ATV320 - How to - Configuration ATV for Modbus Tcp IOscanner

แชร์
ฝัง
  • เผยแพร่เมื่อ 3 ต.ค. 2024
  • ATV320 - How to - Configuration ATV for Modbus Tcp IOscanner
    How to configure the Altivar ATV320 to receive via Modbus Tcp the control and set point using the embedded display and SoMove.
    If you want to use your laptop you can use SoMove:
    www.se.com/ww/...
    The DTM for the ATV320:
    www.se.com/ww/...
    And the communication cable TCSMCNAM3M002P is required or ethernet cable

ความคิดเห็น • 20

  • @simonp613
    @simonp613 ปีที่แล้ว +1

    Hi, could you please do a same video but for ATV9xx? I would also love to see how to add ATV9xx to EcoStruxure Machine Expert because i have some trouble with that.
    Thanks for your videos, they are really helpfull!

    • @LeTomasAHUMADA
      @LeTomasAHUMADA  ปีที่แล้ว +1

      Hi Simon! I do not have a ATV9xx to play and make a video but if you try to use the template function or device is the same you just different drive, take a look: th-cam.com/video/NvO8Qp-R8p0/w-d-xo.html
      I will try to get that drive 💪🏻

  • @ghulamsarwar5899
    @ghulamsarwar5899 ปีที่แล้ว +2

    Hi, i am facing a problem and it is i have Modicon M340 plc which communicate with ATV32 over CanOpen network and i want to replace it with ATV320 and i added ATV320 canopen ESD file to project and also replace ATV320 with ATV32 in CAN hardware configuration in plc my plc still looking for ATV32 drive rather then ATV320 drive

    • @LeTomasAHUMADA
      @LeTomasAHUMADA  ปีที่แล้ว

      Hi Ghulam Sarwar! At the moment my knowledge on the M340 is not that good as the other PLC but if you have change the eds and replace the drive. I recommend you to check the configuration of the ATV320 to be control + setpoint via CanOpen and in the PLC side check how are you controlling the device then analyse and build the application to download it again. If the problem persist i recommend you to contact the Schneider Electric technical support of your country: www.se.com/ww/en/work/support/country-selector/contact-us.jsp

  • @clay_3545
    @clay_3545 5 หลายเดือนก่อน

    Assalamu'alaikum bro i want ask. Can we do a modbuss only using atv 320 and laptop, thank u

    • @LeTomasAHUMADA
      @LeTomasAHUMADA  5 หลายเดือนก่อน

      Hi there! You can use any plc or pc using modbus tcp to control the drive.

  • @НиколайКирев-и8ъ
    @НиколайКирев-и8ъ 2 ปีที่แล้ว +1

    Hi, I have almost the same configuration only that it is over ModBus RTU not TCP. How can I modify the output registers and perform the starting sequence of the ATV? Is there any libraries that I can use? Thanks!

    • @LeTomasAHUMADA
      @LeTomasAHUMADA  2 ปีที่แล้ว +1

      Hi there! For modbus serial communication you have a different area for the ioscanner. I do not know which plc you are going to use but check the next to videos so you can see how to make it work with a modicon m221:
      th-cam.com/video/JOq2tmi17BA/w-d-xo.html
      th-cam.com/video/NoK18heE3HA/w-d-xo.html
      Good luck!

    • @НиколайКирев-и8ъ
      @НиколайКирев-и8ъ 2 ปีที่แล้ว

      @@LeTomasAHUMADA Thanks for the reply, I use M262, unfortunately Machine Expert Basic does not support it.

  • @veys9655
    @veys9655 ปีที่แล้ว +1

    I've done all the parameters that you have shown on terminal. However when I send a data then it gives CnF error. I'm sending again 128 and reset the fault then it gives agan the same fault. Can you please help ?

    • @LeTomasAHUMADA
      @LeTomasAHUMADA  ปีที่แล้ว

      Hi there! Without being with you checking the drive is difficult, please follow the next faq:
      www.se.com/in/en/faqs/FA383980/
      If this does not work, check cable comm param also in the plc and finally reset the drive just in case you configured something that it shouldn’t.

    • @veys9655
      @veys9655 ปีที่แล้ว

      @@LeTomasAHUMADA Thank you for the answer. But I've already found the problem and solved it.

  • @petrurahovan5112
    @petrurahovan5112 17 วันที่ผ่านมา +1

    Salut ca sa conectezi pc cu altivar 320 trebuie cablu special ,multunesc

    • @LeTomasAHUMADA
      @LeTomasAHUMADA  17 วันที่ผ่านมา +1

      Hi there! If the ethernet comm card is not installed in the atv320 then you need the programming cable TCSMCNAM3M002P. In the pc you need the atv320 dtm from se.com

    • @PetruRahovan
      @PetruRahovan 17 วันที่ผ่านมา +1

      Mulțumesc mult dtm am înseamnă că trebuie cablu mulțumesc

    • @LeTomasAHUMADA
      @LeTomasAHUMADA  17 วันที่ผ่านมา

      @@PetruRahovan just in case the link for the DTM: se.com/uk/en/download/document/ATV320_DTM_Library/

  • @FredericZimm
    @FredericZimm ปีที่แล้ว

    Hi,
    we are using an ATV930 Drive with Quantum 140 534 14.
    We are facing some difficulties to set eup the communcation with the ATV.
    We already find out witch register we need to set up to read out the values we need (412742), and we have 9 parameters we read out, Lengtt is set to 10.It seems to work.
    But, to send the Command and the frequency Setpoint (CMD, LFRD, and CMI) and we are pointing to register 412742, length is set to 4.
    Unfortunately, the ATV doesn't recieve the Data, and in the IO-Scanner of the Concept V2.5 we are using, the line is "red"..
    What should we do ?
    Thanks !

    • @LeTomasAHUMADA
      @LeTomasAHUMADA  4 หลายเดือนก่อน

      Hi there! In this case i advice to contact the Technical Support in your country, the concept is a very old software (never worked with it):
      How to access to Schneider Electric Support
      th-cam.com/video/OgnkhPcSdZ4/w-d-xo.html

  • @aalim68
    @aalim68 2 ปีที่แล้ว +1

    Assalamualaikum
    Hi bro