ไม่สามารถเล่นวิดีโอนี้
ขออภัยในความไม่สะดวก

High Ampere ACU Compressor.Cause and Effect (#28)

แชร์
ฝัง
  • เผยแพร่เมื่อ 19 ก.ค. 2020
  • Tutorial.Finding Troubles.Window type

ความคิดเห็น • 81

  • @ferdc8775
    @ferdc8775 4 ปีที่แล้ว +2

    sir thanks for your clear step by step tutorial

    • @jhaybizz
      @jhaybizz  3 ปีที่แล้ว

      Thx din po sir fer dc

  • @andresvargas8306
    @andresvargas8306 3 ปีที่แล้ว +1

    Sir jay magaling ka magturo maliwanag good job sir

  • @allanpalad2159
    @allanpalad2159 4 ปีที่แล้ว +1

    maraming salamat master lodi the best ka talaga...

  • @jonnabersano3972
    @jonnabersano3972 4 ปีที่แล้ว +1

    lupet mo talaga sir jay 👏👏👏

  • @ronansumo9743
    @ronansumo9743 4 ปีที่แล้ว +1

    New subscriber nyo po,ang gusto ko sa channel na ito mas malalim ang mga troubleshooting.
    Question:
    1.Ano po dahilan bakit pumupunta oil ng compressor sa evaporator or condenser.
    2.Gaano po karami coil cleanser
    dapat ilagay sa evaporator &
    condenser.
    Thanks

    • @jhaybizz
      @jhaybizz  4 ปีที่แล้ว +1

      Gd day sir ronan sumo. Tnx po sa pag visit.
      About sa tanon nyopo sir?
      Nag kakaron ng oil ang condenser at evaporator, depende po sa tagal ng paggamit ng unit. Sa katagalan paunti inti na pa pump ng compressor ang oil nya paglipas ng taon....then further years (7-15years) pumping oil na talaga sya dahil luma na compressor
      Yung dami naman po ng 141b. Depende po sa laki ng evaporator at condenser. Pero if sa window na 1.5 hp mga 30 ml. And then pressure ng air na pang flush ay 300psig.
      If nitrogen gamit nyo po mas high ang pressure nyan kaya mas ok

    • @ronansumo9743
      @ronansumo9743 4 ปีที่แล้ว +1

      @@jhaybizz thank you,may isa pa pala ako question.
      1.Paano ko malalaman ang tamang
      quantity ng oil na ilalagay ko sa
      isang compressor.
      Thanks sa malinaw mo na explanation.God bless you channel.

    • @jhaybizz
      @jhaybizz  4 ปีที่แล้ว +1

      Hello po sir ronan susukatin po yan 100-120ml

  • @allanpalad2159
    @allanpalad2159 4 ปีที่แล้ว +1

    di ka maramot master

  • @jadztv6192
    @jadztv6192 4 ปีที่แล้ว +2

    Natawa hahahaha unique nga bro un compressor first time ko makakita ng ganyan,bro mag kano singilan pag ganyan trabaho system reprocess?

    • @jhaybizz
      @jhaybizz  4 ปีที่แล้ว +1

      hello po sir huwes
      para naman maiba, puede nyo ring gawin,pero more effort at may additional cost. and if papayag din may ari sa style natin😁.

  • @garyden14
    @garyden14 4 ปีที่แล้ว +1

    Sir una sa lahat Thanks sa mga tutorial mo loud n clear ask ko lang po yung service valve mas mganda ba di na tanggalin or kung dpat tanggalin pra di mag leak at pno po tanggalin yan pag may freon na pwede ba ipitin ng vise crip at putulin service valve tpos hihinangin di ba delikado mag himang kung may freon TY.

    • @jhaybizz
      @jhaybizz  4 ปีที่แล้ว

      gd day po sir garyden. tnx po sa pag visit
      about sir sa access valve(service valve). depende po sa technicians kung aalisin nya at gagamit siya ng pinch off.pero di yan mag le leak depende sa stratedy ng technician
      And dipo vice grip ang ginagamit. kasi hindi ma so solder dahil may leak pag yan ang ginamit. dapat pinch off. Parang vice grip pero pabilog na pahaba ang pinaka ngipin nya.
      dipo delikado maghinang basta r22 at r410 ang refrigerant.

  • @yulbrioflorido9516
    @yulbrioflorido9516 4 ปีที่แล้ว +1

    Sir bka pde gawan m ng video pg gawa mo ng airtank para mgka idea nmn kme

    • @jhaybizz
      @jhaybizz  4 ปีที่แล้ว

      ahh try po namin

  • @andresvargas8306
    @andresvargas8306 3 ปีที่แล้ว +1

    May data b dyan para s exact filling of oil for every horsepower of compressor
    Very thanks sir

    • @jhaybizz
      @jhaybizz  5 หลายเดือนก่อน

      Para matantiya sir alisin ang old oil ilagay sa cup then kung ano yung naalis yun din ang ibalik na langis na same amount pero bago capella oil

  • @darkseer7027
    @darkseer7027 3 ปีที่แล้ว +1

    pagawa nga ng aircon ko hahahah

  • @andresvargas8306
    @andresvargas8306 3 ปีที่แล้ว +1

    Sir ask ko uli sir paano malaman Kong kulang ang paglagay mo ng capella oil s compressor nasa Specs .ba yan sir

  • @chunksvlogs4244
    @chunksvlogs4244 3 ปีที่แล้ว +1

    Boss good day.. tanong ko lang po kung normal lang po ba ang paginit ng compressor? Nagpalit po Kc ako ng cApacitor kc lumobo. Ngayon po umaandar n kaso umiinit po yung compressor

  • @elmerromero7556
    @elmerromero7556 4 ปีที่แล้ว +1

    Tanong ko lang po,Master .. baguhan lang ako sa R.A.C ..
    Ano po ba ang tama ? Saan po ba dapat ipasok ang oil na ipapalit sa compressor ? Kc yung isang video na napanood ko po sa DISCHARGE nya po ipinasok yung bagong oil kc kung sa SUCTION daw po ipapasok yung oil ay di daw po papasok lahat sa compressor ? Ano po ba talaga ang tama po ?
    Wag nyo po sana masamain ang tanong ko po,Master nais ko lang po malaman kung ano po ang tamang proseso sa pagpalit po ng oil ng compressor

    • @jhaybizz
      @jhaybizz  4 ปีที่แล้ว

      gd am sir elmer. tnx for visiting.
      about sir kung paano maglagay ng capella oil sa compressor. suction po dahil pag sa discharge parang mahirap dahil di nyo agad mailalagay dahil palabas po yan may mga valve na madadaan . unlike sa suction dercho sa ilalim ng compressor
      dapat naka on ang compressor para ma suck nya ang oil na ipapasok natin

  • @ahlsoriano5555
    @ahlsoriano5555 5 หลายเดือนก่อน +1

    ba na Sobrang init ng Compressor kahit na ilangWELCOME Segundo lng namamatay na?
    Pinalitan ko na Capacitor ganon pa rin On / Off pa rin at Sobrang init ng Compresor

    • @jhaybizz
      @jhaybizz  5 หลายเดือนก่อน

      Sir compressor sira

  • @imbaTV-tech
    @imbaTV-tech ปีที่แล้ว +1

    Sir pag ganyan po sir nasa evaporator at nasa condenser ang mga oil..iinit po ba ang compressor sir at nag ha high amper?

    • @jhaybizz
      @jhaybizz  ปีที่แล้ว

      Dpende sa tagal ng unit Hindi naman sir iinit kung 3 years palang, magyeyelo lang siya at hihina ang lamig.
      Pero kung matagal na ang unit mga 10 years at hindi na reprocess, tapos nag high ampere ang compressor, ibig sabihin paubos na ang langis ng compressor nag pump na siya ng oil sa katagalan

  • @ahlsoriano5555
    @ahlsoriano5555 5 หลายเดือนก่อน +1

    Sir..natural lng ba na Sobrang init ng Compressor kahit na ilangba na Sobrang init ng Compressor kahit na ilangWELCOME Segundo lng namamatay na?
    Pinalitan ko na Capacitor ganon pa rin On / Off pa rin at Sobrang init ng Compresor Segundo lng namamatay na?
    Pinalitan ko na Capacitor ganon pa rin On / Off pa rin at Sobrang init ng Compresor.
    D kaya Sira ang OLP?

    • @jhaybizz
      @jhaybizz  5 หลายเดือนก่อน

      Possible sir stuck up na compressor niyo kasinseconds lang patay na agad siya

  • @andresvargas8306
    @andresvargas8306 3 ปีที่แล้ว +1

    Depende po ba yan sa horsepower ng compressor para sa pagpapalit ng oil o tatantiyahin na lang ang paglagay

    • @jhaybizz
      @jhaybizz  3 ปีที่แล้ว

      Tama po depende sa horse power... Na send ko napo kung ilang ml
      Pero dapat po walag oil ang compressor or inalis nyo ang oil...or said ang oil sa loob bago nyo salinan ng 400ml para sa pang 1hp na compressor

  • @alexsup5237
    @alexsup5237 3 ปีที่แล้ว +1

    Sir sa refrgerator ang rated amp. Nya ay 1.9 e wala pang freon ang rated ay 1.5 may posibilidad na sira na ang compressor.

    • @jhaybizz
      @jhaybizz  3 ปีที่แล้ว

      Gd day po Sir Alex,sorry po sa late reply, thanks po sa pag visit
      If mataas po ang current kahit wala pang lamang refrigerant, kahit naka dismantle na siya, or kahit nagpalit na kayu ng OLP ......may problem napo ang compressor nyan...need na po ng repair or replacement.kasi dinapo mag no normal ang operation pag ginamit pa
      Sir Alex if sakali man po if ok lang sa inyo...sa push nalng po ng SUBSCRIBE BOTTON para po ma update lagi kayu sa mga new video.thx po

  • @reynaldoguimbaolibot2521
    @reynaldoguimbaolibot2521 3 ปีที่แล้ว +1

    Boss Jhay anu ba ibig sabihin ng 141b?
    Salamat din sa mga tips mo....
    Goodblesss!!!

    • @jhaybizz
      @jhaybizz  3 ปีที่แล้ว

      thx sir reynaldo sa pag visit at sa question
      HCFC -141b is a flushing agent sir. yung 141b ay "hydrochlorofluorocarbon". pareho sila ng chemistry ng 134a.
      And Refrigerant din siya.gas solvent (pantunaw ng clog oil)
      C2H3Cl2F ang chemical formula nya
      kalinya nya ang r11 na dating flushing agent na ginagamit ng mga tatay natin dati na mga acu technicians din

    • @jhaybizz
      @jhaybizz  3 ปีที่แล้ว

      salamat po tlaga sir rey. and makisuyo nalng po if di nyo pa napindot yung "pulang salita" sa baba sa kanan. pa pindot nalang po sana
      and watch my other video rin po

  • @andresvargas8306
    @andresvargas8306 3 ปีที่แล้ว +1

    Sir ilang Psi ba ng air o hangin ang dapat ipasok sa evaporator at condenser pang tulak sa 141b
    Thank you

    • @jhaybizz
      @jhaybizz  3 ปีที่แล้ว

      Gd day po sir andres...thx po sa pag visit
      Usually 300 psi ok npo pang flush pag window type
      Sa split naman po ok na din ang 300psi sa 10 ft copper tube sa kasama ang evaporator

    • @andresvargas8306
      @andresvargas8306 3 ปีที่แล้ว

      Salamat master additional info

  • @rodrigoclacer9441
    @rodrigoclacer9441 3 ปีที่แล้ว +1

    Sir hnd hnd mo pinakita kung paano mo inalis Ang capella oil sa compressor

  • @noelparas1542
    @noelparas1542 2 ปีที่แล้ว

    master ano po kaya posibleng naging problema newly tech lang po ako. kasi po nagcharging ako ng Refrigirant r22 po 1hp po nag aircon. ginawa ko naman po anh process. kasi po pinalitan ko lang access valve yong existing access valve. after ko nakargahan ayon po nagyelo pag mga 10mins. may lamig naman po. kung ang rates amps po ba is 4.30amps. pwede po ba mag exceed ng mga 5amps. 4.7amps po. kasi po nasa open area during running salamat po sana po matulungan ninyo ako

    • @jhaybizz
      @jhaybizz  2 ปีที่แล้ว

      Sir Noel, Kung nag vacuum naman kayu ng mga 20 mins. Bago kayu mag charge, tama ginawa nyo sir
      Pero kung ang unit ay morethan 3 years i flushing nyo use of 141b + nitrogen or air pressure. Pag hindi nyo na flush at mau clog oil.magyeyelo tlaga yan sir,,, at meron pang worsh scenario yung magyeyelo siya after several hours

  • @roelirasusta5744
    @roelirasusta5744 2 ปีที่แล้ว

    Sir nagtitrip po b pagganyan ang sira??salamat more power

    • @jhaybizz
      @jhaybizz  2 ปีที่แล้ว

      Yes sir Roel kasi clog ang condenser saka capillary tube, mag ha high ampere then trip ang olp

  • @lynlaguidao7559
    @lynlaguidao7559 2 ปีที่แล้ว

    Boss saan po ba mkakabili ng tangke mu na ginagamit nyo po jan. Pang flashing.. Salamat po..

    • @jhaybizz
      @jhaybizz  2 ปีที่แล้ว

      Gd day Mam/Sir Lyn, sa refrigeration suplier po, take note 300 pai lang po ilgay nyo na air, para safe

  • @djglory9096
    @djglory9096 3 ปีที่แล้ว

    Sir paano po kaya ung aircon ko may buzzer sound na malakas bago mag bukas ung compressor nakakabulabog minsan ano kaya dahilan pag mag buzzer sound siya minsan ilang beses bago umandar compresssor sabay humihina pati ilaw namin sa bahay ppag nag buZzer siya salamat

    • @jhaybizz
      @jhaybizz  3 ปีที่แล้ว

      Hello po sir/mam Dj... Isang cost po bakit ayaw mag start ang compressor...possible open,low capacitance or open na capacitance ng Capacitor
      If napalitan npo ng caPacitor, compressor pero may problem pa rin..malapit napong ma knock out ang compressor (dahil sa mechanical problem inside)
      Mam/sir... If dipa po kayu naka subscribe...baka puede po makisuyo if ok lang po, para updated kayo sa new video ko tnx po

  • @dionnesantiago9597
    @dionnesantiago9597 3 ปีที่แล้ว +1

    sir? anong ihig sabihin ng LRA 13? or meaning nya?

    • @jhaybizz
      @jhaybizz  3 ปีที่แล้ว

      Gd day po sir Dionne Santiago. Tnx for visiting sir sa channel
      About po sa meaning ng LRA...(Lock Rotor Ampere)
      Yung 13 ay maximum ampere ng compressor kapag nag ra run , hindi na dapat lumagpas sa 13 (LOCK ROTOR AMPERE 13)
      EX: from normal current na 2.5 pag may load ng refrigerant to 13 amps lang
      kapag tumaas pa sa 13 ang ampere let say 14 above.... hindi na mag ra run ang compressor pag ganyan
      Kaya nag ha hum.
      Ang situation sa loob ay nag lock na ang rotor or nag stuck up na ang rotor sa loob ng compressor ( means ayaw umandar)
      Pag ganyan po palit capacitor or kung dina makuha sa capacitor palit na ng compressor.

    • @dionnesantiago9597
      @dionnesantiago9597 3 ปีที่แล้ว

      @@jhaybizz ok sir! salamat sa paliwanag at nakuha ko ibig sabihin ng LRA 13? God Bless you sir JBzz.

  • @alexeder6666
    @alexeder6666 2 ปีที่แล้ว

    ok lang po ba na sa r22 system ang nakalagay na refrigirant is r410a?

    • @jhaybizz
      @jhaybizz  2 ปีที่แล้ว

      Hello po sir alex. Hindi po pued pag r410 tapos rR22 ang ilalagay na refrigerant.
      Magkaiba po sila ng mixture at pressure. Masisira po compressor nyo
      Ang running pressure ng r410 ay 130 ang r22 ay 70
      Malayo sir ang interval nila

  • @andresvargas8306
    @andresvargas8306 3 ปีที่แล้ว +1

    Sir ask ko lang po about compressor
    Mapa refrigerator o window type aircon po kung sakaling pumping oil na Ang compressor mapa refregirator o aircon dahil mabawasan n ng oil paano po malalaman kung ilang ml ba na oil ang isasalin n bago
    Salamat. Sir meron b kayong data para dyan
    Thank you maestro

    • @jhaybizz
      @jhaybizz  3 ปีที่แล้ว

      Yes sir para sa compressor na pang
      1hp. 400ml
      1.5hp 500ml
      2hp 600ml

    • @andresvargas8306
      @andresvargas8306 3 ปีที่แล้ว

      Thank you sir for response

  • @emmanuelsegunto5507
    @emmanuelsegunto5507 3 ปีที่แล้ว

    Sir pag on ko ng ac mataas ang amper umaabot ng 11 amper then after compressor klick bumababa naman 0.2 ang amper nya ok lang ba to

    • @jhaybizz
      @jhaybizz  3 ปีที่แล้ว

      Gd day sir emmanuel..thx po sa question...if 1 hp or 1.5 hp ang unit. Abnormal po if ma reach nya ang 11 amps. "High ampere" po yan (0.2 amps naka off ang compressor fan lang sir ang running)
      Yung click po na naririnig nyo ay o.l.p nag ka cut sya for protection
      trouble found (possible)
      1)lock of oil sa compressor
      2)dirty unit (condenser)
      3)o.l.p problem
      Sir Emmanuel if dipa po kayu naka subscribe, push nyo nalang po Subscribe botton also notification bell then select all...para updated po kayo sa mga latest video ko... 😁

  • @darioramosjr1986
    @darioramosjr1986 4 ปีที่แล้ว +1

    Master anu po standard ng pag charging ng r22 r410a at r134a? Meron po kasi iba naka raob meron po ina alog alog.salamat po

    • @jhaybizz
      @jhaybizz  4 ปีที่แล้ว +1

      Yes po sir Roida Ramos, tnx po sa pay visit nyo sa channel na ito
      Eto po kasi ang proseso na sinusunod... Ang Ginagawa ng iba ay i charge ang gas sa suction (vapor charging) na dapat naka tayo ang ang tangke para gas ang lalabas sa tangke hindi liquid, pero time consuming, dahil may mga dapat pang i consider sa unit
      Pag sa high side naman sir mag cha charge.....yun ay liquid charge , pero dapat nakapatay ang unit kasi di kasi papasok ang liquid refrigerant pag naka on ang unit
      kaya ang alternative procedure ay mag charge sa suction line habang naka on....tapos liquid charge. nakatiwarik ang tangke(nasa ilalim ang valve )
      Matagal napo n procedure yon na ginagawa ng marami
      Yun pong ina alog naman,tula n sabi nyo, ay para lang malaman kung may laman pa tangke ang freon.

    • @jhaybizz
      @jhaybizz  4 ปีที่แล้ว +1

      Sorry sir diko naisama standard psig pag may laman ang unit(kaya eto na sir pahabol)
      R410 Suction 110-120 psig
      Dischrage
      R22 Suction 60-70 psig
      Discharge 250-300 psig
      R410 (ref) Suction 10-15 psig
      Discharge 125-150 psig

  • @rodrigoclacer9441
    @rodrigoclacer9441 3 ปีที่แล้ว

    Sir,hnd mo pinakita king San mo pinadaan Ang langis sa discharge ba o sa suction?

    • @rodrigoclacer9441
      @rodrigoclacer9441 3 ปีที่แล้ว

      Sa pag alis ng langis sa compressor.

    • @jhaybizz
      @jhaybizz  3 ปีที่แล้ว

      Sensya na sir diko nasama... Pero sa discharge line po papadaanin... ititiwarik nyopo then after 1 min tutulo na siya. Stay nyo lang po 15 mins makatiwarin para maubos lahat
      ....then yung pinagpalitan i pi filter then yung kalahati ipapahigop nyo (if hindi pa itim amg kulay) kasama ng bagong capella

  • @allanpalad2159
    @allanpalad2159 4 ปีที่แล้ว +1

    master add ko lang yung evaporator ng ref namin nilagyan ko naman 141b wala lumabas na na nilagay ko 141b sa kabilang cappillary niya. salamat in advance master

    • @jhaybizz
      @jhaybizz  4 ปีที่แล้ว

      hello sir allan gd am
      sir maraming case na di natin namamalayan. yung isang end ng capillary natin maaring nalagyan ng silver rod ng mag solder tayu, kaya bumara at walang mailalabas na rerigerant sa kabilang dulo. or maaring clog parin, better po na palitan nalang ng bagong capillary.

    • @allanpalad2159
      @allanpalad2159 4 ปีที่แล้ว

      @@jhaybizz may hangin po lumalabas sa capillary master

    • @allanpalad2159
      @allanpalad2159 4 ปีที่แล้ว

      @@jhaybizz kaso yung nilagay kong 141b di lumabas

    • @jhaybizz
      @jhaybizz  4 ปีที่แล้ว +1

      Ok po sir allan.if nilagan nyo ng 141b ang capillary at hangin lang mg lumaabas, possible na problem nya ay mahina ang pressure ng air na nasa tank nyopo
      If magkasama yung capillary tube at evaporator sa pag flushing. Better po na paghiwalayin nyo. Tulad ng ginawa kong video. Separate ang flushing ng capillary at ng evaporator at condenser. Dahil may dis advantage pag magkasama sila.

    • @allanpalad2159
      @allanpalad2159 4 ปีที่แล้ว +1

      @@jhaybizz maraming salamat sir.. gagawin ko po yan. maraning salamat lagi ako nag aabang ng video sa youtube

  • @renantejosesiguiente1442
    @renantejosesiguiente1442 4 ปีที่แล้ว

    sir yang airtank mo, paano nyo mag karga ng hangin sa loob?

    • @jhaybizz
      @jhaybizz  4 ปีที่แล้ว

      ah yes po sir renante gagamit kayu ng pressure guage,saka mga hose, at rotary compressor (LRA 49) na 2nd hand. Yan po pang charge ng air

  • @mariopangan9877
    @mariopangan9877 3 ปีที่แล้ว

    Gud afternun sir.
    Ganyan po problem ng ac unit ko.5.3 lang yung current rated current amperes niya pero umaabot siya ng 8.6. Magkano po ba ang bayad kapag pinareprocess siya?

    • @jhaybizz
      @jhaybizz  3 ปีที่แล้ว

      Mataas po if 8.6. possible sir may problem na ang o.l.p or comprressor nyopo...need na palitan..bago i system reprocess

    • @mariopangan3047
      @mariopangan3047 3 ปีที่แล้ว

      @@jhaybizz kahit po kaya i reprocess siya ganun pa rin po kaya?

    • @jhaybizz
      @jhaybizz  3 ปีที่แล้ว

      @@mariopangan3047 sir kung ang unit nyo ay high ampere, kahit palitan ng bagong overload di na tlaga mag no normal ang current ng comprresor , kahit pa i system reprocess nyo, kasi malalaman nyo na ok ang compressor ngayun palang na nag te test run kayu na may lamang freon, ngayun palang makakapag decide na kayu kung ano problem ,basta gamitin nyo mg clamp meter.
      Better po na palitan nyo na compressor o kaya palit ng bagong unit nalang po. Para di masakit sa ulo kung tlagang hindi na bumababa ang ampere

  • @ahlsoriano5555
    @ahlsoriano5555 5 หลายเดือนก่อน +1

    ba na Sobrang init ng Compressor kahit na ilangWELCOME Segundo lng namamatay na?
    Pinalitan ko na Capacitor ganon pa rin On / Off pa rin at Sobrang init ng Compresor

    • @jhaybizz
      @jhaybizz  5 หลายเดือนก่อน

      Sir compressor na sira stuck up

    • @jhaybizz
      @jhaybizz  5 หลายเดือนก่อน

      Compressor stuck up