How To Verify New Installation and Test MEN Switchboard

แชร์
ฝัง
  • เผยแพร่เมื่อ 24 เม.ย. 2021
  • Advanced: How to test and verify a new MEN switchboard and installation!!! Australia and New Zealand.
    Complete including explanations to testing and procedures.
    Including Visual testing, main earth conductor, earthing, insulation resistance, polarity, switchboard connections, line polarity, earth fault loop impedance and RCD testing. Explaining tests and discussing faults.
    To current legislation and wiring rules in Nz. AS/NZS 3000:2007.
    Subscribe and check out other amazing videos, only on Sparkydave.

ความคิดเห็น • 80

  • @baddi3sslay
    @baddi3sslay 3 ปีที่แล้ว +7

    Bless you for that sneeze at the start

  • @davidowens5178
    @davidowens5178 หลายเดือนก่อน +1

    Awesome Dave Thanks for the refresher never to old to go over all testing procedures

  • @Kratos-pz6cd
    @Kratos-pz6cd 3 ปีที่แล้ว +8

    Dude I’ve learnt so much from you. Great videos!

  • @AgunziLFC
    @AgunziLFC 2 ปีที่แล้ว +5

    Love your vids, i feel im learning more from watching yours than i am at Ara, its helping me a lot, thanks :)

  • @bigbobbyjohnson1
    @bigbobbyjohnson1 3 ปีที่แล้ว +2

    Really appreciate this video mate thank you!

  • @goodvibes0101
    @goodvibes0101 9 หลายเดือนก่อน +4

    Great effort these videos take time to produce thanks for the content Dave. The IR for existing installations is 1 megohm for new I believe it is 50 megohms. The main earth resistance does need to be taken at the earth stake / rod to take into account that connection. Equipotential bond similarly onto the metallic material not the connection device.

  • @damiengrant967
    @damiengrant967 ปีที่แล้ว

    Hey bro, excellent video. This shows you have skills not just as a sparky but also teaching, and making videos. Good man and well done. There are a few good points in the comments regarding testing which could be taken on board but I am definitely not trying to be negative or pick at your work. I actually really like it!!! Please do more

  • @waynejackson8556
    @waynejackson8556 ปีที่แล้ว +5

    Main earth resistance, you must test from the earth electrode (peg) (not the brass clamp) to the earth bar.

  • @sil3nt534
    @sil3nt534 2 ปีที่แล้ว +1

    Awesome video mate. 10/10

  • @P.James.7070
    @P.James.7070 7 หลายเดือนก่อน

    Thanks a lot Dave. I appreciate you going out of your way to help others by making videos with great workmanship and professionalism 'straight out of the trade', so to speak.
    I'm doing a pre-trade at ETCo.

  • @noahflynn4942
    @noahflynn4942 2 ปีที่แล้ว

    Awesome Video Dave!

  • @scottwhite115
    @scottwhite115 2 ปีที่แล้ว +1

    Great video. Thanks.

  • @MarcusMussawar
    @MarcusMussawar 3 ปีที่แล้ว +1

    great video really love the set up

    • @MarcusMussawar
      @MarcusMussawar 3 ปีที่แล้ว

      easy to follow easier to remember really great thank you

  • @colinreid7305
    @colinreid7305 3 ปีที่แล้ว +5

    Excellent information and will hopefully improve electrical installation standards and safety.

  • @ramanmultani4135
    @ramanmultani4135 3 ปีที่แล้ว

    Thanks been waiting for it.

  • @Bipolarvideos
    @Bipolarvideos 2 ปีที่แล้ว +3

    Dave, could you do a video on binding stranded with solid, and other small challenges a new sparkie might run into.

  • @rockyolsson
    @rockyolsson 3 หลายเดือนก่อน +1

    Love the video mate, I live in Nauru and there are many so call sparkies that are wiring houses and never do any test before utilities liven the building/house which is very dangerous for home owners. I work for the biggest private company and I done all our electrical from homes to hospitals, government offices and even the Australian embassy. I always do installation test and earth test to make sure everything is correct and safe before utilities hook up the power supply. Most of the homes that have been done by other electrician have problems and I would be called to check if it’s been wired properly and it is a disaster. Don’t know why it is even connected by utilities and I have to correct it and make it safe so no one would get electrocuted. Very few electrician follow the AS/NZS code or don’t even know anything about it and yet utilities still connected the house they wired. But now we are going to have our own electrical code which is based on the AS/NZS rule book which is good. I have three apprentice that work with that have already moved on to be good and trusted electricians and I am very proud of them. And regarding this video I have encouraged them to watch and let it be a reference or reminder when testing on homes they wired. Anyway keep them videos coming .Cheers.

  • @seanmcclure7828
    @seanmcclure7828 3 ปีที่แล้ว +10

    I interpreted it as If you actually calculate maximum demand on the three final subcircuits and it comes in under the RCD rating, that is still compliant, as opposed to just adding up each sub circuits rating.

    • @damiengrant967
      @damiengrant967 ปีที่แล้ว

      I guess the good thing about taking on board his way is that there is no margin for error. Room occupants can change and load demands on GPO's can change. So therefore if he had used two 20's and a 10 there is a potential future where someone overloads that RCD. I absolutely take your point, but I think I may adopt his methodology on this from now on.

  • @ezequielvaldivia6875
    @ezequielvaldivia6875 ปีที่แล้ว +1

    Good video, I´m Electrician certified too and the DS8(Chilean law for electrical instalations), contain more rules bout the wiring and main box, for security here it´s must install main breaker protector that protect cut omnipole phase and neutral "always" over all if exist more than three circuits + pilot light.. i´ve learned much with you videos.. I´m preparing my visa. thanks a lot, see´u soon over there in NZ..

  • @samituaisrael8533
    @samituaisrael8533 5 หลายเดือนก่อน

    Well presented. Thanks

  • @garycollinge633
    @garycollinge633 3 ปีที่แล้ว

    Great video

  • @justinfarquhar8299
    @justinfarquhar8299 10 หลายเดือนก่อน

    Thanks Great idea to make a some test gear using some resistors. I will copy you and do the same

  • @JasonTMND
    @JasonTMND ปีที่แล้ว +4

    Great video Dave, I watched this a couple of times ahead of my electrical refresher course and made some useful notes.
    I have replicated the polarity test plug too, this has made polarity testing 100% simpler for out in the field.
    Cool tip: I plug the polarity testing plug into a surface socket and have the alligator leads out of the terminals on there to replicate the lead version you have.
    Keep up the quality content!

  • @lanceanderson1653
    @lanceanderson1653 3 ปีที่แล้ว +1

    Hi, the socket outlet plug you use with the known resistances, what is going on in that plug? are the pins all bridged out?

  • @almerdiahmed3160
    @almerdiahmed3160 4 หลายเดือนก่อน

    Nice Job

  • @Cashiez
    @Cashiez 3 ปีที่แล้ว +2

    4:54 I have to agree but as a student I stumbled apon a SIT Polytech Relicensing course booklet
    which states based on 3000.2.6.2.1
    "The load rating of the RCD is not the sum of the number of connected circuit breakers but that of the largest single circuit breaker"
    so it sounds like there might be some interpretion within the industry?
    Although I personally agree with your statement Dave.

  • @antonsparks5147
    @antonsparks5147 2 ปีที่แล้ว

    Thank-you very much for the invaluable video. I'm trying to understand the "Connections check" discussion around 22min 56 sec into the video. The video shows that if both the socket and light breakers are open then there is no continuity between the top connections / load side of the socket and light circuits breakers. Won't they be connected via the RCD neutral bar if:
    * the light circuit switch is switched on, and,
    * the socket circuit is switched on and has an appliance in it?

  • @thenextkingofpirate3638
    @thenextkingofpirate3638 12 วันที่ผ่านมา

    Nice brother ❤❤❤❤❤❤

  • @benpopau7652
    @benpopau7652 2 ปีที่แล้ว

    So interesting

  • @Cashiez
    @Cashiez 3 ปีที่แล้ว +3

    I'm a student Dave & hate to through the book around, I totally have to agree with video time . 4:25 talking about RCD rating and maximum demand of sub circuits,
    AS/NZS 3000: 2007 - 2.6.2.1 say's that the maximum demand of the portion of the electrical installation being protected by the device or
    the highest current rating of any overload protective device on the portion of the electrical installation being protected .
    I have a a SIT polytechnic paper which translates this portion to being:
    2.6.2.1 [B] the highest sub circuit rating, so if we have 3x20 AMP MCB's = 60 AMPS, 20 AMPS being the highest rating, then this complies.
    therefore 16+16+6 = 38 but technically 16 amps is the highest rating and therefore complies
    BUT
    I remember that there are 4 way's of interpreting Maximum demand: (So Looked up the wiring rules)
    2.2.2 (d) limitation
    partial quote "may be determined by the sum of the current settings of the circuit-breakers"
    so this appears to have taught me somthing.
    :-D

  • @jay-peephillips2349
    @jay-peephillips2349 ปีที่แล้ว

    Hi there SparkyDave, first time here learning alot, appreciating the Uploads and enjoying the content.
    My question is, how would one identify whether a breaker is an overcurrent / overload protector, isolator and Earth-Leakage or circuit breaker?

    • @BrodieMarr
      @BrodieMarr ปีที่แล้ว +1

      You have RCD(residual current device) and circuit breakers.
      Rcd= earth leakage
      Cb= overcurrent
      Then there is RCBO which is a combination of the two.
      An Rcd/rcbo is always marked with the ‘type’ a,b,c,d,s.
      Trip time (30mA)
      Markings for the sine ‘curve’
      C16 is a ‘16 Amp, C’type’ breaker.
      63A main switch covers everything
      That 40 Amp Rcd is only covering the 3x C16 next to it
      The next 3 are for stoves,air con, hot water. (These go back to un-protected neutral bar)
      Covered by their own RCD(voltex)40A

  • @jacksonroad9263
    @jacksonroad9263 3 ปีที่แล้ว

    Do we need a earth rod and MEN link in a subboard if its > 50meters away from main switchboard?

  • @hallowadventure
    @hallowadventure ปีที่แล้ว

    Hey Dave, when you're referring to what regs say, you should drop a clause number, to back yourself up, since other people are shooting through their interpretations. :D

  • @JackWang-jx6xj
    @JackWang-jx6xj 20 วันที่ผ่านมา

    wonderful, learned a lot. Is your RCD breaking the neutral?

  • @JGNZ616
    @JGNZ616 2 ปีที่แล้ว

    Do you have to put caps on both ends of the bus bar?

  • @bedges35
    @bedges35 3 หลายเดือนก่อน

    Hi Dave,
    Love your video so clear , but one thing would like to clarify when you are doing the insulation resistant test the way you did it don’t you stuff up the Rcbo or the rcd ?
    Regards Hadi

  • @crazyethanyeahyeah
    @crazyethanyeahyeah ปีที่แล้ว

    Great video mate! Light bulbs in my house keep on blowing out - when I measure the voltage of the socket with the light switch turned OFF multi still reads about 80-120 volts? Does this mean there's a fault some where in the line? many thanks

  • @hexdator2934
    @hexdator2934 ปีที่แล้ว

    An insulation resistance test was completed between Line/Neutral to earth but, how did this method test the insulation resistance between Line and Neutral? Thanks.

  • @346sammy
    @346sammy 2 ปีที่แล้ว +2

    could you please do a video on rewiring a house

  • @samgoesfar
    @samgoesfar ปีที่แล้ว

    Hi dave, thank you for these videos. The question i have is, how do you short out phase and neutral when insulation resistance testing if the switchboard and meter board are live? cheers

    • @damiengrant967
      @damiengrant967 ปีที่แล้ว

      Isolate power and do the IRT testing when it is not live

  • @cheeseluke
    @cheeseluke 2 ปีที่แล้ว

    can you do fan timers ?

  • @stevievaughan6070
    @stevievaughan6070 2 ปีที่แล้ว +6

    great vids dave, but you need to insulation resistance test between active and neutral conductors as well as testing active and neutral conductors to earth. Also you have to turn on all gpo switches in case there is a fault in the gpo itself

  • @cookiecanfly_
    @cookiecanfly_ หลายเดือนก่อน

    Mate have you tried the fluke 1662? How does this megger compare? Thanks

  • @davidclarke2513
    @davidclarke2513 6 หลายเดือนก่อน +1

    Sorry mate but you can't use a socket outlet as a means of through box to wire a lighting g circuit which is on a totally different circuit because if you switch of the socket circuit of at the consumer unit it means that there are still live cables running through the socket,so mate you should have put a plastic tee box in like so the lighting cables do not go through the socket outlet

  • @klemmzagala2649
    @klemmzagala2649 2 ปีที่แล้ว +2

    you are from nz?

  • @DadBangr
    @DadBangr 2 ปีที่แล้ว

    Do you need to do fault loop impedance testing if the circuit is on an RCD?

    • @ozjuice
      @ozjuice 2 ปีที่แล้ว

      Yes, each circuits resistance needs to comply with the circuit device.

  • @taniorahala408
    @taniorahala408 5 หลายเดือนก่อน

    Soild stuff Sparkydave

  • @russelsprout2155
    @russelsprout2155 ปีที่แล้ว +1

    Type AC rcd's now banned since april 30th (my birthday) 2023
    In Australia

  • @Ressy66
    @Ressy66 3 ปีที่แล้ว

    IRT Test - how are you not frying the RCD/RCBO electronics, or LED drivers etc

    • @marklucas4274
      @marklucas4274 2 ปีที่แล้ว +1

      The RCDs and RCDMCB/RCBO dont mind the 500VDC from the IR test.
      I believe the LED didn't get fried because he bonded L & N so they were at the same potential and there wasnt 500V across the L & N of the LED driver, only L + N to Earth.
      Happy to be corrected if that is wrong. I always just unplug them from the 413/surface mount socket prior to meggering the circuit.

  • @jaymax9560
    @jaymax9560 3 ปีที่แล้ว +3

    Can you make a video on how to run wire through the walls and roof and how to secure them to standard. For ethernet and electrical? Thank You :)

  • @steveblunsden4295
    @steveblunsden4295 ปีที่แล้ว +1

    Hoi mate, how do you make up those polarity testers?

    • @sparkydave
      @sparkydave  ปีที่แล้ว

      Might show it in a vid at some stage... resistors (stock spares from alarm systems from memory) and cable/crocodile clips

  • @dongmingyuan5067
    @dongmingyuan5067 2 ปีที่แล้ว +2

    Nice socks LOL @7:35 . When will your new videos come?

  • @ajaykumartargotra2768
    @ajaykumartargotra2768 2 ปีที่แล้ว

    Hi there, I have question if you can answer! I think I have 10amp circuit breaker , now my question is how many led lights I can install on one circuit breaker? 10watt led light. 220v .thanks

    • @MrAStompy
      @MrAStompy 2 ปีที่แล้ว

      Convert Amps to Watts
      10 (Amps) x 220 (Voltage) = 2200 Watts
      Apply 80% rule- 2200 x 0.8 = 1760 W
      1760 / 10 (the Led light) = 176 Led lights

    • @ajaykumartargotra2768
      @ajaykumartargotra2768 2 ปีที่แล้ว

      @@MrAStompy many thanks for your kind reply 👍 🙏

    • @lovepreetmavi3915
      @lovepreetmavi3915 ปีที่แล้ว

      @@ajaykumartargotra2768 with LED, you need to take into consideration inrush current. Best way is to ask the manufacturer of the inrush current and the number of fittings on different type of mcb’s

  • @James_Bowie
    @James_Bowie ปีที่แล้ว

    In Oz, type A RCDs become mandatory in 2023.

  • @garydavidson6260
    @garydavidson6260 ปีที่แล้ว

    I am a little puzzled why you state that the RCD needs to have an amperage greater than the sum of its downstream circuit breakers. I thought that RCD's can handle far greater currents than actually stated (40 A, 63 A etc), however what is critical for RCD's is the 30 mA rating, which detects current imbalance anywhere in the circuit. Our new house, for example, has a "40 A" RCD (30 mA, type A) connected to several downstream circuit breakers totaling almost 150 A load (32 A + 20 A + 6 x 16 A), if all switched on simultaneously. Are RCD's in New Zealand different from those in Europe or am I missing something here. I am not a trained electrician...

    • @damiengrant967
      @damiengrant967 ปีที่แล้ว

      There must be more going on there then meets the eye. Because 150A going through a 40A RCD would absolutely trip it. What you see on the face and how it is wired may be different

    • @garydavidson6260
      @garydavidson6260 ปีที่แล้ว

      @@damiengrant967 Not 100% sure if something else going on but I do not think so. Unfortunately I cannot send photo of my setup here, but what I said above is true. It is a new house in France.

    • @IAmThe_RA
      @IAmThe_RA 7 หลายเดือนก่อน +1

      ​@@garydavidson6260I think it's because a 63A RCD is costlier and I heard that the regs in New Zealand or Australia require each RCD to protects no more than 3 circuits (probably to avoid nuisance tripping).

    • @IAmThe_RA
      @IAmThe_RA 7 หลายเดือนก่อน

      ​@@garydavidson6260The amp rating on RCD means that if the current pulled is bigger than the amp rating the device can get damaged. The same applies to main switch. That's why a fuse upstream is required to protect the installation.

  • @stanleyperez6368
    @stanleyperez6368 2 ปีที่แล้ว +1

    Say cute si stanley

  • @patrickjacobsen7805
    @patrickjacobsen7805 2 ปีที่แล้ว

    Chur bro

  • @Venom-nk8nd
    @Venom-nk8nd 8 หลายเดือนก่อน

    🇵🇬🇵🇬,,,

  • @stuartsmith4307
    @stuartsmith4307 6 หลายเดือนก่อน

    i wanted to watch it all the way to the end but fuc soz mate ui could nt handle ya nazzel voice and ya just sort of dragged this shit out , soz cuz

  • @infinityentertainment5500
    @infinityentertainment5500 2 ปีที่แล้ว +2

    Dear Dave, do you have any Facebook pages? if you don't mind can I have your contact no. pls? You are really amazing bro.