Shorted Contactor Coils - An Emerging Issue and How to Diagnose It

แชร์
ฝัง
  • เผยแพร่เมื่อ 30 ก.ย. 2024
  • Shorted Contactor Coils is an Emerging Issue and Bryan Orr shows how to diagnose it.
    Find the video on AC Blown Fuses here: • AC Blown Fuses - How t...
    Read all the tech tips, take the quizzes
    and find our handy calculators at www.hvacrschoo...

ความคิดเห็น • 138

  • @tokyocam
    @tokyocam 3 ปีที่แล้ว +11

    Crazy this just happened to me yesterday.

    • @tokyocam
      @tokyocam 3 ปีที่แล้ว

      Had nothing else hooked up to the board but the wires going outside. Jumped R and Y and blew the fuse. Went straight outside to resistance check.

    • @JoseJB0
      @JoseJB0 3 ปีที่แล้ว +5

      @@tokyocam Check the y & c wires from the attic to outdoors & next time go straight to the truck to get the contactor. 🤣👍

    • @joshuat2751
      @joshuat2751 3 ปีที่แล้ว

      @@tokyocam i had a short on my R and Y in the air handler from a crappy install. stripped the wires but the R and Y jackets were ripped in multiple areas touching each other.

    • @eliezerwittgreen367
      @eliezerwittgreen367 3 ปีที่แล้ว +1

      Same here! How crazy is this!

    • @inquisitivetechm5214
      @inquisitivetechm5214 3 ปีที่แล้ว

      Good stuff. I remember when this type of issue gave me problems years ago. I'm a commercial hvac service tech & a big thing that causes this issue now is low voltage. Either when the system was installed where they have 208v present & installers or other techs never change the transformer tap from 240v to 208 & when the supply voltage drops during the day the amps on the control circuit go up & eventually burn up the coils. I know that's not something you'll typically see in residential but things to be aware of. Also had a low impedance short on the contractor not blow the control fuse in the furnace but managed to fry the primary side of the transformer.
      Keep these videos coming Brian I share your site & videos with trainees regularly.

  • @paulrozinski1488
    @paulrozinski1488 3 ปีที่แล้ว +14

    We shouldn’t be surprised that more and more failures are occurring . Just like everything else in this world, the goal of manufacturers is “ make it cheaper”. That attitude is what keeps us busy.

    • @deoranferguson5657
      @deoranferguson5657 3 ปีที่แล้ว +2

      I agree 100%

    • @Spillmansgarage
      @Spillmansgarage 3 ปีที่แล้ว +3

      Yep! Sucks if you’re the homeowner, great if you’re the tech.

    • @bobdixon4998
      @bobdixon4998 ปีที่แล้ว +1

      And don't forget that the Chinese are not the consumers friend!

  • @Kilcrops0914
    @Kilcrops0914 3 ปีที่แล้ว +6

    I went to a no cooling call yesterday in a house with 2 carrier systems. Both systems were down with blown fuses and BOTH were caused by a shorted contactor. Only 2 years old too

  • @jwchicano
    @jwchicano 3 ปีที่แล้ว +8

    I've found a lot of these this past year.

  • @michaelmcewan5074
    @michaelmcewan5074 3 ปีที่แล้ว +5

    Thanks for the video. I too have been coming across this same issue with not only Carrier equipment but Rheem and Trane as well. I’ve also noticed the capacitors that Carrier uses in they’re residential equipment are pretty cheapo as well. I find them measuring below tolerance after only a couple of years and sometimes they completely fail within 3-5 years. It’s to bad they don’t use higher quality components within the equipment especially since they cause a no cooling situation which puts doubt in the mind of the homeowner about their choice in equipment brand and contractor.

  • @danieldelano9892
    @danieldelano9892 3 ปีที่แล้ว +3

    Made in China

  • @ejonesss
    @ejonesss 3 ปีที่แล้ว +1

    i am willing to bet that the manufacturers are starting to make the coils as 12 volt coils and over volting them to 24 volt.
    why? possibly copper prices have gone up in recent months and they are using half the amount of wire to save on costs to keep the contactor/relay at the same consumer price.
    to verify this theory tear down an old contactor coil and string it out and do the same for a modern one i am willing to bet the modern coil is half the length.
    they could just replace the power supply for the "y" circuit but the problem is not everyone replaces the entire system they may only replace the indoor unit or even just the control board and power supply and then it would not be enough to power the contactor.
    another possibility is for the manufacturer to use a resistor of the value of half the length of the coil to compensate for the missing length.
    one final way is to use aluminum or steel wire instead of copper as aluminum and steel is cheaper.
    at the scrap yard you get paid $2 to 3 per pound for number 2 copper.
    maybe you get 75 cents for the best aluminum scrap.
    steel or tin goes for 1 to 10 cents a pound and is paid by the 100 pound usually though some scrap yards will have a scale set up for smaller amounts of tin to accomodate those riding bikes pulling very small amounts of scrap.

  • @musicmakerman867
    @musicmakerman867 ปีที่แล้ว +3

    You held up the exact part in my AC. I wondered why my 3a fuse blew. Sure enough, I went and checked across the coil and got 0.9 ohm. Ordered one next day. Thank you for saving me money!

  • @garbo8962
    @garbo8962 3 ปีที่แล้ว +1

    I spent 50 years as a commercial electrician and NEVER came across a shorted coil. They bad coils were always open and never blow a fuse. Worked on coils from 12 to 480 volts mostly AC. When I opened a coil it might havs a black burnt spot where it arched when the voil opened up. Junk original equipment that manufactures install are garbage. If it was important or ran 24/7 would install a Square D or an Allen Bradley next bigger size starter.

  • @williamwilkerson4224
    @williamwilkerson4224 ปีที่แล้ว +1

    Had a 2019 contacter fail this week

  • @jericosha2842
    @jericosha2842 3 ปีที่แล้ว +1

    I'm a newer tech and I'm seeing this almost once a week. Maybe I'm unlucky. Been seeing it in newer Carrier and Rheem units.

  • @chrisgreen8897
    @chrisgreen8897 3 ปีที่แล้ว +3

    What about 3 pole contactors? Does the same apply for those as well? A new one out of box measures lower then the 2 pole.

    • @OcRefrig
      @OcRefrig 3 ปีที่แล้ว

      It’s Best to compare to a New one Out of the box. I Have a 3 pole , 60 amp contactor, 24 volt coil , measures 1 ohm brand new.

  • @sheldonrosenberger345
    @sheldonrosenberger345 3 ปีที่แล้ว +3

    I have seen this in a Trane A/C this week as well that was installed last year. It was a Homer branded contactor.

  • @clevc112
    @clevc112 2 ปีที่แล้ว +2

    Just rewound a 3 phase contactor coil today and it works great now. Had the same shorted coil look.

  • @antoniosantiago2770
    @antoniosantiago2770 3 ปีที่แล้ว +9

    8 ohms will blow a 3 amp fuse eventually. 24v /8= 3 amp. (Border line) Ohms law. I agree stick to 10 to 20 ohms. We have allot of 3 amps in some units out here. A 5 would hold better but stick to 10 to 20 ohms definitely. Great video I learned it the hard way

    • @davidb5952
      @davidb5952 2 หลายเดือนก่อน

      ohms law! Thanks for that reminder.

  • @rosskious7084
    @rosskious7084 3 ปีที่แล้ว +2

    Have seen this off and on for thirty years. Every great once in a while until about 2005 . It slowly increased until it is fairly common nowadays.

  • @ThelifeExperiment
    @ThelifeExperiment 3 ปีที่แล้ว +2

    I’ve had a bunch this week on Goodman’s. Keep finding them to have five ohms when they have twenty off the truck.

  • @FrostHVAC
    @FrostHVAC 3 ปีที่แล้ว +1

    I've seen contactors with 30-60 ohms that were popping low volt fuses/breakers. Is there a page/sheet for ohms needed for relay/contactor coils? I'd love to have that on hand to know. I've ran into this problem a few times, my first instinct is to replace the contactor if I find no direct shorts on low volt wires. Awesome vid bro

  • @tonycharron73
    @tonycharron73 ปีที่แล้ว

    QUESTION: if my original contactor (off a 2019 Rheem) was a Zettler single pole 24V coil (FLA 25 LRA 150 RES 35) what would. Good "upgrade" contactor be?

  • @coreyhowell6965
    @coreyhowell6965 ปีที่แล้ว

    Just replaced the contactor on my 2018 Goodman ARUF447D14AC air handler. One of the electric heat contactor coils was reading 2 ohms and not shorted to ground, now aux heat is working properly

  • @PosterityOf1776
    @PosterityOf1776 4 หลายเดือนก่อน

    Lesson learned. The top 🎩 switch should read 0 ohms.
    The coil should have between 12-20 ohms.
    I recently tested my coil at home and had 14ohms.

  • @hotfeva9843
    @hotfeva9843 ปีที่แล้ว

    Just ran a call on a 30 year old unit 😂 thing is performing better than most units manufactured in the past 10 years. Why is that? "Made in China" perhaps.....

  • @joejesko7410
    @joejesko7410 3 ปีที่แล้ว +1

    Good video, thanks. I had this same thing happen two weeks ago...blow fuse and low ohms (2) across the contactor coil. New coil was 14 ohms. Once replaced, unit was fine.

  • @TheTruthForum
    @TheTruthForum ปีที่แล้ว

    i got 120 volt contactors on the ahus in my building and im having issues with chattering... all wires are solid connections no corrosion and no low voltage im assuming the coil is bad on it.. funny part is it will fire the motor up if you give it a knock or two... and run for a hr or so and ill find it tripped at reset relay again

  • @sean2410
    @sean2410 2 ปีที่แล้ว +1

    This happened to both of my Bryant systems that were just two years new. They should have a recall on these defective made in China part!

  • @Chemp95
    @Chemp95 3 ปีที่แล้ว +2

    The sealed coils seem to fail more

  • @bobdixon4998
    @bobdixon4998 ปีที่แล้ว

    I have one shorted to ground. Yep and a blown fuse. Yes it's a carrier and yes it's Chinese!! I'm surprised !!!

  • @mts7274
    @mts7274 ปีที่แล้ว

    Why do some supply houses list that part as a "Contactor Relay"? Is it also a relay? Example... th-cam.com/video/y4sx84SHMlw/w-d-xo.html

  • @jkbrown5496
    @jkbrown5496 3 ปีที่แล้ว +1

    Southwire has a nice set of alligator clips that slip onto the standard meter probes. I got mine at Lowes.

  • @jkbrown5496
    @jkbrown5496 3 ปีที่แล้ว +1

    The couple I've taken apart, Packard and Dayton, have rectangular steel plate that is pulled down on to the E laminations. Same as the electromagnet in a toaster holds a plate keeping the toast down till the time runs out. The contactor you showed at the end of the video has another E profile mating to the removable E laminations to coil fits into. I could see how a fitting problem could creep into the manufacturing since those 3 surfaces have to mate flush. If an air gap remained, there would be higher currents since the reactance would be less. Like if you only partially inserted the core into a solenoid. Higher currents, more heat, eventually you see insulation failure near the center of the coil.

  • @bloajmj2680
    @bloajmj2680 ปีที่แล้ว

    Wow just checked from blowing fuse, coil was 1.2 ohms😮

  • @beardedSpartan454
    @beardedSpartan454 5 หลายเดือนก่อน

    I have had 3 no cool and heat calls because of this, most showing continuity to ground on my Y wire and i chased it back to the outdoor unit. However today i was thrown for a loop when the new contactor showed continuity to ground on the Y in to the contactor when i had it wired in? Wires were disconnected in the air handler/furnace. Is it normal to have continuity to ground on the 24 volt in on the contactor? New tech here

  • @sneezyferret6482
    @sneezyferret6482 ปีที่แล้ว

    Can a bad coil cause a contactor to engage and close a circuit, but fail to disengage when given a signal by the electronics, causing it to keep a closed circuit until physically switched off?

  • @wilfredovega577
    @wilfredovega577 3 ปีที่แล้ว +1

    Thank you for your amazing insight and knowledge. you are very thorough in explaining every detail . thank you.

  • @edoneill6701
    @edoneill6701 ปีที่แล้ว

    should just go ahead and have that calm down drink before the video, the alcoholic had shaking is nauseating and made those close up hand shots maddening to follow. geezus man

  • @joshuat2751
    @joshuat2751 3 ปีที่แล้ว +1

    ran into this 3 times in the past month, also alot of blower motor modules on carrier units failing lately.

  • @marcusmcduffie2106
    @marcusmcduffie2106 2 ปีที่แล้ว +1

    Thanks for this video I referred to it today lol. Im a experienced hvac technician but I always want to double check that I am doing my ohms testing right. I salute you and appreciate your pointers and teaching , it shows that you have a passion for helping others in the trade. God bless you sir and continue doing what you do it really helps and your knowledge/ clarity stick with us and its not over our head teaching.. take care talk to you soon...

  • @michaelcostello6991
    @michaelcostello6991 3 ปีที่แล้ว +1

    These examples are wonderful. This info can be very useful outside of air conditioning also. I briefly worked alongside a very experienced tech who would tell me nothing and stab you in the back. Went back working as a mechanical fitter in a factory but am still interested I learning. Thanks

  • @dannysmith713
    @dannysmith713 3 ปีที่แล้ว +1

    I've found new contractors with one side of the coil not connected to the terminal.

  • @Sc19869
    @Sc19869 11 หลายเดือนก่อน

    So for the coil we want high resistance and if it’s low it’s shorted and for the path of current we want 0 to low resistance.

  • @ismaelsilva7893
    @ismaelsilva7893 21 วันที่ผ่านมา

    Dose this test apply to any contactor for example a 3 pole contactor will the resistance value be same.

  • @YouTubeCommunists
    @YouTubeCommunists 3 ปีที่แล้ว +2

    Greatest teacher ever Brian,thank you.

  • @Inverselattice0
    @Inverselattice0 ปีที่แล้ว

    Is the black stuff on the copper a clear indicator that the coil is bad

  • @joeyysossa4144
    @joeyysossa4144 ปีที่แล้ว

    I have a Mabe brand 220V 2ton minisplit the neighborhood had a power surge my minisplit was working wierd it soinded ""weak"" when I looked at the contactor it had no info on the voltage to activate the coil...how can I find that Information???

  • @billj4859
    @billj4859 3 ปีที่แล้ว +1

    My last call on Friday was a shorted contactor coil and blown transformer.

    • @jamesleroy2784
      @jamesleroy2784 3 ปีที่แล้ว

      Weird me as well . On a 2yr old American standard . Blown transformer then shorted out contactor

  • @unclemike8467
    @unclemike8467 3 ปีที่แล้ว +1

    Such a clear, focused and practical video!

  • @Grey-Troll
    @Grey-Troll ปีที่แล้ว

    Thanks for the informational content from a member of the DIY-or-DIE crowd haha One look at the low voltage schematic and a quick look confirmed this is what keeps popping 3A fuses... after going through half a bag of 50 fuses due to not finding a 'dead short' right off.
    Mine was tough to nail down because it would sparitacally work and kick on the unit outdoors, then go back to popping fuses after running for a few mins. I like wiring jobs in any number of other hobbies, but this hvac short has been a chore, and blatantly treated as such for the past 8mo to a year due to procrastination. Thankfully I don't live where its triple digits and can survive my lazyness. Switching to a backup wood/oil furnace over the winter is fine, but dang I wouldn't survive an afternoon in texas the temps they've had lately in some parts. I know some folks down there and all I say is I hope they keep and enjoy all that as much as I enjoy the cold weather haha

  • @Fatboy53
    @Fatboy53 ปีที่แล้ว

    Thanks! AC wasn’t working; this fixed it! 2013 Carrier 2 ton. In Utah, bought for $20 at Ferguson and the coil for $13. Thanks again!

  • @joesmoe3073
    @joesmoe3073 2 ปีที่แล้ว

    Everything is failing on carrier

  • @wpl11972
    @wpl11972 3 ปีที่แล้ว

    Brain, You missed a part. You said this is happening in Carrier units. You should have touched on the transformer. If you only have 208v coming in and the transformer is set to 240 from factory. Your low voltage is going to be lower. This will cause the coil to have higher amperage. More heat will short a coil.

  • @lindakingsley6765
    @lindakingsley6765 10 หลายเดือนก่อน

    is it possible to buy replacement coil online

  • @vannicholson6191
    @vannicholson6191 2 ปีที่แล้ว

    Thanks for the. video!I replaced my 10+ year old contractor abut two weeks ago along with my capacitor. Got home from work yesterday to a completely dead system, blown 3 amp fuse on the board. s soon as I opened the service panel outside I could smell the shorted coil. old coil read 14-20, the new one on the unit was at 0.7. got a replacement down the street on a Saturday lol, sweet fix.

  • @tylercaton6145
    @tylercaton6145 2 ปีที่แล้ว

    emerging problem - interesting. reading 0.00 across low voltage on my contactor and couldn't find many videos addressing this. thanks!

  • @Xlr8Fragz
    @Xlr8Fragz 3 ปีที่แล้ว

    Had this multiple times this year but came across something interesting with a single pole contactor on a call yesterday. Door switch on furnace blown, transformer blown. Replace both, blower turns on no led on board. Smell the transformer right away. Check voltage at board and had 7 volts between R and C. Electrical shunt? Replace the contactor fixed all issues

  • @HVACTechKnowledgy
    @HVACTechKnowledgy 3 ปีที่แล้ว

    Yeah I'm curious to know what's going on myself. I've replaced like five or six contactors in the past 2 weeks.

    • @willys7974
      @willys7974 3 ปีที่แล้ว +1

      Chinesium bullsh*t

  • @RalphMercuroMusic
    @RalphMercuroMusic 3 ปีที่แล้ว

    Curious what the unloaded control voltage is. If Carrier is using cheap transformers you may have 30 volts before a call for cooling. High voltage hitting the coil every cycle will damage the coils. Worth a shot to check on the next one... This was an issue with 24volt gas valves failing in the late 90's.

  • @userok209
    @userok209 28 วันที่ผ่านมา

    thanks ............free Palestine

  • @ajpiazza01
    @ajpiazza01 2 ปีที่แล้ว

    This just happened to my Bryant installed in late 2018. Same symptom of a blown fuse when the thermostat calls for cooling. Tested all the wires to rule out a thermostat or some other short. The 24v terminals on the contactor had zero resistance. Took the cover off the back of the contactor and the coil looked and smelled burned. It looked just like the coil at 5:55 in this video. This should not happen on a system that is less than 4 years old. Cheap parts. Thanks for the video!

  • @Savage-lx5yj
    @Savage-lx5yj 3 ปีที่แล้ว

    My guess is this is a result of reverse EMF produced by the quick collapse of the magnetic field. I wonder if the addition of a diode would correct the problem.

  • @b-2466
    @b-2466 2 ปีที่แล้ว

    This happened at my house yesterday. No power to thermostat. Wires looked okay, air handler looked burnt up, ohmed out at 3.7 ohms. Thanks for the info hvac school.

  • @gamewizardks
    @gamewizardks 3 ปีที่แล้ว

    I ran into this issue last summer with 2 different contactors. The first one the Furnace Control Board was not fused and this issue fried the transformer. It took awhile for me to isolate because I've never run into it before. The 2nd time it happened, I knew right where to go.

  • @mikefixac
    @mikefixac 3 ปีที่แล้ว

    Hey Brian, just came across this YT channel. Really good stuff, thanks much.

  • @DavidHernandez-gt9bo
    @DavidHernandez-gt9bo 3 ปีที่แล้ว +1

    Good explanation 👍

  • @karmanator2
    @karmanator2 ปีที่แล้ว

    Say you want to trigger that switch artificially to test it live. What would be the easiest way?

    • @davidkendall4588
      @davidkendall4588 ปีที่แล้ว

      Poking the button on the front of the contactor with a screwdriver worked for me. Just be careful.

  • @toolemanful
    @toolemanful 2 ปีที่แล้ว

    Have u heard of a code 73 on a carrier 24ana

  • @dripYAdivys
    @dripYAdivys 3 ปีที่แล้ว

    I've been seeing this in some trane air handlers I service. They use contactors instead of sequencers. I would like to recommend a video. Go over boiler zone valve controls. How to wire them, th-tr, tr, th. How the end switch side works.

  • @hkhsm359
    @hkhsm359 3 ปีที่แล้ว +1

    Thanks for sharing

  • @gregmercil3968
    @gregmercil3968 3 ปีที่แล้ว

    I changed out a contactor a few weeks ago where the contacts very very burnt and pitted, but the coil itself ohm’d out just fine. 😆

  • @wbquarles
    @wbquarles 2 ปีที่แล้ว

    Just to add. Not all shorted contactors will cause the fuse to blow or a burnt transformer. I've had the majority just cause the unit to not run or maybe what I call scramble the t-stat until the contactor is replaced. I've had new tecks take hours trying to troubleshoot the issue until they either do a head slap and find it or call me and I tell them what to look for on the contactors.

  • @nehemiasmartinez6286
    @nehemiasmartinez6286 3 ปีที่แล้ว

    Starting HVAC school in September! my gush learning a lot from you

  • @Humble-Bee
    @Humble-Bee 3 ปีที่แล้ว

    Carrier is known to have issues of short lifespan of this contacts, at times no fuse is blown but the step down transformer burnt. In cases they damage the board before the fuse go out.

  • @myhitoho
    @myhitoho 3 ปีที่แล้ว

    I seen this with a match up we use with carrier and nest thermostat.
    Gives me error code of your signal lost.
    As soon as I replace contractor fixes issue.

  • @jamesleroy2784
    @jamesleroy2784 3 ปีที่แล้ว

    Ive had a lot of those Homer brand contactors shorting out.. had one last week on a 2 yr old American standard , and many more on Carriers

  • @OcRefrig
    @OcRefrig 3 ปีที่แล้ว

    Hi Brian,
    Thanks for the update on a Field Related Problem you are seeing. It helps us all !!!
    But,
    I Have a brand New 3 Pole Contactor ( 24 volt coil ) on my Table That Measures 1 Ohm resistance across the coil. I’ll double check it. But, You Might want to make a updated video that states Less than 6 ohms is not ALLWAYS
    A Shorted coil. Depends on Voltage , size of contactor , manufacturer etc.
    a Good reference is just grab a New Coil off the truck and it ohm it to make a reference.
    Just a FYI.

    • @OcRefrig
      @OcRefrig 3 ปีที่แล้ว

      Brian,
      the Contactor is a Very Large 3 Pole , 60 amp contactor. 24 volt coil.
      Johnstone # L36-697
      Make: Eaton
      Model: C25FNF360T
      Definately purpose contactor
      1 Ohm across coil. Brand New. Never used.

  • @wilfredovega577
    @wilfredovega577 3 ปีที่แล้ว

    This happened to me this afternoon. on a Carrier unit. I had to replace 3 amp fuse and outdoor 1+ contactor.

  • @deoranferguson5657
    @deoranferguson5657 3 ปีที่แล้ว

    Just was reading in one of my books. Very good that you showed the omhs . A lot of people miss that's part

  • @hewaakrey8581
    @hewaakrey8581 3 ปีที่แล้ว

    Hi how i know the working discharge and suction pressures of each frions
    Thanks for video

  • @crapmusstank6558
    @crapmusstank6558 3 ปีที่แล้ว

    Good parameters for 24v coils. Expected resistance changes depending on the voltage of the coil.

  • @lindakingsley6765
    @lindakingsley6765 10 หลายเดือนก่อน

    just had one do that

  • @officerdaughtry
    @officerdaughtry 2 หลายเดือนก่อน

    Good video

  • @Rizzman82
    @Rizzman82 ปีที่แล้ว

    GREAT JOB SIR

  • @pinkasbreuer6094
    @pinkasbreuer6094 3 ปีที่แล้ว

    Thanks for the video I had contactor failure cause coil last week

  • @Gabriel-vz7ml
    @Gabriel-vz7ml ปีที่แล้ว

    Thank you

  • @LBZ8581
    @LBZ8581 ปีที่แล้ว

    TTThhhaaannnkkk yyyooouuu!

  • @mikefreedom5612
    @mikefreedom5612 3 ปีที่แล้ว

    It's really hard to claim any coil < 6 ohm is failed coil. Usually you can go by elimination, testing directly the contactor, or insulation test ( during that test many processes are involved according to type of coil, etc...)

    • @mikefreedom5612
      @mikefreedom5612 3 ปีที่แล้ว

      @@richw4166 what you are pointing to is DC current calculation. What we measure with our multimeter is just resistance but when coil is under power so we talk about impedance and inductance of the coil. Low resistance doesn't means always bad coil because impedance is the most important here. Like you have s bulb with a coil of very low 1 ohm , didn't mean that current though that coil is 110A.

  • @arthurayers5044
    @arthurayers5044 ปีที่แล้ว

    Pure Quality. Thank You.

  • @danieldelano9892
    @danieldelano9892 3 ปีที่แล้ว

    I have found bugs fried inside where the contacts are made, also the contacts are just fried together and won’t open. Ants invested the contactor and made it stop working.

  • @agostinodibella9939
    @agostinodibella9939 3 ปีที่แล้ว

    I wonder if you could put a 2 amp fuse in series with the contractor coil to protect the rest of the AC circuit from going dead if the coil shorts out? At least your blower fan would still work.

    • @davidkendall4588
      @davidkendall4588 ปีที่แล้ว

      If you turn off cooling at the thermostat and replace the fuse, the fan will run. It’s only when you call for cooling that you’ll blow the fuse and shut everything down.

  • @thrivehappy9610
    @thrivehappy9610 2 ปีที่แล้ว

    Hello teacher. Thank you

  • @donnierobertson3088
    @donnierobertson3088 3 ปีที่แล้ว

    Nice job and video like always

  • @joeaugustine2245
    @joeaugustine2245 3 ปีที่แล้ว

    I’m Swapping a lot on Ruuds too

  • @_HVACdad
    @_HVACdad 3 ปีที่แล้ว

    Name of Brand for those leads?

  • @jamesmerrill4745
    @jamesmerrill4745 3 ปีที่แล้ว

    If the coil is bad can the contactor still pull in intermittently? Or once the coil reads low ohms its done.

    • @jbecker386
      @jbecker386 3 ปีที่แล้ว

      Once the coil shorts like that, it's done.

  • @jasonb.1749
    @jasonb.1749 3 ปีที่แล้ว

    Had one Thursday

  • @felipepradaserrano777
    @felipepradaserrano777 3 ปีที่แล้ว

    I was needing this video today 😞

  • @superiorcomfortheatingairl4636
    @superiorcomfortheatingairl4636 3 ปีที่แล้ว

    Thank you for sharing, I was unaware this was happening on newer units. I am assuming since these are under warranty the distributor are going to give us the the same low quality contactor until their inventory is depleted. Does anybody recommend any brand for the reliability? I have had a couple issues with Jard and Packard brands in the past

    • @OcRefrig
      @OcRefrig 3 ปีที่แล้ว

      Eaton & Ge - Makes a Good product.

    • @davejohnsonnola7908
      @davejohnsonnola7908 3 ปีที่แล้ว

      Emerson SureSwitch. It is solid state, sealed unit that crazy ants cannot get into.

  • @jbecker386
    @jbecker386 3 ปีที่แล้ว

    Found one yesterday

  • @haabhhh4290
    @haabhhh4290 3 ปีที่แล้ว

    Very informative

  • @davidkendall4588
    @davidkendall4588 ปีที่แล้ว +1

    My Carrier installed in 2019 just quit two days ago and kept blowing fuses when the AC tried to kick on. Took a while to figure out where the issue was, but after physically depressing the contactor button and seeing the fan at the condenser spin up, I was pretty sure I found the problem. Then I watch this video and sure enough it’s talking about shorted contactors in 2019 Carriers. Good stuff. Not a tech, but as a homeowner who likes to fix stuff myself, content like this is valuable.

  • @joeyysossa4144
    @joeyysossa4144 ปีที่แล้ว

    Great video...im saving it.