แล้ว +3

    I literally played this video, for the past 3 hours studying all day. Using the 2017 edition.Table 310.15(B)(16) yet the top reads 310.60 on pg 70-150. That was messing me up. Now that I tabbed my book that was half the battle. Turn the page and find #of conductors This video is so perfect for load calculations. Cut the search down by a lot. Keep up the good work

  • @tylerbiggs9474
    @tylerbiggs9474 6 ปีที่แล้ว +38

    you seriously just made my life so much easier. i have been struggling in school but watching this video made everything so much better and i got an A on my test. please dont stop making videos

  • @TheTantanski
    @TheTantanski 4 ปีที่แล้ว +9

    My first time managing a small project, this helped me clear things up.!!! Thank you.!!

  • @concepcionmariera2162
    @concepcionmariera2162 ปีที่แล้ว +1

    /// FIRE !!!! QUICK AND SIMPLE. I LOVE TO LEARN THIS WAY. THANK YOU.

  • @benfullerton7931
    @benfullerton7931 ปีที่แล้ว +1

    As a brand new JW, this is awesome, thank you so much.

  • @BrockBenkula
    @BrockBenkula 3 หลายเดือนก่อน +1

    You taught me a lot more than school did about to take journeyman test so wanted a better understanding of de rating and you helped thank you

  • @CGV5280
    @CGV5280 4 ปีที่แล้ว +3

    I'm in my 1st yrs. 1st semester 6months in the trade. Your a great instructor. Thank you for the video's.

  • @peterponcedeleon3368
    @peterponcedeleon3368 4 ปีที่แล้ว +1

    I really appreciated the tutorial! Please make more. I have been a tradesman my entire adult life. Turned Financial Advisor, now working in the content monetization space. I loved it!!!!

  • @danieldyer9177
    @danieldyer9177 2 ปีที่แล้ว +1

    I've been busting my brain and you made this so easy to understand take you very much

  • @jessegravesgraves4749
    @jessegravesgraves4749 3 ปีที่แล้ว

    Believe it or not , I actually learned the most from you. ! As far as TH-cam channels are concerned.

  • @jarrydee2799
    @jarrydee2799 5 ปีที่แล้ว +2

    Thank you for this. I am taking my J-man test end of Nov. and I just KNOW this stuff is going to be on the test. Thank you for making it easy!

  • @big40glock84
    @big40glock84 6 หลายเดือนก่อน +1

    Thank you for making this video brother

  • @lanceuppercut5939
    @lanceuppercut5939 11 หลายเดือนก่อน +1

    Awesome video, very easy to understand thank you.

  • @Artikgrau325is
    @Artikgrau325is 5 ปีที่แล้ว

    Very well explained, derating always was somewhat a mystery for me, and I've only pulled whatever size I was told to pull. Now I have more knowledge to do a quality job in the field. Thank you.

  • @joseovelasquez6264
    @joseovelasquez6264 5 ปีที่แล้ว +2

    Craig great video this is making alot of sence now
    Am taking a electrical system code and theory class at my school and we are going through de rating conductors and also Over current protection devices but this video helps alot more thanks for sharing with us about the NEC

  • @TuberKMT
    @TuberKMT ปีที่แล้ว +1

    Super helpful and simple to follow. Thank you! Subscribing!

  • @davi-un7ku
    @davi-un7ku 3 ปีที่แล้ว

    Thank you sir extremely good explanation, none of my teachers explainations where clear but you did it with ease! The apprentice thanks you

  • @mark_torresx3
    @mark_torresx3 9 หลายเดือนก่อน +1

    Nice thank you so much is very useful. Keep the videos coming I’m subscribed.

  • @RicardoDelgado-zr4ki
    @RicardoDelgado-zr4ki 10 หลายเดือนก่อน +1

    Another great video sir, thanks for the breakdown, my professor wouldn’t have the patience

  • @KenKaneki-xh7by
    @KenKaneki-xh7by 5 ปีที่แล้ว

    This helped me out far more than class did. Thank you so much.

  • @jarrydee2799
    @jarrydee2799 5 ปีที่แล้ว +2

    I wish you were my boss!! You seem like a nice guy, with lot's of knowledge

  • @ArelSprite
    @ArelSprite 2 ปีที่แล้ว +1

    Excellent explanation!

  • @juanramirez-mp4uk
    @juanramirez-mp4uk 4 ปีที่แล้ว

    I really liked your video. I'm going through classes and helped me to catch up. Thank you.

  • @brandondenton494
    @brandondenton494 ปีที่แล้ว +2

    Is the neutral/ grounded wire a current carrying conductor?

    • @craigmichaud-electricalins4602
      @craigmichaud-electricalins4602  ปีที่แล้ว +2

      Yes it is! CM

    • @MrWom80
      @MrWom80 4 หลายเดือนก่อน

      Does a feed and return (SL) in one conduit, consider to be ALL current carrying conductors? Example: 12/2 feed switch, 12/2 return back, but route threw a T fitting to another location.One conduit has (2) Blk & (2) white, same circuit. Is this 4 current carrying conductors?​@@craigmichaud-electricalins4602

  • @peterjenkins886
    @peterjenkins886 4 ปีที่แล้ว

    thank u craig quick to the point and very clear with instruction

  • @realspillmidwestboxingtalk2139
    @realspillmidwestboxingtalk2139 ปีที่แล้ว +1

    Great breakdown

  • @EastCoastSparky
    @EastCoastSparky 11 หลายเดือนก่อน +1

    great explanation thanks!

  • @philmiller9376
    @philmiller9376 6 ปีที่แล้ว +4

    Heat is the Enemy. Nice Video

    • @craigmichaud-electricalins4602
      @craigmichaud-electricalins4602  6 ปีที่แล้ว +1

      Thank you for watching!! It is a great thing for people to understand. We don't just pull wire and put up lights. This is why we charge for our knowledge.

  • @paulanthony4089
    @paulanthony4089 4 ปีที่แล้ว

    Great explanation. Your videos help so much with my studies. These books are confusing. Keep it up!

  • @mattc41854
    @mattc41854 5 ปีที่แล้ว

    Hey that was a great video!!! It really made sense of this sweating thing. I never really understood it but your video was really easy to understand. I’m going to check out your other vids. Thanks again

  • @milan512
    @milan512 5 ปีที่แล้ว +1

    Hello , You’re videos are bad ass !! 💯

  • @ready4itall89
    @ready4itall89 6 ปีที่แล้ว

    Just want to give you props. Very well done. Made simple

  • @bernieromero5597
    @bernieromero5597 3 ปีที่แล้ว

    cool video, makes it easier to understand

  • @aaronfidelisrecine
    @aaronfidelisrecine ปีที่แล้ว +1

    OMFGGGGG IT MAKES SENNNNSEEE THANK YOU!

  • @ig3024
    @ig3024 4 ปีที่แล้ว +1

    Idk how to ask this any easier way but does conduit size change the derating factor? For instance 9 c.c.c #12 20amp breaker (70%)maximum without derating Through 3/4 conduit. Does this still stand for 1” or 1 1/4 conduit. Since the conduit is larger less heat? If conduit size doesn’t matter then how could this formula stand for 9 c.c.c #12-20amp breaker through a 4” conduit? If I pulled 10 wires would I really have to Derate?

  • @guadarramarichard
    @guadarramarichard 3 ปีที่แล้ว +1

    so if u up the wire, the breaker size stay the same?

  • @MikeJones-nm8qt
    @MikeJones-nm8qt 5 ปีที่แล้ว +1

    Hi Craig!!! Love your videos!!!

  • @whatsreal7365
    @whatsreal7365 ปีที่แล้ว +1

    Appreciate the info brother!

  • @gengizaghdasi
    @gengizaghdasi 6 ปีที่แล้ว +2

    Thank you this was easy to understand

  • @moeezwarraich132
    @moeezwarraich132 หลายเดือนก่อน

    Great video 👏👏
    But can you tell me how to calculate the new and old cable remaining Life ?

  • @nicksince91
    @nicksince91 4 ปีที่แล้ว +2

    My dude craig coming with straight knowledge. Much appreciated.

  • @8yerbrain
    @8yerbrain 4 ปีที่แล้ว

    Thank you for your excellent explanation.

  • @jorgeceballos8308
    @jorgeceballos8308 6 ปีที่แล้ว +2

    What abuot with two diferent gauge of wire in the same pipe, what's the proces?

    • @mattrob15
      @mattrob15 3 ปีที่แล้ว

      I don't think it matters, but you have to debate each wire accordingly.

  • @jorgeescutia9578
    @jorgeescutia9578 4 หลายเดือนก่อน +1

    Does the 40% wire fill matter if ur de rating instead?

    • @craigmichaud-electricalins4602
      @craigmichaud-electricalins4602  4 หลายเดือนก่อน

      @@jorgeescutia9578 yes it does!! Conduit fill based on 40% is based on area where derating only refers to the safe ampacity of the conductor. CM

  • @dja711
    @dja711 3 ปีที่แล้ว

    Thank you for the video I have a job site situation. I have 9 circuits (general use receptacles) to run in a 1 inch EMT. So 18 current carrying conductors. number 12 thhn. So 50 percent adjustment on 30 amp wire. Is that ok on a 20 amp breaker. Thank you.

  • @JesusCruz-wt2zp
    @JesusCruz-wt2zp 3 ปีที่แล้ว +1

    Would you make a video about when we count neutral as a CCC and when not

  • @levarmenifee3065
    @levarmenifee3065 6 ปีที่แล้ว +1

    Good tutorial learned this in class today

  • @ricardocolbert5493
    @ricardocolbert5493 2 ปีที่แล้ว

    Ok ,I hope that you are experiencing a complete recovery, I will be on alert for your post some time in March thanks for responding, hope to remain in contact w/u be safe.

  • @patrickgreen9486
    @patrickgreen9486 5 ปีที่แล้ว +1

    In your example are you accounting for the neutral conductors in your four wires? And also what if you have three hots in your circute? In that case how would it work with six current caring conductors?

    • @craigmichaud-electricalins4602
      @craigmichaud-electricalins4602  5 ปีที่แล้ว +2

      The nuetral is always counted as a current carrying conductor. So if you have 6 wires and they are current carrying then you calculate them according to the code. Hope that explains it better for you. Thank you for your question. CM

  • @buddhalovechild
    @buddhalovechild 2 ปีที่แล้ว

    Excellent. Thank you.

  • @edwardsmith4353
    @edwardsmith4353 4 ปีที่แล้ว +1

    any chance of updating to 2020 NEC code?

  • @jeanious2009
    @jeanious2009 6 ปีที่แล้ว +2

    After 3 current conductors, does the neutral count as a current carrying conductor?

  • @christianhufton6445
    @christianhufton6445 ปีที่แล้ว

    How do do the same thing with different size conductors

  • @janorve21
    @janorve21 27 วันที่ผ่านมา +1

    Thank you🎉

  • @icevariable9600
    @icevariable9600 ปีที่แล้ว

    So, I'm wondering if it would be cheaper to run one 1" EMT with 10 conductors at 50% ampacity, or two 3/4" with 5 conductors each, at 80% ampacity. Or what the hell, maybe throw up 3 1/2" EMT with 3 conductors each, all at 100% ampacity. Lots to think about. Thanks a lot for this awesome insight into a very perplexing part of my job.

  • @82Ismael
    @82Ismael 5 ปีที่แล้ว +2

    Question a current carrying cunductor also includes a neutral wire? Also thanks for yhe video

    • @craigmichaud-electricalins4602
      @craigmichaud-electricalins4602  5 ปีที่แล้ว

      Thank you for the question!! Yes the neutral wire is considered a Current-carrying conductor. Thank you for watching my video!! CM

    • @86aoshi
      @86aoshi 5 ปีที่แล้ว +1

      @@craigmichaud-electricalins4602
      Is it true that the neutral doesnt count as a current carrying conductor if its a balanced shared neutral?

    • @craigmichaud-electricalins4602
      @craigmichaud-electricalins4602  5 ปีที่แล้ว

      @@86aoshi I have never heard that. In any type of fault or change in the system can throw it out of whack. In the NEC it calls for all current carrying conductors. That is how I have always seen it. If you find anything that is different please email so I can read about the process. Thanks for the question!! CM

    • @86aoshi
      @86aoshi 5 ปีที่แล้ว +1

      @@craigmichaud-electricalins4602
      Check out 310.15(B)(5)

  • @flacoeloco
    @flacoeloco 5 ปีที่แล้ว +1

    Very good explanation, always wondered how to derate, you just made my life easier, don’t stop making your videos👍💯

  • @907sno
    @907sno ปีที่แล้ว

    This might be a dumb question but is that amperage per conductor or total amount in the conduit.

  • @mikegardiner6639
    @mikegardiner6639 3 ปีที่แล้ว +1

    Your awesome... One question when de rating do you include the nuetral? So all my wires if I had to bump them up to the next size would all have to be a number 6 including the nuetral? And one more question. Can you legally go done one size with the nuetral and 2 sizes with a ground? Thanks for your knowledge. You make learning extremely fun.

    • @KLAWNINETY
      @KLAWNINETY 3 ปีที่แล้ว +3

      The neutral is a current carrying conductor, so you have to size it accordingly and include it in your pipe fill and de-rating calculations. You also do not need to de-rate the ground as far as I know since it does not carry current, for example if you are using a #10 de-rated down to 20 amps you can still use a #12 ground, you don't actually have to upsize the ground to a #10 the way you would if the #10 hot was being used for a 30 amp load.

    • @mikegardiner6639
      @mikegardiner6639 3 ปีที่แล้ว

      @@KLAWNINETY thank you makes perfect sense

  • @jamesbuie1686
    @jamesbuie1686 5 ปีที่แล้ว +1

    Where exzAcky would I use this application on a device or a feed or service entry??

    • @craigmichaud-electricalins4602
      @craigmichaud-electricalins4602  5 ปีที่แล้ว

      Thank you for your question. Derating a Conductor is a step in properly sizing the wire. It is the code version so I explain how to do it. Like I said you only use this when you have more that 3 current carrying conductors in a cable or conduit. It is not for devices but in some cases used for service feeder sizes. I hope that this answers your question!! Thanks for watching!! CM

  • @fishmasterdan
    @fishmasterdan 3 ปีที่แล้ว +1

    Thanks for making videos. However I would like to point out derating is based on conductor type. Most our conductors today are 90d not 75d like the video. After your derating has been calculated you then cant exceed your termination ratings . Ie #10 rerated to 50% is 20a which does not exceed the 75d column if your using 75d terminals. In this example you could use 20 #10 at 20a in 1" emt.

  • @clavelarmandojesus4048
    @clavelarmandojesus4048 4 ปีที่แล้ว +1

    You don’t have an idea how values this is for me . Now I have to do my homework on NEC . Thanks

  • @kamilkamal9900
    @kamilkamal9900 3 ปีที่แล้ว

    I have a question please sir.
    When I do temperature correction for the conductor based on the type of the insulations some times we have the same insulation type in 75 column and 90 column so which column should I use when I have the same insulation rating in the two columns?
    Thank you.

    • @918M
      @918M 2 ปีที่แล้ว

      75

  • @oscar27ization
    @oscar27ization 5 ปีที่แล้ว

    Yeh but once you have derated and have your amperage total, what do u do? That’s the breaker size amperage that you will use for each circuit?

    • @truthbebold4009
      @truthbebold4009 4 ปีที่แล้ว

      Example: if you need to wire a 50 amp circuit in this scenario, you would have to adjust your wire size. So instead of #8 THWN you could select #6 which (after adjustment for 80%) has an ampacity of 52 amps.

    • @oscar27ization
      @oscar27ization 3 ปีที่แล้ว

      @@truthbebold4009 but isn’t 50 amps x 80% = 40? At a 75 degree would be a number 10?

  • @jorgehuizarsr1630
    @jorgehuizarsr1630 3 ปีที่แล้ว

    hell yea made sense thank u sooooo much

  • @educationpower1823
    @educationpower1823 3 ปีที่แล้ว

    Interesting that you call it debating
    The code got rid of that term and identify it as adjustment or correction. Just curious..

  • @CommunityGuidelinez
    @CommunityGuidelinez 2 ปีที่แล้ว

    Over the years I've noticed a lot of guys ask if a neutral is considered a current carrying conductor, so I've adjusted my vocabulary from "hot/neutral/ground" over to "Ungrounded Conductor/Grounded Conductor/Grounding Conductor". I also make sure I spend plenty of time with them on Article 💯. 😉

    • @1brrooke1
      @1brrooke1 ปีที่แล้ว

      Grounded and grounding conductor are two separate things. Don’t know if you caught that.

    • @CommunityGuidelinez
      @CommunityGuidelinez ปีที่แล้ว +1

      @@1brrooke1 Thats right. As I said, Ungrounded Conductor(hot), Grounded Conductor(Neutral), and Grounding Conductor(Ground). The terminology of Grounding Conductor is misleading because the ground is not considered a current carrying conductor, it's only there to provide a path for available fault current. 👍

  • @miguellopez6328
    @miguellopez6328 6 ปีที่แล้ว +1

    Thank you very much !!

  • @borinreyes
    @borinreyes 4 ปีที่แล้ว

    I'm having a little bit of issues understanding how can i apply this when it comes to conduit size ?

  • @phantomjoe86
    @phantomjoe86 2 ปีที่แล้ว

    Thank you so much

  • @rubygarcia516
    @rubygarcia516 3 ปีที่แล้ว +2

    NEC 2021
    TABLE 310.16 & 310.15 (c) (1)

  • @bigripdeniro1952
    @bigripdeniro1952 4 ปีที่แล้ว +1

    why u use 75d column and not 90dc

    • @douglassanchez5604
      @douglassanchez5604 4 ปีที่แล้ว +1

      Big Rip Deniro I always use the 90dc I have no idea why he took the 75dc

  • @anthonyshedd9656
    @anthonyshedd9656 6 ปีที่แล้ว

    Isnt THWN rated at 70 amps for an 8 size copper wire?

    • @zionlion47
      @zionlion47 6 ปีที่แล้ว

      #8 copper thwn is rated for 50 amps. Nec code: table 310.15(B)(16)

    • @craigmichaud-electricalins4602
      @craigmichaud-electricalins4602  6 ปีที่แล้ว

      No 70 amps is in the 90 degree column. You only use it when you dont know the exact wire type. Thank you for the question!! CM

  • @ricardocolbert5493
    @ricardocolbert5493 2 ปีที่แล้ว +1

    Craig I’m subscribed to your but I never receive any message when you post new videos. I study your post. You teaching method simplifies many areas of the electrical code, that are often difficult to grasp. thanks in advance Rick

    • @craigmichaud-electricalins4602
      @craigmichaud-electricalins4602  2 ปีที่แล้ว +1

      I will be starting back up in March!! Had some health and family issues! Thank you for subscribing!! CM

  • @vasiqshair
    @vasiqshair 5 ปีที่แล้ว

    Excellent!

  • @djadrian2006
    @djadrian2006 3 ปีที่แล้ว

    Ok im confused on how this ties in to conduit size

  • @zakirullahzakir6569
    @zakirullahzakir6569 5 ปีที่แล้ว

    Sir, for derating you have to go to 90degree column not 75degree

  • @oscar27ization
    @oscar27ization 2 ปีที่แล้ว

    Why they say you can use ANNEX without derating??

  • @mstrlucky652
    @mstrlucky652 4 ปีที่แล้ว

    you're supposed to use the 90-degree column when applying adjustment of correction

  • @catonfarm9757
    @catonfarm9757 2 ปีที่แล้ว

    Is there any time that you would count the neutral as current carrying conductor?

    • @CommunityGuidelinez
      @CommunityGuidelinez 2 ปีที่แล้ว

      Thats a perfect example of why I don't teach my guys to call it a neutral. The technical term is "Grounded Conductor", and that should answer your question sir.

  • @kevinmccorkle7476
    @kevinmccorkle7476 3 ปีที่แล้ว

    Great info. Please don't stand in front of your board, makes it a bit tougher.

  • @sethrambo2234
    @sethrambo2234 5 ปีที่แล้ว

    Thank you

  • @grassrunner7983
    @grassrunner7983 ปีที่แล้ว

    Nice

  • @waylontabor4725
    @waylontabor4725 4 ปีที่แล้ว

    Thanks

  • @christopherestevez6375
    @christopherestevez6375 3 ปีที่แล้ว

    Plesse show charts

  • @Testing329
    @Testing329 2 ปีที่แล้ว

    Viva Christo Rey

  • @hhtetris3
    @hhtetris3 4 ปีที่แล้ว

    More simplified version

  • @EricJames-jn4dd
    @EricJames-jn4dd 2 ปีที่แล้ว +1

    Isn’t thwn I’m the 90 degree column

  • @gregjameston3210
    @gregjameston3210 4 ปีที่แล้ว

    Not efficient. The code keeps it safe.

  • @PeymanSultan-wn6iw
    @PeymanSultan-wn6iw ปีที่แล้ว +1

    Thanks