I noticed that for transition you only add the largest size (width) and ignore the other (small one) & Even though there is `from fan` symbol on the template, you calculate it the other way around. how does the program consider and calculate it?
Please watch it again, i have already put the small and large side values, the fan is not a part of ESP calculation. Equipment is a part of total static pressure.
@@passionateengineer04 you misunderstood my question. when you calculate the first transition, you did not enter 24" (width) anywhere. you only entered the heights and width of the one of ducts.
Is there any way we can view the tabular value of the fittings from the software? I couldnt find the pdf versions of various fitting values presented in tables. (the ones i found is not as complete as the ones in the ashrae dfdb software) also, i didnt see the link to download it. Are you using the original one or the cracked version. Thanks in advance!
This is so useful. Thanks for this video-
Greetings from Colombia
Very informative videos.Thanks for sharing ur knowledge. Can u kindly share Esp excel sheet .
Please check the video description
Hi, thanks for the video! May i request for the link to the software? Thanks in advance!
please check video description
Thank you
THANK YOU
I noticed that for transition you only add the largest size (width) and ignore the other (small one) & Even though there is `from fan` symbol on the template, you calculate it the other way around. how does the program consider and calculate it?
Please watch it again, i have already put the small and large side values, the fan is not a part of ESP calculation. Equipment is a part of total static pressure.
@@passionateengineer04 you misunderstood my question. when you calculate the first transition, you did not enter 24" (width) anywhere. you only entered the heights and width of the one of ducts.
Hi dear for shoe neck side for duct branh how canculate n data base which fitting
Check transitions
I have a question the translation should have different hight size , coz am trying with the some size then boom an error
Transition have two different sizes smaller and bigger
Is there any way we can view the tabular value of the fittings from the software? I couldnt find the pdf versions of various fitting values presented in tables. (the ones i found is not as complete as the ones in the ashrae dfdb software) also, i didnt see the link to download it. Are you using the original one or the cracked version. Thanks in advance!
These all values are available in ASHRAE handbook.
This software is not crack one.
i can`t calculate the pressure loss, the software shows the message "possible input error" do you know how to fix it?
Run as administrator.
Thanks a lot. Please share the software link
please check video description
Thank you
You didn’t consider grille pressure drop that will come around 10-20 pa
tanx a lot for this piece
Can you share me where to download this for laptop
I will upload it on my website and will share link soon.
Thank you
Please share thank u@@passionateengineer04
how to change unit in ip to si in software
You can download the SI version.
Click on Utilities a small dialogue box(preferences)will appear, then click on units
can u please share the link to download the software
Share your email, i will send you.
please share the Ashre data base link
please check video description
Thank you
Why you are wasting time in converting mm to inches go to setting n units and change it ...........................
Pathetic, max time used in converting mm to inches.
Can you please elaborate?
could you please share the link of this software?
Ok i will share