What's the Difference Between All These Wire Types?!?!

แชร์
ฝัง
  • เผยแพร่เมื่อ 26 ก.ย. 2024

ความคิดเห็น • 306

  • @turrubiartes21ify
    @turrubiartes21ify 2 ปีที่แล้ว +106

    I would love to share the following information:
    No H - 60 Celsius insulation rating
    H - 75 Celsius insulation rating
    HH - 90 degree Celsius permitted in dry or damp locations
    -2 - 90 degree Celsius permitted in wet or dry locations
    N - Nylon outer cover
    T - thermoplastic insulation
    U- underground
    W- permitted in wet locations

    • @URBANENGINEER
      @URBANENGINEER 2 ปีที่แล้ว +14

      X - Thermoset insulation.

    • @carultch
      @carultch 6 หลายเดือนก่อน +3

      @@URBANENGINEER X means cross-linked polyethylene.

  • @DominickRuocco
    @DominickRuocco 2 ปีที่แล้ว +106

    This channel easily deserves 1 million subscribers. I have been in the electrical field for 15+ years but I still learn something new after watching one of Dustin's videos.

    • @ElectricianU
      @ElectricianU  2 ปีที่แล้ว +16

      Thank you my dude we’ll get there ⚡️⚡️💪

    • @meganw6007
      @meganw6007 2 ปีที่แล้ว +1

      I just looked up... 432,000 currently, as of 4 August 2022. Almost halfway there!

    • @mikeburrello4396
      @mikeburrello4396 ปีที่แล้ว +1

      As a veteran who got discharged during the height of c19 I was offered NO type of technical training schools because they all shut down.
      This channel has given me so much hope that there's a career I can delve into without needing to pay for a formal education.
      Thanks for everything you put into this channel man, really 🙏

    • @Tom-og7fi
      @Tom-og7fi 6 หลายเดือนก่อน

      ​​@@mikeburrello4396if you want to learn the trade to a very very in depth study of electricity and most everything about the entire trade including why electricity functions the way that it does right down to how to produce electricity then I would strongly suggest a real union apprenticeship. As far as no programs available during Covid I have to say the union apprenticeships did not stop taking in apprentices.

  • @antoniomorales261
    @antoniomorales261 2 ปีที่แล้ว +28

    I’m a apprentice electrician just finally got my hours needed to go for journeyman’s. Your channel has been so helpful on my journey so far really can’t see myself doing anything else love being a electrician

    • @adrianmendez98
      @adrianmendez98 7 หลายเดือนก่อน +1

      Did you ever get your license?

  • @tightirl
    @tightirl 2 ปีที่แล้ว +210

    a "most common residential code violations" type video would be neat.

    • @Ezzell_
      @Ezzell_ 2 ปีที่แล้ว +20

      top 25 violations the inspectors find

    • @jacewhite8540
      @jacewhite8540 2 ปีที่แล้ว +4

      @@Ezzell_ important distinction

    • @Blahblahblah8016
      @Blahblahblah8016 2 ปีที่แล้ว +3

      Agreed. I do new resi construction, so I would prob know most of them but would still love to see that video

    • @tightirl
      @tightirl 2 ปีที่แล้ว +5

      @@Ezzell_ ya i like this better, actually.

    • @BudaMac
      @BudaMac 2 ปีที่แล้ว

      Agreed!!!!

  • @normILL
    @normILL 2 ปีที่แล้ว +30

    For context, almost all "THHN" on the shelf is going to be cross listed as THWN as well so you can use it in PVC which is considered a wet location. Also, almost everyone I know uses XHHW for overhead services where the conductors are exposed to rain/snow.

    • @arcadiaoutlaw
      @arcadiaoutlaw ปีที่แล้ว

      This is really good to know, Thank you !

  • @InphazeC8
    @InphazeC8 2 ปีที่แล้ว +11

    You don’t know how many times I’ve seen so many contractors or even guys who been doing this for years who don’t use the right type of insulation for the right applications. Love this video!

    • @IceBergGeo
      @IceBergGeo 2 ปีที่แล้ว +3

      If you're dealing with building wire (single conductor wires) almost all them are multi-purpose, meaning they have many different ratings to each wire. If you look at a THHN listed wire, it'll also be rated THWN, THW-2, MTW, T9O, etc. Good for use both in USA and Canada. (Which is why most wires are rated 600V instead of 480.)

  • @markchidester6239
    @markchidester6239 2 ปีที่แล้ว +17

    Excellent video
    Being a plastics injection molder, this was very interesting.
    Thermosets will not melt again. There is a chemical transition that happens when heat is applied to the material. It can burn, but not melt.
    Good examples of their use is a plastic ashtray and these newer soft cooking utensils. Some electrical boxes and circuit breakers are also a thermoset.

    • @GB-yo8xf
      @GB-yo8xf ปีที่แล้ว +1

      I always remember "stat" means quickly..."set" means just that....Set ( leave and forget)

  • @shawny6997
    @shawny6997 2 ปีที่แล้ว +17

    Thank you so much for explaining these questions. Electrician U is definitely the most interesting and useful channel if you're interested in electrical stuff.

    • @ElectricianU
      @ElectricianU  2 ปีที่แล้ว +1

      Why thank you Shawn Y 👌 glad I saw the comment, keep them coming!

  • @nicholasmoore8424
    @nicholasmoore8424 2 ปีที่แล้ว +14

    Nice work on the code book video, I really like seeing the layout and the zooming capabilities in action. No one else has this (apparently) and it makes a world of difference. Thanks for the commitment to continued improvement of teaching methods, Dustin! We see you bro...

  • @JohnDoe-tb2fl
    @JohnDoe-tb2fl 2 ปีที่แล้ว +3

    Dustin is the man! I’m very appreciative for his information and entertainment. All the electricians I know under 40 all watch his videos.

  • @micahclark1583
    @micahclark1583 2 ปีที่แล้ว +11

    A video interviewing a inspector would be great. Some topics can include common code violations/misconceptions, and quality of work in the trade. Thanks!

    • @ElectricianU
      @ElectricianU  2 ปีที่แล้ว +4

      That’s a great idea

    • @Jeff-xy7fv
      @Jeff-xy7fv 2 ปีที่แล้ว +2

      Absolutely! Even better would be actual body-cam footage of electrical inspectors yelling at homeowners for not doing the work to Code, and making dumb mistakes that clearly indicate that they don't know what they're doing!

  • @pebs1070
    @pebs1070 2 ปีที่แล้ว +3

    No BS I was just googling types of wire yesterday! You the man Dustin!

  • @goodolsparky9386
    @goodolsparky9386 2 ปีที่แล้ว +4

    Your the man Dan!! I’m a licensed electrician in Massachusetts and I have a brand new apprentice that still has not attended school but will be in 6 months or so . I’m not the best at teaching or the technical stuff so I tell him to watch a lot of your videos , this way he may understand a bit better . Your awesome at explaining things even for me who is a licensed journeyman. I hope you extend over to Massachusetts for the continued education part . Love your channel and will continue to support it! Last note … I need to get me a ElectricianU shirt and hat !! Love the logo . Anyways take care and keep up the awesome work 🤙🏻👍🏻.
    - Chris Schwab

  • @morrisstewart1528
    @morrisstewart1528 2 ปีที่แล้ว +4

    I went through hvac school. I wish it was more focused on the electrical end. Currently working at a hardware store and these videos are extremely helpful and entertaining and just the right length.

  • @stevesargent4269
    @stevesargent4269 2 ปีที่แล้ว +5

    Great video! I used to work in the plastics department at an auto plant in the plastics department. Propylene is just another type of plastic. Just different manufacturing processes. Think dash of your car vs insulation on speaker wire. At any rate, keep up the great work you're doing👍

  • @lanceleavitt7472
    @lanceleavitt7472 2 ปีที่แล้ว +1

    Yes, this helps. We always ran THHN for our automatic electric gates but never knew why. -- Thanks ---

  • @jhill.7216
    @jhill.7216 2 ปีที่แล้ว +2

    I appreciate you for bringing this content I’m in hvac but I thank you for this!! 👏🏽

  • @tylerblazejewski3184
    @tylerblazejewski3184 2 ปีที่แล้ว +2

    So happy you got back into making these videos, always stoked when I get the notification 👍

    • @ElectricianU
      @ElectricianU  2 ปีที่แล้ว +1

      Thanks for watching my dude!

  • @josephdestaubin7426
    @josephdestaubin7426 2 ปีที่แล้ว +1

    That was awesome, it was not a question that I knew I needed to ask. So I'm really grateful that someone else asked.

  • @hanksnowden5288
    @hanksnowden5288 2 ปีที่แล้ว

    I was just looking this up over the weekend. The timing couldn't have been better!

  • @bigcountry5520
    @bigcountry5520 2 ปีที่แล้ว +2

    The outer coating of THHN also provides less surface resistance, and allows for an easier pull.

  • @lauramagagnoli7750
    @lauramagagnoli7750 2 ปีที่แล้ว +1

    This chanels helped me so much with figuring out what the hell everything means and just getting a general understanding of everything thanks for spreading ur knowledge

    • @ElectricianU
      @ElectricianU  2 ปีที่แล้ว +1

      No problem my friend, thanks for watching and taking the time to comment!

  • @Tubiggiesmalls
    @Tubiggiesmalls 2 ปีที่แล้ว

    This is the greatest TH-cam channel of all time, undisputed.

  • @dannywitz
    @dannywitz 2 ปีที่แล้ว +3

    It would be great if you covered the assembled cords too! SJ JOOW, PVC and more, you could get less common and cover some of the spiffy wires used in solar also, this is interesting stuff

  • @shifty2492
    @shifty2492 2 ปีที่แล้ว +1

    really appreciate this video, we’re doing correction factor calculations in class right now !

  • @christopherworks400
    @christopherworks400 2 ปีที่แล้ว

    I loved it the one day in class, the teacher brought 20 3ft pieces of wire. Showed the difference in casing and how the casing can look similar but have totally different rating/use.

  • @shanemoore8025
    @shanemoore8025 2 ปีที่แล้ว +4

    Thank you for this information!! But now it leads me to the additional question; how do you calculate what the heat rise will be so you then know which covering to use?

  • @ljprep6250
    @ljprep6250 2 ปีที่แล้ว +1

    So, Dustin, "etc." is the written abbreviation for "et cetera". The little 3 up to the right of the note is superscript (subscript is written below the base height). Electricians are generally brighter than the average public, so I'm surprised you were never taught these common details.
    American public schools have been totally failing our students. This is so sad.
    Your coverage of the NEC table was good, so good vid.

  • @ubersham
    @ubersham 2 ปีที่แล้ว +1

    LOVE THIS! Thank you so much for explaining this in simple terms with code references!

  • @IceBergGeo
    @IceBergGeo 2 ปีที่แล้ว

    Well said. Pretty straight and to the point. All the info that 95% of guys will need to know.

  • @courant37
    @courant37 2 ปีที่แล้ว +1

    Nice presentation. Love the animation with the arrow pointing my attention to where I need to be looking at as he explains.
    Dummy - proof!
    Great content overall!

  • @vince6829
    @vince6829 2 หลายเดือนก่อน

    Thanks for sharing your knowledge

  • @Merescat
    @Merescat 2 ปีที่แล้ว

    The MOST succinct explanation I have ever heard on this topic! Well worth the listen! 😃

  • @raymond3722
    @raymond3722 2 ปีที่แล้ว +1

    Thanks for the explanation well illustrated.

  • @josephnicolas2158
    @josephnicolas2158 ปีที่แล้ว

    This Chanel is truly one of a kind!! 5 Diamond status! Keep up the amazing work and thank you kindly for all involved bringing this info to us.

  • @ronblack7870
    @ronblack7870 2 ปีที่แล้ว +2

    actually aluminum alloy has changed over the years . old aluminum wire is not the same as new. aluminum wire older than 1971 has a different alloy . it is recommended to change it out.

  • @Keepitchristian1
    @Keepitchristian1 2 ปีที่แล้ว +2

    If THHN is cross listed as MTW or THWN or THWN-2 how do you know which temperature rating to reference in 310.4A.
    Also my PDF version of the 2020 NEC Book does even have THHN listed in the 310.4A table.

    • @denverbraughler3948
      @denverbraughler3948 7 วันที่ผ่านมา

      You may use the highest rating that is suitable for the application, e.g., if it’s a wet location, you can’t use the dry rating.

  • @aldenbrooks3931
    @aldenbrooks3931 ปีที่แล้ว

    This is so helpful! Im just getting into the trade and wow this was a super simple and well spoken video!! Thanks!

  • @sparkytas
    @sparkytas 3 หลายเดือนก่อน

    Howdy from an Australian "Sparky" (Aussie slang for electrician - or do US electrians get called "Sparkies" too?).
    Love the videos, thinking of travelling to the US someday and interested on how you do things. All my fellow Australians who have travelled around the US have loved it!
    We never (at least I've never heard of it being used) Aluminium in any conductors in a house, or even inside commercial building. Only in overhead and underground mains belonging to the energy distribution companies. Aluminium isn't against code, its just never used.

  • @whyqu.i.t
    @whyqu.i.t 2 ปีที่แล้ว +1

    Dude, I'm really appreciating these videos. I like to think I'm caught up and then bam there's another extremely relevant and practical application video WITH the details my brain needs to apply said details. Thank you for making an impact with the details by making it interesting and not dry and boring. U da man.... See what I did there....U

    • @ElectricianU
      @ElectricianU  2 ปีที่แล้ว

      Hahaha thanks man I’m glad you get something from all this craziness. We have so much more coming, especially on the Website. Stay tuned 👌

  • @TheSpatulaCity
    @TheSpatulaCity 2 ปีที่แล้ว +1

    Cool. Super Helpful.

  • @nicogalvan4466
    @nicogalvan4466 2 ปีที่แล้ว +2

    Dustin can you do a video on how to navigate through the Code book? I have trouble going through even when I was in school.

  • @Aepek
    @Aepek 2 ปีที่แล้ว

    For next vid, explain to ppl what types of these conductors (& romex) that can be run through conduit outdoors (or underground) & in diff weather conditions etc…. As get so many questions all the time about that, & another question I get: having J-boxes in attics, crawl spaces & the “types of materials they made from” & if need cover plate or not. Last question answer a lot (these like top 3 I get) is: what do we do with wires we cut & are not working (maybe breaker tripped or disconnected), we cut & shove into wall to remove “outlet/switch” that’s in the way BUT are working & can be live, etc….. Never a dull day😊
    Just use Romex (nm-b) outdoors in 1 inch of water when rains inside conduit to a 20a receptacle. Hey, it’s gfci, not TWR rated, but it’s gfci, & is what the contractor ran from my parents 15a outlet (on inside of wall they drilled they & took a traveler to a new outdoor outlet) to a 20a & from the 20a connected a sprinkler controller (if not familiar, sprinkler systems aren’t supposed to be connected to gfci when “hardwired”): & did back stab connections & didn’t even “screw down” hot & common terminals in the side. Hate backstab & wish didn’t make ever, although back connections are great.
    Also, finding THWN not easy to find in my area AT ALL. THHN, easy to find & THWN, gotta work for it😉. Now, I gotta get that romex out of the conduit & redo everything. Oh joy for handymen: which in my state can’t even legally install a ceiling fan, let alone electrical rough in & anything else a remodel includes. Imo, this guy messed up this house as flickering lights, tripped breakers, & so on (installed water heaters & oh boy, that cost $1300 to fix & bring to code).
    Thx Dustin, cheers!

  • @frankdagreat598
    @frankdagreat598 2 ปีที่แล้ว +2

    SHAWN Y THANK YOU FOR THAT QUESTION!!!!!

    • @shawny6997
      @shawny6997 2 ปีที่แล้ว +4

      My pleasure. Surprised to see he actually saw my question and made a video about that. Best and most interesting channel for those who are interested in electric trade.

  • @tsmithdotks
    @tsmithdotks 2 ปีที่แล้ว

    You're always sharing some important knowledge. Thank you.

  • @TheWmiller8
    @TheWmiller8 2 ปีที่แล้ว +1

    Thank for the great explanation. What about high temp wire. In work in facility that has a very hot room? At the top of the 20 foot ceiling can be up to 200 degrees f due to a burner we have the heat molten sulfur up to 1200 degrees f to burn the material into a gas

  • @MagnificentVillain
    @MagnificentVillain ปีที่แล้ว

    Very well explained. Thank you for the information.

  • @nikolausnielsen6412
    @nikolausnielsen6412 2 ปีที่แล้ว

    My favorite channel for furthering my electrical knowledge. It’s also fun to put on because my wife automatically leaves the room . “ Why are you always watching that show?!!” I’m going to go to bed 🤪

  • @trardo890
    @trardo890 2 ปีที่แล้ว

    Awesome video! Been going over this in school and they have a weird way of explaining this... you cleared it right up for me haha! Great video!

  • @alexbemis2656
    @alexbemis2656 2 ปีที่แล้ว

    Keep it's up, man. Your videos are essential to the trade!

  • @tommycho9068
    @tommycho9068 2 ปีที่แล้ว +1

    Great education video
    Many thanks
    P.S. Please keep it up for us.

    • @ElectricianU
      @ElectricianU  2 ปีที่แล้ว +1

      Thanks my friend! No plan on stopping anytime soon 🤙

  • @SHDWFocus
    @SHDWFocus 2 ปีที่แล้ว

    Just got out of my wire class where they showed us all this now I’m eating lunch watching this video on all the same stuff

  • @aboodymahdy
    @aboodymahdy 9 หลายเดือนก่อน

    Thank You, man. That was really helpful.

  • @earlgriffith3592
    @earlgriffith3592 2 ปีที่แล้ว +1

    What happened to the size of copper in wire after the late 70's? When in Electricity class in HS, used 12/2 back then and now 12/2 looks more like 14 gauge. It seems smaller and is easier to bend. 14 now looks like 16 or 18.

    • @jasonhessels
      @jasonhessels 2 ปีที่แล้ว +1

      My observational guess is the copper has been better compressed into its circular profile ie less air space between strands as well as better insulation formulations allowing thinner coatings.

  • @ismael4443
    @ismael4443 2 ปีที่แล้ว

    Dustin! Thank you my man for all the extraordinary content. 🤘🏽

  • @blakehorton8110
    @blakehorton8110 2 ปีที่แล้ว

    Omg I love this thank you so much for keeping everyone humble man...facts I love it 👌🖖🤘

  • @25TheCaveMan
    @25TheCaveMan 2 ปีที่แล้ว

    So much great info! Thanks man, you're doing good things here!!

  • @barnburner2475
    @barnburner2475 ปีที่แล้ว

    Great information, thank you Dustin!

  • @Nite20fly
    @Nite20fly ปีที่แล้ว

    Thanks you and you best.

  • @Leomej04
    @Leomej04 2 ปีที่แล้ว +1

    Bruhhh literally was looking at this stuff earlier today when I at the recyclers 😂😂😂

  • @BigGuy8059
    @BigGuy8059 ปีที่แล้ว

    One little point: Ampacity is all about the metal conductor size. You can look up the number of amps it is safe to run through various conductor sizes. This is how we get 14 gauge for 15 amp circuits versus 12 gauge for 20 amp. You can also look up how much power will be dissipated per foot by gauge and current. This will always be much lower than that needed to get to the 75 degree or 90 degree insulation rating. The insulation rating is for environments like near furnace exhausts and such. But the spaces in a residence that you run wire in is never going to be 75 C! A Texas 150 F attic is only 66 C. If you ever have a wire that is hotter than 75 C just from the current going through it, you need a larger conductor.

  • @justincampbell9535
    @justincampbell9535 2 ปีที่แล้ว

    THANK YOU! MUCH NEEDED VIDEO

  • @caylan8095
    @caylan8095 ปีที่แล้ว

    Super useful! Thank you.

  • @josephrhodes4844
    @josephrhodes4844 2 ปีที่แล้ว +1

    Have you ever done a video on the proper use of a DMM ? I see people trying to troubleshoot circuits a lot of the times and the first thing they'll try to do is measure across a fuse...

    • @misterkupsky7252
      @misterkupsky7252 2 ปีที่แล้ว +1

      If your circuit is otherwise complete, there will be voltage across the fuse if it is bad. That's how the blown fuse indicators work. Also a completed 3-phase circuit will put a voltage on both sides of a fuse which always confuses the newbies I am trying to mentor. Reading any voltage across a fuse indicates it is bad.

  • @edwinsGT8866
    @edwinsGT8866 2 ปีที่แล้ว +1

    There once was an inspector named Jessen
    who kept all the contractors guessin'.
    He said with a frown
    as he turned the job down.
    When will you guys learn your lesson?

  • @Dicer328
    @Dicer328 2 ปีที่แล้ว

    Great edits adding the arrow to follow along.

  • @jeffreydavis9059
    @jeffreydavis9059 ปีที่แล้ว

    Thanks for the knowledge it helps alot

  • @MrIsaacpr7
    @MrIsaacpr7 5 หลายเดือนก่อน

    Any chance you’ll be adding Florida to the continuing education list? Can’t wait! :)

  • @grassrunner7983
    @grassrunner7983 2 ปีที่แล้ว

    Nice one!

  • @ravasavideos
    @ravasavideos 2 ปีที่แล้ว

    Hi Dustin. Saludos desde Tijuana, BC. México. Good video

  • @morgan79347
    @morgan79347 4 หลายเดือนก่อน

    Well you hit on a lot of things I was looking for. I wish you had talked about what these wires are used for. I need to run from my panel through the basement then outside in conduit ending up at a sub panel. I was originally going to run SER 1/0 cable, it seems that electricians disagree on whether or not it could be burned in conduit. Any thoughts you have would be appreciated.

  • @bigcountry5520
    @bigcountry5520 2 ปีที่แล้ว

    Thanks for the hard work

  • @cameronblanchard4631
    @cameronblanchard4631 2 ปีที่แล้ว +1

    Hey Dustin. Can you explain how a rib relay works and how to wire it

  • @paulmaxwell8851
    @paulmaxwell8851 2 ปีที่แล้ว

    I'd really like to see you interview Steve.

  • @SquirrelsForAll
    @SquirrelsForAll 2 ปีที่แล้ว +1

    Hi Dustin! Could you please do a video on SER cable? Please! I'm wiring a 100 amp sub panel (80 ft run, through attic). I love the price of aluminum, but I'm hesitant due to the cold creep issues and corrosion problems (with/without Noalox). Copper just seems to exceptionally stable. I'm honestly not sure if aluminum is worth using, albeit 1/3 the price of copper. Maybe I'm just too old school. Thank you.

    • @Tech10x10
      @Tech10x10 2 ปีที่แล้ว

      I'm trying to figure out a similar situation. I would be interested in hearing what route you went.
      My job runs 90ft from the main panel in a garage, over rafters, down inside the wall, through a 2" hole and 1.25" PVC with a section of schedule 80 underground 18" deep then up and through a shed wall to a subpanel. That was the plan, anyway, until I pulled it through the first wall and realized the twists from the spool made it nearly impossible and I was shredding the jacket trying to force it. It was 2-2-2-4 AL SER and I feel very stupid for trying.
      I'm still not sure if I should use THHN/THWN-2 #4 with a conduit in the walls or if I can pull them through holes in the studs to the panel. The rafters in the garage need a 17ft ladder to access. If I have to put conduit up there, I may just consider not having power instead.

  • @snarkbark2714
    @snarkbark2714 2 ปีที่แล้ว

    what article talks about the wire from being damaged?
    That's just as important burnt up wire can break and cause fires in homes.

  • @smicaf
    @smicaf 2 ปีที่แล้ว

    Thanks for sharing your expertise and passion for the electrical trade. Got any advice for someone who is looking to get back into it after being out of it for 10+years?

  • @spelunkerd
    @spelunkerd 2 ปีที่แล้ว

    Just after 5:50, fun fact I had to look up today, I didn't know what mils was. It's thousandths of an inch, 20 mils is 0.020 inches. Used to measure plastic thickness, like garbage bags and glove thickness.

  • @secureedge7393
    @secureedge7393 2 ปีที่แล้ว +2

    Hey Dustin. Miguel here.
    If you have PVC conduit going underground; do you still have to use weather rated wire? ...Or even outdoor patio conduit for example... Could you just use THHN as long as it is inside conduit?
    Thanks bud, love the content!

    • @isaeproductions5217
      @isaeproductions5217 2 ปีที่แล้ว +2

      No, conduit outside is a wet location
      Must use thhw

    • @PGGraham
      @PGGraham 2 ปีที่แล้ว

      @ISaeProductions is right, but most THHN is cross rated as THWN as well. Check the listing.

  • @44R0Ndin
    @44R0Ndin 2 ปีที่แล้ว

    Kinda wish you got into the more exotic insulation types.
    Like MI for instance, whole buildings will be done in MI, but they're specialized buildings doing specialized things.
    I mean, from what I understand of electrical work, if you're building a rocket engine test stand, MI seems like a good choice.
    Same (but for different reasons) if you're supplying electricity to something like a rock crusher or wiring up a foundry.
    Things like that, what kinds of exotic wire types there are out there, and where you'd expect to find them, I think that could make an interesting video.

  • @fuegoman45
    @fuegoman45 2 ปีที่แล้ว

    Super informative. Even for a non electrician 🤙

  • @diySolarPowerFunWithRay
    @diySolarPowerFunWithRay 4 หลายเดือนก่อน

    Cool. Why would you use a thermoset over the other thermoplastic?

  • @garrysekelli6776
    @garrysekelli6776 2 ปีที่แล้ว +3

    Is there counterfeit wires from chinese labs that is say like it is a certain product but actually it is not?

    • @InspiredCraftsman
      @InspiredCraftsman 2 ปีที่แล้ว +1

      I've noticed this in the 12 volt wiring of vehicles. The amount of copper varies by a lot between wire manufacturers even though it says the same gauge. I'd be interested to see if this happens in high voltage wires.

  • @farrieterrisky
    @farrieterrisky 2 ปีที่แล้ว

    After the question I whisper to no one during the into music "use your code book"
    First sentence, let's grab our code book.
    I'm in the right place!

  • @codydouglass242
    @codydouglass242 2 ปีที่แล้ว

    Cool books for home use

  • @denverbraughler3948
    @denverbraughler3948 7 วันที่ผ่านมา

    Voltage doesn’t melt insulation. 10000V applied to a conductor won’t melt 600V insulation.
    Insulation undergoes *breakdown* when the electric field exceeds the dielectric strength of the insulation to a return path, presumably a grounded metallic raceway.

  • @Johnnybytheway
    @Johnnybytheway 2 ปีที่แล้ว

    Great video. I wish you would have made note of the diameter size difference which changes the number of allowable conductors in a raceway.

  • @snarkbark2714
    @snarkbark2714 4 หลายเดือนก่อน

    Correct me if I’m wrong, so even though romex and thhn have conductors with the same jacket properties, romex is in 60C because the sheathing will melt if it was at 90C?

  • @rob8823
    @rob8823 2 ปีที่แล้ว

    I was so sad to not hear my personal favorite ..MTW.. Ive heard it called machine tool wire. Also TEW. Probably not used too often for your main power runs but it is great for situations where workability in tight spaces is a factor, like control circuits.

  • @briansmyla8696
    @briansmyla8696 7 หลายเดือนก่อน

    You mentioned wet vs damp environments, but you didn't show the actual definitions of wet vs. damp as defined in the code. That's an important distinction, especially when you're a CE provider.

  • @gregc8394
    @gregc8394 ปีที่แล้ว

    Excellent. Question , can TNNW Tray cable be used in residential to feed subpanel in detached garage. 100 amp with conduit from house to garage .

  • @docbrazen
    @docbrazen 2 ปีที่แล้ว

    So there is stranded and solid too. Is stranded wire at the same AWG rated to the same ampacity? For example is 12 AWG THHN stranded and solid both OK for 20amp branch circuits?

  • @lrayvick
    @lrayvick 5 หลายเดือนก่อน

    Not even sure how to ask my question. I recently made a 250 foot extension cord out of TW 8 AWG flat 3 wire. The conductor bundle is wrapped in a black rubber-like protective layer. In our area this wire is normally used in water wells. It is in excellent condition. One end is plugged into a 30 amp RV recepticle off of our main breaker panel. We plug an RV "shore power" cable into the other end for occasional use. It is layed out across an open yard. We are in SoCal. From your presentation I conclude it has a 140 degree rating at about 40 amps. How do I test it for temp to see how I am doing relative to the spec? Do I wait until noon on a hot summer day, crank up the load and use an infared thermometer to measure the temp of the wire bundle? (Like most such specs I assume there is a pretty good safety factor i.e. that the cable covering/insulation won't melt until say 170 degrees). I assume I would do this closest to the load.

  • @jasonparkinson7621
    @jasonparkinson7621 2 ปีที่แล้ว

    I'm a little more smarter by watching this. Thanks, sir.

  • @network_king
    @network_king 2 ปีที่แล้ว

    I remember had electricians at my house run wire to the grage in a PVC conduit for a 100 amp service there, I had no idea what kind of wire was right for that. I assumed something waterproof as outside conduits from what I know tend to fill with water. Not even sure what they used maybe THHN is fine for that. I did have them up it a size though from like a #4 to a #3, if could be done in copper that is how i requested for between building and the mast i believe.

  • @bryceg5709
    @bryceg5709 ปีที่แล้ว

    Flourenated ethylene propylene is a plastic made of polyethylene and polypropylene blend PE soft PP stiff florenated is pfas its teflon to make it slick

  • @garywahle581
    @garywahle581 2 ปีที่แล้ว

    Great job/ thanks for the information

  • @leemarker944
    @leemarker944 ปีที่แล้ว

    Are you always available for questions? Thanks

  • @nicd5439
    @nicd5439 หลายเดือนก่อน

    Would a hybrid of outside conduit going from breaker, through wall of house into a crawlspace, (crawlspace not using conduit) then back out through wall of house to an outside receptacle, again with conduit work? Or does thhn or the like need to be in conduit regardless of environment? I want to keep outside of house as non cluttery as possible.

  • @jt-el8540
    @jt-el8540 ปีที่แล้ว

    New sub, great stuff brother 👍