How to do a Insulation Resistance Test on a Single Phase Installation

แชร์
ฝัง
  • เผยแพร่เมื่อ 20 พ.ย. 2024

ความคิดเห็น • 57

  • @mesh6969
    @mesh6969 ปีที่แล้ว +4

    Rajen is a legend, done my installation rules with an 'A' pass with his lectures as well as unit standards.

  • @MORLAIMOMOHCONTEH
    @MORLAIMOMOHCONTEH 24 วันที่ผ่านมา

    Amazing

  • @Abdul_blogs
    @Abdul_blogs 11 หลายเดือนก่อน

    Sir ek problem ye hai ki mere ghar ki electric bill bahut jada aara hai fir mai ne complaint kiya tho electric board wale bolte hai shyd aapki earthing problem hai ya aapke ghar ki wiring problem hai iske wajeh se aapki ghar ki electricity bill aa rahi hai ya aapke ghar ki freeze me problem hai ya aap ghr ki wiring cheak karo ya earthing proper karlo mai ne earthing cheak ki sahi hai bulb se cheak phase aur earthing acche se glow ho rahi hai abh wiring me kya cheak karna hai o batao sir aur proper earthing na hone se electric bill jada aati hai kya 400 unit aati hai har mahine plz help

  • @harunhm9214
    @harunhm9214 2 ปีที่แล้ว +6

    Helloo... when you did the IR test between LE & NE, you did not press the test button. That why the reading is OL

    • @212529Y
      @212529Y ปีที่แล้ว

      It's automatic , need not to press

    • @manojpydi8477
      @manojpydi8477 3 หลายเดือนก่อน

      H​@@212529Y

  • @lalantuddu
    @lalantuddu 5 ปีที่แล้ว +3

    Nice sir

  • @paulperriman9144
    @paulperriman9144 4 ปีที่แล้ว +15

    You assumed the power was off and didn't test it for any supply. You also didn't test the meter to see if it functions correctly. Never ASS U ME

    • @benmakokha3089
      @benmakokha3089 3 ปีที่แล้ว +3

      That is right! Especially for a training demo.

    • @shukelatraining8627
      @shukelatraining8627  2 ปีที่แล้ว +2

      Isolation process was not shown due to time constraints of video and editing. Video is to encourage enrolment on the course for full details of tests, regulations and instruments used.

    • @ahxishwe5664
      @ahxishwe5664 ปีที่แล้ว

      test the new installations first . safety 101.

  • @christophermcewan8065
    @christophermcewan8065 3 ปีที่แล้ว +1

    Thank you!

  • @snenhlanhlankabinde9698
    @snenhlanhlankabinde9698 5 หลายเดือนก่อน +1

    🙌

  • @wambuifred6637
    @wambuifred6637 ปีที่แล้ว

    This is great

  • @momohboima.s.1595
    @momohboima.s.1595 2 ปีที่แล้ว

    Please thank you for your efforts but please can you break it down to krio

  • @harunhm9214
    @harunhm9214 2 ปีที่แล้ว +1

    Hello,,,, when you did your IR test on LE & NE, you did not press the test button ;;;; that why the reading is OL

    • @shukelatraining8627
      @shukelatraining8627  2 ปีที่แล้ว +1

      Test button can be locked in test position. Video edited.

  • @mikethesparky4000
    @mikethesparky4000 3 ปีที่แล้ว +2

    Do you need to do a loop test when doing test on a single phase power

  • @simonmailu8335
    @simonmailu8335 2 ปีที่แล้ว

    Send vedio on how to carry out Pme,earth electrode test,earth loop impedance test pls.

    • @shukelatraining8627
      @shukelatraining8627  2 ปีที่แล้ว +1

      Videos will defeat the purpose of the course. Attend the course to get the full run down of the tests, instruments and methods.

  • @Xxxcappie23
    @Xxxcappie23 2 ปีที่แล้ว +1

    Can you explain why the switches need to be switched on for this test please?

    • @sanveersookdawe
      @sanveersookdawe 2 ปีที่แล้ว +2

      Probably to test the full length of the wiring

    • @shukelatraining8627
      @shukelatraining8627  2 ปีที่แล้ว +2

      Insulation must be tested up to the point of consumption terminals of lights and appliance. Note loads disconnected.

    • @prospero9955
      @prospero9955 ปีที่แล้ว

      If switched off, any hidden blunder or two opposing connector(L&N) might not be detected while testing but while it is energized Surg takes place.

  • @nathachasmith387
    @nathachasmith387 ปีที่แล้ว

    How to insall a pre paid meter

  • @chukwuamauche1881
    @chukwuamauche1881 3 ปีที่แล้ว +3

    Please can list all the 16 test to be done before certification of completion is awarded to an installation

    • @noahjaziel9172
      @noahjaziel9172 3 ปีที่แล้ว

      instaBlaster.

    • @valdimirputin
      @valdimirputin 2 ปีที่แล้ว

      Good question..... One was done, what are the other 15? How are the tests documented as test/fail?

    • @shukelatraining8627
      @shukelatraining8627  2 ปีที่แล้ว

      All tests are listed in SANS10142/1 or enroll for the course.

  • @WilliamKuyokwa-j9u
    @WilliamKuyokwa-j9u ปีที่แล้ว

    Oh. I remember when i was conducted practical at my institution school they ask me to explain how do you test insulation resistance test then i explained but i reached there we say select the meter on 500 DC after that invigelator asked me why you put on that 500 dc i failed even today please may someone tell me why?

    • @winniewamboi6801
      @winniewamboi6801 ปีที่แล้ว

      This is because if the insulator maintains its integrity at 500V then it will be safe for use under normal day to day voltages of around 240-230V

  • @arnoldbridgemudimu3814
    @arnoldbridgemudimu3814 ปีที่แล้ว

    Where are located plz

  • @arnoldbridgemudimu3814
    @arnoldbridgemudimu3814 ปีที่แล้ว

    Where are you located plz

  • @belimoventures3512
    @belimoventures3512 3 ปีที่แล้ว

    Continuity testing

  • @josephomom9492
    @josephomom9492 3 ปีที่แล้ว

    In which condition to you issue your certificate , i need one.

    • @shukelatraining8627
      @shukelatraining8627  2 ปีที่แล้ว

      Originals from D.O.L or registered organization like ECA, one must be a registered contractor.

    • @ahxishwe5664
      @ahxishwe5664 ปีที่แล้ว

      Insulation testing. Design amp for MCB check. RCCB check and testing. Which will be covered in another video.

    • @SollyNkogatsi
      @SollyNkogatsi วันที่ผ่านมา

      Where is shukela training?​@@shukelatraining8627

  • @williemobrien
    @williemobrien 2 ปีที่แล้ว

    You might want to learn how to bend pvc pipe first mate

  • @muhammadqadeer7808
    @muhammadqadeer7808 4 ปีที่แล้ว +5

    Dear Sir,
    You have a lot of mistakes in DB
    1- Colour Coding RYB
    2- Wire lugs and insulation missing
    3- Cable dressing not proper

    • @shukelatraining8627
      @shukelatraining8627  2 ปีที่แล้ว +2

      The panel is a training panel and the faults are for learners to identify as per your list and more.

    • @muhammadqadeer7808
      @muhammadqadeer7808 2 ปีที่แล้ว +1

      @@shukelatraining8627 plz make sure if you train people then you should have to maintain standards, bcz a lots of people following you.

  • @nathanl8438
    @nathanl8438 3 ปีที่แล้ว +3

    ha ha ha why dc ? is it a battery ? It needs to be ac :)) good luck to the learners

    • @roseelectronics4582
      @roseelectronics4582 3 ปีที่แล้ว +1

      insulation resistance test is done with dc voltage. at least, that's how these testing instruments are designed

    • @kukrikukemoer4956
      @kukrikukemoer4956 3 ปีที่แล้ว

      😂😂😂😂 the meter uses Dc

    • @mlungisimthombo3939
      @mlungisimthombo3939 2 ปีที่แล้ว

      insulation tests are done with dc voltage

    • @shukelatraining8627
      @shukelatraining8627  2 ปีที่แล้ว +1

      Instruments use batteries to operate and the output is therefore D.C.

    • @30mAkills
      @30mAkills 2 ปีที่แล้ว

      AC results in impedance value which is irrelevant here. See my another comment.

  • @geraldsibanda793
    @geraldsibanda793 ปีที่แล้ว

    Thank you!