महोदय जी आप इतने अच्छे से जानकारी दिये बहुत बहुत धन्यवाद, हमारे आश्रम मे एसी 1.5 टन, और 1hp मोटर ,दो फ्रीज हैं कौनसी Rccb लगाये कृपया जानकारी देने का कष्ट करे
Sir you have given us a wonderful information about RCCB by a beautiful class teaching. I got so many important facts about RCCB from your video. Thank you.
sir amazing explanation of this concept never anyone explained this type now please make a video of transformer stability video REF and SEF protection practically
Very informative. Thank you for sharing this valuable knowledge. I don’t know why RCCB in my single floor house is 63A 100mA. Should I change this to 30A
@@GKAgrawal2 No Sir, one that I know is 1HP submersible pump in boring and usual refrigerator, RO, TV, Fans in households. For some reason if 30A may trip would it be ok to go with 40A /100mA.
Pranaam sir, aapki har video se acchi information milta hei, kuch na kuch sikhne ko milta hei. ( sir ,ghar mein koi 30 mA - 25 Amp rccb use karta hei toh mcb kitna Amp ka use karna hoga???) Please boli ye ga sir.
Very nicely explain thank you sir i have faced one problem in one soft were office Falceling led light fixture fired shot circuit and flame came but no mcb was trips luckily we was their swith off the main supply fire controled immediately plz telme that what type of MCB we can use in this location...
बढ़ियाँ.. आज confusin दूर हुआ फिर भी एक प्रश्न है अगर series test lamp के दो point पकड़े तो rccb ट्रिप होगा? मतलब की जब मेरा शरीर bulb के series में रहेगा तब rccb ट्रिप होगा? धन्यवाद
नहीं नहीं सर मैंने series के दोनो लीड मेरे दोनो हाथ में पकड़ रखी है.. और current मेरे बॉडी से bulb में जा रहा है… लेकिन मेरा पैर धरती को कही भी टच नहीं होगा तो?
Sir, In your video Titled AC or DC which is more dangerous, you told us that for 50/60 Hz AC supply a typical value of 12 mA causes a female person to lose her ability to control the muscles. If that's the case then having 15 mA no trip threshold for RCCB won't protect the person. Please elaborate more on this.
There is time factor also to be considered. For how long we can afford shock without any jnjury, and how long breaker takes to trip. Read my article on "AC or DC, which Is more dangerous" for more detail in my website www.gkagrawal.com
Sir main line me RCCB lga hua hai , ek hi neutral hai aur inverter se ek main wire hai to inverter ke output me RCCB and MCB lga sakte hain? Please batlaye.
sir plz reply . i am install RCBO L&T C63 300ma COMPANY arond 3 kw load my house plz suggest me 300ma 63 amp safe for human shock or i am install 40 amp 30ma RCBO
सर अगर हमने Rccb को स्प्लिट ऐसी में लगाया और ऐसी को बॉडी में करंट लीक हो जाए और कोई इंसान काम करते वक्त बॉडी से चिपक गया तो क्या ऐसे समय में RCCB ट्रिप होकर इंसानी जान को बचाने में कारगर साबित होगा या नहीं, कृपया मार्गदर्शन करे
Sir ji mera doubt parallel operations of 2 generator pe h..... Maine kahi pe ye Padha h ki synchroscope ,synchronising switch k across connect hota h... ye Sahi h kya,,, or ye synchronising switch TPST switch h.....sir agar ye Sahi h to plz ye btao ki synchronising switch ya TPST switch ACB(air circuit breaker)me hota h kya.iska mtlb synchroscope ACB me connect hota h,,, plz reply sir
Sir mera ghar mei dp mcb 32A ka hai but uskei badd rccb laga hai jo ki 40A/100ma. Kya ampiear difference sei koi dikat hai or 100ma rcc sahi hai ya fir 40 ya 60 ma rccb sei change kardu
Sir iam worked in r&d department electrical. Main db having elcb 63amps 100ma . In one distribution mcb 15amps that connected two switch boards. Without connected equipments mcb on condition elcb tripped what happen leakage current crosses 100ma ? Please answer me
Mere Ghar me 2 fridge, 5 fan , 4 tube light ,7 9waat ke bulbs hai 2iron press hai 3 led TV 3 wotar Hiter hai to muje kitne MM Ka wire our kitne Ahmper ki MCB our Rccb lagani cahi ye
Membership
th-cam.com/channels/O31rZS4_EDYJ8CGXiRZdxg.htmljoin
Please aapka number dijiyega bahut argent...sir....ji
Nice video sir ....
हम इसी व्हिडीओ के प्रतिक्षा में थे ।
धन्यवाद सर.....
Thank you so much sir mujhe iss knowledge ki shakht jarurat thi
महोदय जी आप इतने अच्छे से जानकारी दिये बहुत बहुत धन्यवाद, हमारे आश्रम मे एसी 1.5 टन, और 1hp मोटर ,दो फ्रीज हैं कौनसी Rccb लगाये कृपया जानकारी देने का कष्ट करे
25Amps, 30mA wala.
Amazing knowledge sir I have 10+ year Experience in electrical industries but you are my best teacher for electrical engineering
Good that you found my video useful.
Sir ghr me kitne. Amp ki aur kitne ma ki rccb pryog kre
Dhanyawaad achchhi jankari ke liye aur namaskar.
नमस्कार
Sir, You expained so nicely!!!👌👌👌💐💐💐Many thanks for solving my query.
Hii sir me apke sare video dekhta hu bahut achha padhate ho sir app. thank You 🙏imp Theory padhne ke liye
Very good, apki knowledge avashya badegi.
Nice video aap bahut acha samjhate h
Sir you have given us a wonderful information about RCCB by a beautiful class teaching. I got so many important facts about RCCB from your video.
Thank you.
sir amazing explanation of this concept never anyone explained this type now please make a video of transformer stability video REF and SEF protection practically
Sir, your teaching style is always great 👍
Bhut achcha chacha ji
बढिया जानकारी
Sirji pranam,
Your videos are truly inspiring.
Is there a difference between RCCB and ELCB???
Or is their working principle the same???
Thanks sirji.
Very exclusive information in this video on the RCCB selection
Very informative. Thank you for sharing this valuable knowledge. I don’t know why RCCB in my single floor house is 63A 100mA. Should I change this to 30A
30mA is better. But your RCCB is 63A, do you have such heavy loads.
@@GKAgrawal2 No Sir, one that I know is 1HP submersible pump in boring and usual refrigerator, RO, TV, Fans in households. For some reason if 30A may trip would it be ok to go with 40A /100mA.
Pranaam sir, aapki har video se acchi information milta hei, kuch na kuch sikhne ko milta hei. ( sir ,ghar mein koi 30 mA - 25 Amp rccb use karta hei toh mcb kitna Amp ka use karna hoga???) Please boli ye ga sir.
Yeh tho load per hai, but 25A sey jyada ka na hona chiyey.
@@GKAgrawal2 rccb jitna amp ka hoga utna hi amp ka mcb lagega???
Given great Gyan
Bahut achha se batahe hai sir
Very informative video. Your way of explaining is superb. I slute you.
Nice explanation
In residence(4kw).... Which rrccb safe...
Thanks sir for good knowledge.
Lot's of thank you sir
Pranam 🙏
Sir, Thank you for one of the best explanation in selecting RCCB.
But I have question which one to choose 40A or 63A
Depend upon load current.
@@GKAgrawal2 sir mein 3kw use hota hay toh kitnay amp ka rccb lgana chahiye btaye pls
Namastey sir. Grateful to you for your teaching. Can you please suggest a most reliable model tried and tested by you.
What you mean by model
Very nicely explain thank you sir i have faced one problem in one soft were office Falceling led light fixture fired shot circuit and flame came but no mcb was trips luckily we was their swith off the main supply fire controled immediately plz telme that what type of MCB we can use in this location...
Watch my video on AFDD breaker for arc sensing and fire protection
You can provide small rating normal MCB for every room.
Very Super
Excellent and very helpful explanation. Thank you
बढ़ियाँ.. आज confusin दूर हुआ
फिर भी एक प्रश्न है
अगर series test lamp के दो point पकड़े तो rccb ट्रिप होगा?
मतलब की जब मेरा शरीर bulb के series में रहेगा तब rccb ट्रिप होगा?
धन्यवाद
हाँ , कयोंकि पैर थरती को छुयेगा ।
नहीं नहीं सर
मैंने series के दोनो लीड मेरे दोनो हाथ में पकड़ रखी है.. और current मेरे बॉडी से bulb में जा रहा है… लेकिन मेरा पैर
धरती को कही भी टच नहीं होगा तो?
Sir,nice your electrical. Video..milliampiear kya hota hai. Ples. Batao sir.
I was looking for such a great video thanks sir
Feel happy that, you got necessary information in my video.
Sir great learn with you.sir please make a vedio on electrical standards.
Sir ager incomer.300ma hai output mai 30ma rcb hai.ager earth leakage.hota to.phelay kaunsa.trip hoga.thank a lot.aap ke jawab ka mujhe intejar rahega
Sir maine 100 mh 25Amp rccb Gharme lagaya sahi hai ya galat plz. Ans. Me thank u
Thanks sir . Sir ek bat puchni thi aap se .
Rccb main types hote hai .
A, AC , in main se home k liye kon sa sehi hai .
Thanks for information about your experience.
धन्यवाद 🙏🙏
Nice...
Sir, In your video Titled AC or DC which is more dangerous, you told us that for 50/60 Hz AC supply a typical value of 12 mA causes a female person to lose her ability to control the muscles. If that's the case then having 15 mA no trip threshold for RCCB won't protect the person. Please elaborate more on this.
There is time factor also to be considered. For how long we can afford shock without any jnjury, and how long breaker takes to trip. Read my article on "AC or DC, which Is more dangerous" for more detail in my website www.gkagrawal.com
Thankyou sir. Your video was really helpful.
Also, You may not get this kind of information easly
mst video sir ji
Good information
Good explanation
Great knowledge
It's very good
बहुत दिन से एसा ही कुछ ढूंढ रहा था
Very nice 🔥🔥🔥
Very good video
Great knowledge sir
Very nice
Sir RCCB lagane Ka Sequence Batao Detail Video me..,
Aur advantage & Disadvantage Bhi Batao
Watch my all other videos on RCCB
Sir please prepare a video in microprocessor release setting method of any air circuit breaker ( ACB) ? I think you will do . Thanks a lot .
Thak u sir u gave best knowledge.....
good teaching
Sir inverter ki output se lekage hoga to usame rccb use kr sakte hai kya
Please btaye ya 1 video bnaye
Great Sir
This has exclusive information.
Sir main line me RCCB lga hua hai , ek hi neutral hai aur inverter se ek main wire hai to inverter ke output me RCCB and MCB lga sakte hain? Please batlaye.
Sir,
Hotel use, Penal board(bus bar) se separate wire gaya hai only for geyser(2kw or 2000w) k lie, isme kitna mA ka rccb lagau.
Great sir...
Gharo mai Kitne RCCB use krna chaahiye....
Aur uke connection kaise hone chahiye......?????????
Please reply
Very good sir
sir hme ghr m sari msb 16 ki 7 lgi hui h to kitne amp ki mcb lgay 30 mili to ho gya or amp kitna lgaay 32 ya 40
Sir 200 mamp ke load ke liye kitne amp ki MCB ya rccb use kar sakte h
200 milli amp load hote hi rccb trip ho jaye please tell me sir
Sir plz inform mee 1000 waat load '30mA' lagaye.?? Meri House mee.???
Super ❤️ babaji
Nice video sir
Sir aap jenius ho
Sir, is there any need of earthing when we are using RCCB in building? Can we avoid the use of earthing as it increases the overall cost of wire?
Earthing must
sir plz reply . i am install RCBO L&T C63 300ma COMPANY arond 3 kw load my house plz suggest me 300ma 63 amp safe for human shock or i am install 40 amp 30ma RCBO
Good teaching method
Really good 🙏🙏
I going depth into ground leakage current increase or decrease?
Please explain, sir
Sir kya hum 1ho ki summersible me rccb ka istemal kar sakte hai?
great video sir
सर अगर हमने Rccb को स्प्लिट ऐसी में लगाया और ऐसी को बॉडी में करंट लीक हो जाए और कोई इंसान काम करते वक्त बॉडी से चिपक गया तो क्या ऐसे समय में RCCB ट्रिप होकर इंसानी जान को बचाने में कारगर साबित होगा या नहीं, कृपया मार्गदर्शन करे
thanks great effort.
Sir 30 mA wali RCCB m agar residual current bd jaye 30 mA se upper ho jaye to RCCB trip hoga ya nhi???
Trip hoga. Mera video RCCB breaker in Hindi dekho.
Rccb lgata hon to kya main Mcb lgana hai ya nahi?
Taau tusi great ho 😆
Sir ji mera doubt parallel operations of 2 generator pe h..... Maine kahi pe ye Padha h ki synchroscope ,synchronising switch k across connect hota h... ye Sahi h kya,,, or ye synchronising switch TPST switch h.....sir agar ye Sahi h to plz ye btao ki synchronising switch ya TPST switch ACB(air circuit breaker)me hota h kya.iska mtlb synchroscope ACB me connect hota h,,, plz reply sir
Sir kya pure ghar me ek rccb lagega ya har room ke bord me !
Sir mera ghar mei dp mcb 32A ka hai but uskei badd rccb laga hai jo ki 40A/100ma. Kya ampiear difference sei koi dikat hai or 100ma rcc sahi hai ya fir 40 ya 60 ma rccb sei change kardu
40A ki koi dikkat nahi, RCCB 30mA ka hona chahiye.
Ghar me invater single wire se wiring kiya hua hai to wanha rccb lagane se main our invater ka load chalega
Whether 500 ma is safer or 50ma?
सर घर के लिए 10ka 30ma रेटिंग वाला RCCB वर्क नही किया करंट लगने के बाद भी,,,
रीज़न बताइये,,,,,क्या ये ज्यादा रेटिंग वाला था कि कुछ और कारण।।
करंट 30 मिली एंपियर से कम होगी
Thanks
Rccb 30amp ka lagaye mcb kitna amp ka Laguna chahiye sir total watt 500 ho toh
सर.वाटर हीटर के लिये लगा सकते है क्या
Hamse puchha gaya ki RCCB ka Triping current kitna hota hai..
Sir answer koga...
30mA type RCCB key liye 30mA leakage current hi tripping current.
@@GKAgrawal2 thanks...
Sir 7.5hp 3 phase motor ke liye kitne ampere ka rccb lgaye plzz Rply me sir
Sir iam worked in r&d department electrical. Main db having elcb 63amps 100ma . In one distribution mcb 15amps that connected two switch boards. Without connected equipments mcb on condition elcb tripped what happen leakage current crosses 100ma ? Please answer me
One possibility is that switch boards have problems like dust, moisture, cut wire etc
Sir meter to- 32A MCB, 30A RCCB to split AC to house canect , right sir bataye
32amp mcb me rccb 30ampr lga skate h sir
Mere Ghar me 2 fridge, 5 fan , 4 tube light ,7 9waat ke bulbs hai 2iron press hai 3 led TV 3 wotar Hiter hai to muje kitne MM Ka wire our kitne Ahmper ki MCB our Rccb lagani cahi ye
Sir geyser 3kw use kartha hu instant geyser jo hay
Ushmay kitnay amp ka rccb lgana hoga btaye pls
Sir what is the maximum allowable current flow through human body
Watch my exclusive video on AC or DC which is more dangerous. You will get the answer.
Mere ghar main l∆n 0.03 hai sir vo bahot trip hoti hain to 30 ml ka ripless karde kya
Koi equipment ghar kaa kharab hai. Shayad water heater. Ek, ek karkey sab equipment off karkey dekho
👍👌
Hello sir, agar 16 amp rated rccb mein se 20 amp current flow karenge tab kya hoga. Please bataye
RCCB ke contacts burn ho saktey hai.
@@GKAgrawal2 ok sir
हमारे घर में 2 कुलर ,फ्रिज, 4 सिलिंग फेन,6 लीटर का गीजर तथा 1hp की मोटर है तो हमें कितने एम्पियर वाला लगाना चाहिए
25 ampere ka rccb