Hi.. Video is very nice & explained well... VFD is commonly for Pumps & Motors only ? or it can be used for other loads like Industrial heaters / Ovens etc..
Sir submersible pump abbacs550, use panrom,, three phase la perfect a run aaguthu,, two phase la water flow low a iruku, frequency 36mela pogamatenguthu,550v iruku,,, nanga use paneathu direct current,,, solar illa, direct three phase agriculture current, ,,two phase la niraya water flow aga vali sollunga,,, kvr i drive la connect panna mudiyuma
Unga drive ACS550 la 3 phase rectifier iruku neenga 3 phase voltage kudukum pothu unga DC voltagela ripples or oscillation romba kamiya irukum so motor full speedla oodum, neenga 2 phase kudutha DC voltagela fluctuation irukum so DC under voltage controller motor speedah limit panidum so practically not possible..1 phase conduct panalaina other 2 phases ku load adigam aidum so unga rectifier damage agavum chance iruku so it is limited in drive... input phase loss illana DC ripple faultla drive trip aaga chance iruku.. mostly in any VFD make it would be same.
Sari ok, frequency increase panna Motor oda Speed increase aaguthu ok( as Per formula N=120F/P). Indha Motor oda Speed increase Pandrom En, Edhukku, adhoda use enna?? Adha pathi Theliva oru video podunga
The choke is used for many reasons like compensating the cable capacitance, to increase the dv/dt etc.., in simple words it avoids the voltage spike incase of longer cable length for example more than 300 meters in ACS800-01,04 drives, the longer cable would have higher cable capacitance and the high frequency could cause voltage reflection at motor terminals due to the cable capacitance and inductance which could damage the motor insulation, also other way around for the motors with lower cable length also sometimes need choke to limit the voltage rise time to avoid damaging windings based on motor manufacturer specification, voltage rise time above 0.3 micro second would be ok for any form wound motors.
To avoid DC overvoltage the choppers are used, while decelerating the motor speed with very shorter ramp down time or while the load is driving the motor more than the set speed (synchronous speed) then the DC bus voltage would increase and the voltage would reach the over voltage fault limit or it may damage the component so brake chopper is used with the brake resistor to dissipate the extra DC energy as heat to maintain the DC voltage within the fault limit.
Vfd and soft starter both are same bro. Vfd use pani speed vary panalam. But soft starter only constant speed but smooth starting ivlodhan bro soft starter
Bro, This video is very useful for me. But I have a small doubt, for example, the motor is fed from VFD and VFD is fed from SWGR. THD value will be maintained in SWGR as per IEC. If THD value is exceeded, how to recover this? can we modify the change in VFD without replacement?
We can use 12 pulse bridge rectifier for reduction total harmonic distortion...we have maintained phase angle 30 degree for harmonic reduction...so we have to use converter transformer( converter duty transformer) it have one primary winding and two secondary windings...this is one of the important method for maintain harmonic
Input AC voltageah diode or thyristor rectifieroda rectification factor kuda multiply panina ungaluku DC voltage kedaikum which 1.35 times of the applied AC voltage eg.. 400*1.35 = 540V DC
If you take ABB VFD it has DTC Direct Torque Control which will take care of the torque demand of the application. or any VFD does produce the torque using the motor slip (load angle) margin by adjusting the stator voltage and frequency.
Generator Automatic voltage regulator(AVR) pathi oru video podunga bro.
THANKS FOR EXPLANATION
Bro your video very useful
Super explanation
Bro moter was struck then display current motor rpm or fixed rpm was displayed
good explanation
Sir power consumption in industry decrease pana enna pannanum solluga sir... Na new job poirukean manager power consumption kami pana sollraga
Hi.. Video is very nice & explained well... VFD is commonly for Pumps & Motors only ? or it can be used for other loads like Industrial heaters / Ovens etc..
Bro, Ac to dc convater la Ac voltage 440V input , output dc voltage evlo set pannu vaing ka bro
Sir doute motor name plate detail la pathan (allowable runing up time 100% un: 12s ,80% un:22s) poriyalla
Sir submersible pump abbacs550, use panrom,, three phase la perfect a run aaguthu,, two phase la water flow low a iruku, frequency 36mela pogamatenguthu,550v iruku,,, nanga use paneathu direct current,,, solar illa, direct three phase agriculture current, ,,two phase la niraya water flow aga vali sollunga,,, kvr i drive la connect panna mudiyuma
Unga drive ACS550 la 3 phase rectifier iruku neenga 3 phase voltage kudukum pothu unga DC voltagela ripples or oscillation romba kamiya irukum so motor full speedla oodum, neenga 2 phase kudutha DC voltagela fluctuation irukum so DC under voltage controller motor speedah limit panidum so practically not possible..1 phase conduct panalaina other 2 phases ku load adigam aidum so unga rectifier damage agavum chance iruku so it is limited in drive... input phase loss illana DC ripple faultla drive trip aaga chance iruku.. mostly in any VFD make it would be same.
Bro pls give clear definition and parameters setting video of atv310 VFD and lmx32ad servo drive Schindler electric
Please explain about V/f method ,scalar, DTC
Good well explained.I feel your speaking is fast.pl. be slow while explaining. Will helpful
Sir வணக்கம்
1 hp Singer phrase meter with vfd control யுடன் கிடைக்குமா? நல்ல brand எது என்ன விலை இருக்கும்
Hi sir i am working oman.i have vfd.ABB company 24 v. Now not working.some error .Come sir.A2 16 .MD VFD comm Error.what problem .Pls answer me sir
Sari ok, frequency increase panna Motor oda Speed increase aaguthu ok( as Per formula N=120F/P). Indha Motor oda Speed increase Pandrom En, Edhukku, adhoda use enna?? Adha pathi Theliva oru video podunga
Can I get vfd for 5hp.singale.phase electric motor
Sir abb vfd auto remote on off 0 to 20 ma on off video given sir
Singal pase low volt irukku sir anakku vft 2h motar ranpannanum India sollunga sir acreegalcher
Bro, what is the operating temperature?
Sir need vfd wiring connection and running video with demo ..need practical test
Bro capacitor bank working uploaded plz
Bro Please Explain AHF Working Principle
sir E-03 what complint
Can u explain ESP
Crompton emrton vfd fdu 48 control. Wireing sollukaga
Please post a video on oscillator to control frequency
Pls explain AVR (Generating to busbar connection)...
SIR PLEASE DO ONE VIDEO FOR SERVO DRIVE AND DC MOTOR SSD
Could you please explain solar pump vfd.
Ji,good morning, one dout 220 v power a 110v a mathamudiyuma.
Vfd not possible, you have to buy transformer step down the power input 220v output 110 ....follow this link th-cam.com/video/7qw9CSSf6OU/w-d-xo.html
If choke not used in output of vfd which creates any problems?
The choke is used for many reasons like compensating the cable capacitance, to increase the dv/dt etc.., in simple words it avoids the voltage spike incase of longer cable length for example more than 300 meters in ACS800-01,04 drives, the longer cable would have higher cable capacitance and the high frequency could cause voltage reflection at motor terminals due to the cable capacitance and inductance which could damage the motor insulation, also other way around for the motors with lower cable length also sometimes need choke to limit the voltage rise time to avoid damaging windings based on motor manufacturer specification, voltage rise time above 0.3 micro second would be ok for any form wound motors.
nitrogen injection fire protection system full video upload pls sir
Increment ramp decrement ramp na என்ன
Pls explain chopper why using,which purpose, working..
To avoid the ripples and fluctuations in DC voltage. Simple ah sona chopper will regulate the DC voltage and give constant voltage to the inverter
To avoid DC overvoltage the choppers are used, while decelerating the motor speed with very shorter ramp down time or while the load is driving the motor more than the set speed (synchronous speed) then the DC bus voltage would increase and the voltage would reach the over voltage fault limit or it may damage the component so brake chopper is used with the brake resistor to dissipate the extra DC energy as heat to maintain the DC voltage within the fault limit.
IGBT எங்க இருக்கும்?
Soft starters pathi video podunga nanba, thank you.
Vfd and soft starter both are same bro. Vfd use pani speed vary panalam. But soft starter only constant speed but smooth starting ivlodhan bro soft starter
@@shakthisaravanan26 thank you bro.
Super gee
Nanpaa intha model drivela on panna udane temperature high problem varuthu ithuku enna remedy pls sollunga nanpaa
Check the thermistor of vfd which is placed inside the vfd
There is an NTC which measures the IGBT heat sink temperature... may be NTC faulty illana temp measurement circuit faulty
Bro why we are using VFD for control the speed of induction motor......... other drivers is also there what is the reason bro.
Economy
Good
Where is the practical explanation, can u explanation driver circuits,commutation circuit ,control circuit for igbt
Where is the practical section ??? That's important
Practical season ah pakalam nu sonninga practical season enga?
Vfd not working auto mode. Hand mode only running. What happens. Pls tel me. It a very urgent.
1) REMOTE SELECTION NOT ACTIVE OR NOT ENABLED , 2) 4- 20ma ANALOG INPUT MAY BE OPEN .
Please check manual ,check parameter setting input terminal setting . Enable this setting
How to increase or decrease frequency
Plc la minimum 20hz apply panni trail edukalam
Download manual from internet as follow you using current vfd driver model . Set the parameter setting for increase or decrease can select points
Contactor patri sollunga
Vfd ethuku use Pandoram athan uses
Single phase input and three phase output VFD சொல்லுங்க நண்பா
Emrosn
ACS310, ACS355 ABB
Bro, This video is very useful for me. But I have a small doubt, for example, the motor is fed from VFD and VFD is fed from SWGR. THD value will be maintained in SWGR as per IEC. If THD value is exceeded, how to recover this? can we modify the change in VFD without replacement?
We can use 12 pulse bridge rectifier for reduction total harmonic distortion...we have maintained phase angle 30 degree for harmonic reduction...so we have to use converter transformer( converter duty transformer) it have one primary winding and two secondary windings...this is one of the important method for maintain harmonic
Yes whenever the input cycle increases atomatically hormanic will decrease
What propose bro
dc bus la high voltage varuthu,athu why.??????
Input AC voltageah diode or thyristor rectifieroda rectification factor kuda multiply panina ungaluku DC voltage kedaikum which 1.35 times of the applied AC voltage eg.. 400*1.35 = 540V DC
@@athish6716 oh okeyy thank you so much , understand 👍👍
Danfuss vld micro drive fc 51 external pot and rev fwd sollunga pls
Brother. frequency etha depend panni varried aaguthu .
Ex .: AHU starter. Vfd
Frequency is based on motor speed reference
Super BRO
என்னிடம் மூன்று டிரைவ் இருக்கு சர்விஸ் பன்னி தருவிங்கெ லா
How to increase vfd starting torque, how to put the settings
If you take ABB VFD it has DTC Direct Torque Control which will take care of the torque demand of the application. or any VFD does produce the torque using the motor slip (load angle) margin by adjusting the stator voltage and frequency.