Hello, I urgently need your help. I have a DSE 6020mklll generator, currently configured for three-phase 400V. I want to change it to three-phase 230V. Please provide step-by-step guidance on how to confirm the changes on the DSE controller after modifying the starter connection to a delta connection. Additionally, please advise on how to configure the cooldown time after manually switching off the generator. Note: It's a 30kW 12 Leads generator.; I hope you can assist me here.
I am struggling with two issues. The first is the actual pins on my HGN6120NC controller I connect with a two wire remote start system. The second is how to wire a preheater to the controller. What pins on the controller will send a 12 volt power to a relay that can then feed the battery power to my preheater during the preheater phase of the starting procedure?
@@benzblogsVlogs Thank you for the information. I did get the preheater sorted out with your help. However, I am still having a difficult time figuring out how to connect the HGN6120NC controller to a two wire remote start. I am off-grid and it seems to need a mains power to go out for a remote start to function. Is there any way around this?
...In other words, without a mains power source (an off-grid system) is there any way to remotely start and stop an HGN6120NC controller with a two wire remote start system?
I have the hgm6110n, is it compatible with the cmm366 module? I want to remotely monitor the generator's vitals making use of the smartgen cloud platform
Can i set my smartgen 6100 to completely shut off all power for a certain amount of time when the grid power comes back. Basically, i have a 500kva generator with an 800amp automatic change over switch. However, when the grid power comes back on the generator switches from generator to grid to quickly and then all the vsd's and pumps run on under faults. I need the generator to completely cut power for 30 seconds before turning on the grid power. Thank you
Hi. How do you configure the settings on the hgm6120n module. I used the 0636 password which opened but couldn't set the configurations. The 0318 couldn't even open.
Thank you so much sir. Am in Uganda and am very much interested in learning more about generators with you. Kindly give me a chance. Am currently working as a telecom power technician here in Uganda with I' engineering. Kindly let me know what it takes. Thanks sir.
good morning sir;; i have a genset 220v single phase with smartgen hgm6120n, can i connect directly from the mains voltage (ESAMELCO) to port 31 - 34, ??
good morning sir, i have genset , 220v - single phase with smartgen hgm6120n , can i connect directly MAINS VOLTAGE(ESAMELCO) to port 31 - 34,?... salamat po
Sir I have hgm6110N.but when I start the engine.. Their alarm is under fraq alarm then engine shutdown in a few minutes.I don't know how to solve the problem.I hope u helping me. Thank you
Underfreq meaning its from the voltage if under speed is from your engine just check run the genwrator take a look with the voltage this ither no voltage low
@@benzblogsVlogs diko po ma start yung genset hanggang crangking lng po sya, after non lumalabas na yung fault nya na no gens frequency Regarding po sa mpu 900 something yung reading
Check mo kong tama ang pinkconnectkan mo sa wire at ats dapat ng close ang contact pag ng command ang ats kong may ats di kc gagana yan kong e auto mode mo kong walang mg bigay ng command na omandar dapat my command na nangagaling sa ats
magkano kaya idol dapat ko singilin sa may ari kc. na damage cya ng rat.. lahat ng wiring kinain ng daga pati ung SmartGen butas butas na talaga wala na display lumilitaw illumination na lng ng backlight nya.. nakabili nko s shopee.. rewiring ulit cya at installation ng Smartgen at configuration.. sa tantya mo sir idol magkano dapat sinigilan doon? wala ako idea.. galing kc ako abu dhabi di ko alam presyuhan ngaun dito sa pina
Simple sir if u need remote go to digital input any of the stlots you can do the config as remoth start and just uncheck the amf so its not work during auto function
From ats search the remote start this is two wire but make sure dry contact not voltage out from ats side thin from the genrator module its in the digital input but you need to check in the config or in the tagging
Hello, I urgently need your help. I have a DSE 6020mklll generator, currently configured for three-phase 400V. I want to change it to three-phase 230V. Please provide step-by-step guidance on how to confirm the changes on the DSE controller after modifying the starter connection to a delta connection. Additionally, please advise on how to configure the cooldown time after manually switching off the generator. Note: It's a 30kW 12 Leads generator.; I hope you can assist me here.
Nice idol salamat sa pag share ng video mo
Welcome lods salamt din sayo
Hello, I urgently need your help. I have a DSE 6020mklll generator, currently configured for three-phase 400V. I want to change it to three-phase 230V. Please provide step-by-step guidance on how to confirm the changes on the DSE controller after modifying the starter connection to a delta connection. Additionally, please advise on how to configure the cooldown time after manually switching off the generator. Note: It's a 30kW 12 Leads generator.; I hope you can assist me here.
I am struggling with two issues. The first is the actual pins on my HGN6120NC controller I connect with a two wire remote start system. The second is how to wire a preheater to the controller. What pins on the controller will send a 12 volt power to a relay that can then feed the battery power to my preheater during the preheater phase of the starting procedure?
Go to digital ouput config preheatduri g preheat timer add one relay for your sw 12 vdc goingvtobyour heater
@@benzblogsVlogs Thank you for the information. I did get the preheater sorted out with your help. However, I am still having a difficult time figuring out how to connect the HGN6120NC controller to a two wire remote start. I am off-grid and it seems to need a mains power to go out for a remote start to function. Is there any way around this?
...In other words, without a mains power source (an off-grid system) is there any way to remotely start and stop an HGN6120NC controller with a two wire remote start system?
I have the hgm6110n, is it compatible with the cmm366 module? I want to remotely monitor the generator's vitals making use of the smartgen cloud platform
Yes it is you can use rs232 for cloud monitoring support
Thanks sir for your good explanation.
Haw can I get software of this conteoller? Is it free like dse, comAp or dief?
Just go to there website
Can i set my smartgen 6100 to completely shut off all power for a certain amount of time when the grid power comes back. Basically, i have a 500kva generator with an 800amp automatic change over switch. However, when the grid power comes back on the generator switches from generator to grid to quickly and then all the vsd's and pumps run on under faults. I need the generator to completely cut power for 30 seconds before turning on the grid power. Thank you
Meaning you have automatic transfer switch
Hi. How do you configure the settings on the hgm6120n module. I used the 0636 password which opened but couldn't set the configurations. The 0318 couldn't even open.
Only basic config that you can donon that this full config is need a laptop and software to do full config
Sir where do I connect remote start on that controller. Thanks. I appreciate your work
Go in digital input if u have sofeware and the laptop much easier to find it coz its always depend on the config bit its in digital input
Thank you so much sir. Am in Uganda and am very much interested in learning more about generators with you. Kindly give me a chance. Am currently working as a telecom power technician here in Uganda with I' engineering. Kindly let me know what it takes. Thanks sir.
good morning sir;; i have a genset 220v single phase with smartgen hgm6120n, can i connect directly from the mains voltage (ESAMELCO) to port 31 - 34, ??
V2
Thanks bro
Welcome bro
good morning sir, i have genset , 220v - single phase with smartgen hgm6120n , can i connect directly MAINS VOLTAGE(ESAMELCO) to port 31 - 34,?... salamat po
Yes only the sensing to the module to know if any blockout so generator automaticly start but it should be automativ breaker
I have the 6120N and the ATS starts immediately when I press Auto. Can you please tell me what I have to do to correct this. Thanks
Dis able the amf function
Use the temot start cntrol
@@benzblogsVlogs Thanks for the advice but how do I do that? Can you please explain it to me?
@@RayDe-n8h go to configuration there u can find the amf juat dis able it
@@benzblogsVlogs Can you please tell me how to do that? Thanks
Sir I have hgm6110N.but when I start the engine.. Their alarm is under fraq alarm then engine shutdown in a few minutes.I don't know how to solve the problem.I hope u helping me. Thank you
Underfreq meaning its from the voltage if under speed is from your engine just check run the genwrator take a look with the voltage this ither no voltage low
Sir i would like to join you for training. What does it take. Thank
Welcome sir
Sir, ganyan controller nmin nag aalarm ng no gens frequency?
Ok first make sure that during engine run there volatge correctly thin if there is mpu installed check and check ngine speed if correct
Just sinoly start check the voltage amd the speed if normal if no voltage thin rectify first
@@benzblogsVlogs diko po ma start yung genset hanggang crangking lng po sya, after non lumalabas na yung fault nya na no gens frequency
Regarding po sa mpu 900 something yung reading
Sir ask ko lng po anu kaya problem once na auto mode ung smartgen control ayaw umandar ng genset? Slamat po sa feedback
Check mo kong tama ang pinkconnectkan mo sa wire at ats dapat ng close ang contact pag ng command ang ats kong may ats di kc gagana yan kong e auto mode mo kong walang mg bigay ng command na omandar dapat my command na nangagaling sa ats
Sir pwede ko po b kau contact sa messenger?
Maraming salamat po 8n advance
@@gbmajin welcome hanapin mo ang remote strt ng ats
idol pwede ba yan ikabit sa 25 kva na single phase na diesel generator..kc nakabili ako ng ganyan sa shopee china ang seller HGM6100N
Pwedi kaso e config mo mona
magkano kaya idol dapat ko singilin sa may ari kc. na damage cya ng rat.. lahat ng wiring kinain ng daga pati ung SmartGen butas butas na talaga wala na display lumilitaw illumination na lng ng backlight nya.. nakabili nko s shopee.. rewiring ulit cya at installation ng Smartgen at configuration.. sa tantya mo sir idol magkano dapat sinigilan doon? wala ako idea.. galing kc ako abu dhabi di ko alam presyuhan ngaun dito sa pina
@@armandouy3618 sa singiln sir diko familliar kc di nman ako nkgawa ng ganyn before tanong nlng natin sa iba din sensya n po
@@benzblogsVlogs pwede kaya singilin ko n lng ng 1,500 cya sir idol. sa rewiring ng smartgen at installation/ configuration
@@armandouy3618 pwedi naman ceguro
Please sir, which pin no in Cat ECM C15 is the nuzzle disable?
Injector disable? Or inable
@@benzblogsVlogs yes sir, injector enable.
@@egwuatuuwalaka6641 34 in 40pin connector for costumer side
@@benzblogsVlogs Thanks sir for your support, please is not for 40 pins, is for 70 pins.
Hi there, can u help with how to control the screen contrast ?
Which module
@@benzblogsVlogs hgm6110k
Sir pano po ikabit command switch ats to genset panel
Trough remote start every module have deferwnt config but im sure in the digital input but check in the config which in the digital input
Hello sir How to program the remote start dry contac hgm6120 and disconnect the mains remote start
Simple sir if u need remote go to digital input any of the stlots you can do the config as remoth start and just uncheck the amf so its not work during auto function
What is amf sir???
Sir need pa po ba ng laptop para madeactivate ung main contact
@@danilosoltura2840 yes
Try also module if posible some is not paosiblenin module
Hello sir benjie how to copy old configure of old module smartgen sir
Simply save bro
@@benzblogsVlogs salamat sir God bless you
Sir how to connect a command switch ats to genset
From ats search the remote start this is two wire but make sure dry contact not voltage out from ats side thin from the genrator module its in the digital input but you need to check in the config or in the tagging
Read what i told u
Hello, I urgently need your help. I have a DSE 6020mklll generator, currently configured for three-phase 400V. I want to change it to three-phase 230V. Please provide step-by-step guidance on how to confirm the changes on the DSE controller after modifying the starter connection to a delta connection. Additionally, please advise on how to configure the cooldown time after manually switching off the generator. Note: It's a 30kW 12 Leads generator.; I hope you can assist me here.