What is a Lost Neutral? Lost Neutrals demonstrated

แชร์
ฝัง
  • เผยแพร่เมื่อ 20 พ.ย. 2024

ความคิดเห็น • 349

  • @PowderMill
    @PowderMill 16 วันที่ผ่านมา +41

    I’m an electrical engineer, licensed electrical contractor and volunteer firefighter of 35+ years.
    This is the very best demonstration of the risks posed by a “bad” or missing neutral.
    It SHOULD be made mandatory training for anyone working in the trade.
    Thank you!

    • @stringlarson1247
      @stringlarson1247 16 วันที่ผ่านมา

      EE, as well. I was fortunate to be there in the early 80s before the curriculum started to change to microchip design, etc.

    • @morganinspectionservices3840
      @morganinspectionservices3840  16 วันที่ผ่านมา

      Wow! Thanks so much for the feedback and comment. I really appreciate it.

  • @Mark117-zu5wp
    @Mark117-zu5wp 2 หลายเดือนก่อน +71

    I worked for electric utility company 36 years and learned all about bad neutrals and repaired many neutrals. When I retired they brought me back a trainer and one of the things I taught was open and bad neutrals. What they caused we called a power surge due to the imbalance of in coming service voltage. This is not to be confused with a power surge that occurs during lightening storms in the south. The purpose of the neutral in a 3wire or 4 wire service is to balance the hot legs. That was the only answer accepted on the final exam. Also many believe it is ok to touch a neural with bare hands. As long as everything is connected properly you shouldn't receive a shock. How ever if there is a neutral problem somewhere you will receive a shock just as if you touched the hot wire. It's all fun stuff but always be careful and ware your PPE. Better to be safe than dead.

    • @morganinspectionservices3840
      @morganinspectionservices3840  2 หลายเดือนก่อน +5

      I appreciate you watching, and I appreciate the feedback. It’s always a nice to hear from an from an expert in the field.

    • @bramcoteelectrical1088
      @bramcoteelectrical1088 หลายเดือนก่อน

      Great 👍 advise and we'll said

    • @donalfinn4205
      @donalfinn4205 15 วันที่ผ่านมา

      Wow.

    • @demoniack81
      @demoniack81 2 วันที่ผ่านมา

      You can get a small shock even from an earth wire (not sure how you call it in the US, the protective ground circuit) if it's broken.
      Almost all electronic devices have filtering capacitors that are meant to leak a small amount of current to filter out high frequency harmonics, and if the earth wire is broken they can't do that and will just charge up and wait to discharge through you.

    • @bramcoteelectrical1088
      @bramcoteelectrical1088 2 วันที่ผ่านมา

      @@demoniack81 or high leakage earth's especially on servers and pcs earthing arrangement

  • @JunkyardDigs
    @JunkyardDigs 10 หลายเดือนก่อน +26

    This happened last night during a wind storm, I was confused as hell, since half the light worked, and the other half were bright as hell. Can't believe we didn't blow any bulbs or anything after 12 hours. Thanks for the explanation!
    Edit: months later I would learn one of my friends backed into our telephone pole 😂

    • @morganinspectionservices3840
      @morganinspectionservices3840  10 หลายเดือนก่อน +6

      Wow! So you didn’t lose any electrical equipment in your home? If not, you were very lucky!!😊😊

    • @franklofarojr.2969
      @franklofarojr.2969 3 หลายเดือนก่อน

      @@morganinspectionservices3840 Cell phone and laptop chargers connected would like not only survive, but work normally during the overvoltage if they were (as they usually are - but not all are) rated for 100-240V for world use. So they'd run happily on 120, 170, 212 or even 240V or down to 100V. So something surviving and even working doesn't necessarily mean it is getting 120V. So you could plug a laptop charger in and have it work, then plug in a hair dryer and have it explode, and mistakenly not blame the power because ("the computer still worked").

    • @ericnewton5720
      @ericnewton5720 18 วันที่ผ่านมา +4

      I think he didn’t lose electronics generally because of the dc switching power supplies being able to deal with the slightly higher voltage that’s still below 240. A lot of computers power supplies used to have a manual switch for 120/240 operation, but these days many of them just auto adjust.

    • @Aaron_Voltz
      @Aaron_Voltz 17 วันที่ผ่านมา +2

      ​@@ericnewton5720 I was wondering if anyone else would comment about just that. Most modern electronics can auto adjust to 120 @ 60hz or 240 @ 50hz. This might even be the case with LED bulbs.

    • @BrokenLifeCycle
      @BrokenLifeCycle 12 วันที่ผ่านมา

      @@ericnewton5720 When faced with a world that has residential voltages between 100V and 240V at either 50Hz or 60Hz, a company is more likely to just design a single device that can handle as many cases instead of a bunch of separate localized variants of the same thing.

  • @ThatEEguy2818
    @ThatEEguy2818 15 วันที่ผ่านมา +11

    My dad worked in the water department of a local city. One day when he was working on a water main, they had to disconnect a house from the main to swap out a pipe. When they disconnected, the pipe sparked and the owner of the house came out yelling about his bulbs blowing. My guess, he and his neighbor shared a transformer, he lost his neutral between his house and pole, and his system was grounded to a water pipe. He was using his neighbors neutral through the water pipe, and my dad disconnected it when he separated the pipes.

    • @morganinspectionservices3840
      @morganinspectionservices3840  11 วันที่ผ่านมา +4

      That's a very interesting example of how a lost neutral can be present and affect a whole circuit!

  • @jimruthem6587
    @jimruthem6587 6 วันที่ผ่านมา +2

    Understood open neutral but your explanation of Lost neutral was an education. Thank you!

  • @tedlahm5740
    @tedlahm5740 ปีที่แล้ว +22

    Absolutely fantastic animation and demonstration.

  • @odieFeng
    @odieFeng ปีที่แล้ว +14

    Great explanation. I think I finally understand how this lost neutral thing works.

  • @fisqual
    @fisqual 5 วันที่ผ่านมา +1

    I always kinda knew why the high/low voltages were happening but this explanation really solidified my knowledge of why. Thanks so much for the video!

  • @brianlittle717
    @brianlittle717 26 วันที่ผ่านมา +5

    ⁠thanks for the reply. At 2:10 you said they were phases or legs. That’s two different things. Either way you look at it, it’s a single phase transformer. What we really mean when we mention phasing is time. Are the two legs out of time with one another? No they are not. There is nothing that can cause a delay. So they are in time. An oscilloscope would show a 120 volt sin wave or a 240 volt sin wave with their peaks being at 170 volts or 340 volts. The two legs do not add together to create 240 but rather we are breaking the 240 in half with the center tap. By doing so we are only changing the amplitude of the sin wave. All measurements are relative with respect to reference.
    My phone always gives an error when replying to a comment so I have to leave another comment.

    • @Starbuckin
      @Starbuckin 25 วันที่ผ่านมา +1

      Excellent comment!

    • @Randall-mt7jk
      @Randall-mt7jk 15 วันที่ผ่านมา

      Single phase , each leg to neutral 120v. 240 across both legs.

    • @brianlittle717
      @brianlittle717 14 วันที่ผ่านมา

      @@Randall-mt7jk​​⁠correct. One sin wave has twice the amplitude as the other and that’s the ONLY difference between the two voltages. They are the same phase.

    • @aspensulphate
      @aspensulphate 8 วันที่ผ่านมา

      Good points. Note that loads which only require 240 volts (e.g. electric heater) do not need a neutral, though they should be grounded.

  • @goldCrystalhaze
    @goldCrystalhaze 15 วันที่ผ่านมา +1

    The best explanation i have ever received. Thank you for sharing your knowledge!

  • @donpretlow
    @donpretlow 3 หลายเดือนก่อน +3

    Just had another issue with the neutral line going to the transformer on the pole. I had some strange power fluctuations again but not as drastic. So I put my clamp meter on one leg going into my panel. Then I turned every other breaker off putting a larger load on one leg. It showed a voltage delta of about 15 volts. I called FPL and they sent a service truck out. He pulled the meter and put a device on it to check and it showed it was just over the allowed difference. After inspecting the ground cable he saw where my neighbors tree was chafing the wire. It was warn down to a single strand. They replaced the neutral drop and it is now fixed.

    • @morganinspectionservices3840
      @morganinspectionservices3840  3 หลายเดือนก่อน +2

      Good thing you caught that and followed through on it. I really appreciate you sharing that. I and my viewers learn from everybody else’s experiences.

  • @marshallstephens7356
    @marshallstephens7356 5 หลายเดือนก่อน +1

    Thank you so much for posting this video! We had a big wind storm roll through yesterday and knocked out the neutral wire to our home. I wasn't sure why our lights were acting strange; but now I know. Thank you!

    • @morganinspectionservices3840
      @morganinspectionservices3840  5 หลายเดือนก่อน

      I am glad the video was helpful. Thanks for watching and thanks for the feedback.

  • @brianlittle717
    @brianlittle717 25 วันที่ผ่านมา

    Thanks Mike. I’ve done heat and air most of my career and started my own business 5 years ago. I’m near Memphis. I struggled with this very concept but the guys at our local power company are the reason I understand it now. I’ve been up there several times early in the morning when they get there to start their day and pick their brains. There are still concepts I don’t understand so I’m always learning. For example, nowadays they are teaching that voltage is not a force and I’m really struggling with that one because that was the entire basis of electricity when I studied in college back in the 90s. Electromotive force = voltage.
    I really struggle with computers. I don’t have the patience nor do I understand all the errors I get. With an electrical circuit, a switch energizes a load. When you apply voltage to that load, current WILL flow and the circuit WILL work. Sort of like pressing a key on a mechanical typewriter. You press the key and the hammer WILL hit the paper. With a computer, you give it an input and a thousand things have to happen before the computer decides to energize the load. Or you press a key and the computer receives a request, thinks about it, and decides if it wants to respond. I hate computers and right now I’m frustrated because I’ve tried again for about an hour to figure out how to respond to these comments and I get an http status error 400 error when I reply. Nothing on TH-cam or Google has worked. I’m using an iPhone 15 pro max that is 3 months old.
    But yeah I’d love to see you do a video on this. I’ve done a couple videos myself but I don’t know how to use the computer to do the animations and stuff and I don’t know how to edit a video so mine are just one take and they were just on capacitors proving that current can flow through them. Experimental stuff. I’ll subscribe so I can catch it.

    • @morganinspectionservices3840
      @morganinspectionservices3840  25 วันที่ผ่านมา +1

      Well, I have an engineering degree, but I’ve been a home inspector for the last 22 years. I love learning and I love teaching. I have learned that I love making animations and I’m trying to make better and better videos. I’m getting older and spend almost all of my free time working on new videos because right now it is my passion. I often have to learn things before I make my videos so I can sound like I know what I’m talking about. You have inspired me to continue on. It’s been good talking to you.

    • @cliffhaskett7703
      @cliffhaskett7703 4 วันที่ผ่านมา

      I understand your misunderstanding.
      I have generally been in the automotive
      field and know that a hot & a ground makes 12 volts. Hence, an electrical component works. Occasionally, the addition of a resistor or relay change that basic Hot/Ground logic. No problem , I'm still on board.
      Then came the computers. I throw my hands up and say, nope, ain't gonna try to understand.
      Well , then I dabble a little and get a tiny understanding.
      Don't trust my logic on this, and I gladly stand corrected if I'm totally off base.
      Your observation of flipping a computer switch and it simply sends a signal is correct , IMO.
      In my world (automotive) , the revelation came to me from watching a college student explaining their "Robotics" class. The student went into Can Bus theory. Can Bus ? (maybe I've spelled it wrong) , where have I heard that before ?
      Yep , in newfangled automotive electronics diagnosis.
      Can Bus - High.
      Can Bus -Low.
      From my understanding, the Can Bus system runs on 5 volts or less. The Can Bus system goes through a system of checks of this, and that before energizing the desired component.
      All sensors sending signals ?
      Seat belt fastened ?
      You get the picture .
      From what I understand, Can Bus High generally operates critical components.
      Ignition, fuel supply , Etc.
      Can Bus Low generally operates secondary components.
      Seat belts , heated seats , radio,Etc.
      Going back to the Robotics class theory.
      A robot, theoretically, cannot move its right leg until it receives a signal that it has already moved its left leg in a walking scenario.
      Cars are now robots.
      The car will not start (hypothetically) until it receives a signal that the seat belt has been fastened.

  • @TheBry_Guy
    @TheBry_Guy 7 หลายเดือนก่อน +3

    great demo. thanks!

  • @condor5635
    @condor5635 24 วันที่ผ่านมา +1

    Great video. Can you speak to the dangers of having a bonded neutral on your generator versus it being a floating neutral when using it to power your house through a manual interlock? Thanks!

  • @donpretlow
    @donpretlow ปีที่แล้ว +13

    I’ve had that happen at my house during a hurricane. A tree fell on the drop to the house separating the neutral. As soon as the lights went bright I knew what happened and ran to secure the breaker. It took out the refrigerator, microwave, oven, dishwasher and clothes dryer. Completely fried three surge protecting power strips and burned out a bunch of light bulbs.

    • @morganinspectionservices3840
      @morganinspectionservices3840  ปีที่แล้ว +3

      Yes, it can be very destructive to electronic equipment. Good thing you knew enough to recognize what was happening and shut off the power as quickly as possible.

    • @franklofarojr.2969
      @franklofarojr.2969 3 หลายเดือนก่อน +2

      Damaged the dryer? Wow. They use 240V usually, but some use 120 also to run some circuits, if that side goes high it could do damage. If it goes low, not so likely.

    • @donpretlow
      @donpretlow 3 หลายเดือนก่อน +4

      @@franklofarojr.2969 It fried the circuit board. I replaced it with an old 1980s dryer that has been refurbished. No electronics works better than any new dryer I have had.

    • @wdmm94
      @wdmm94 2 หลายเดือนก่อน +3

      Back in the day when a washing machine had a more mechanical clock timer for cycling.

  • @bobskie321
    @bobskie321 3 หลายเดือนก่อน +8

    I think that problem only happens in countries using 120 volts because they have three cables going to their house from the transformer (+120v, 0v, -120v). In countries using 240 volts that's not a problem because they only have two cables going to their house from the transformer. If they lose one of the cables the light won't turn on.

    • @morganinspectionservices3840
      @morganinspectionservices3840  3 หลายเดือนก่อน +5

      Yes, you are correct. It only happens in countries where the voltage is split at the transformer, so countries that only use 220 or 240 V do not encounter this same problem.

    • @cedriclynch
      @cedriclynch 15 วันที่ผ่านมา +2

      ​@@morganinspectionservices3840This sort of thing does happen in countries using 240V systems, because the distribution is 3-phase. Factories, apartment blocks and other large premises get a 3-phase supply (that is supposed to be 415V between any two phases and 240V between any phase and neutral) and most houses get one of the three phases, rotating from house to house along the road. Loss of the neutral causes different voltages on the different phases according to the loads on them, and you can get things burning out because of excessive voltage.

    • @okaro6595
      @okaro6595 15 วันที่ผ่านมา

      Few countries use 240 V. Most of Europe is 400 V three phase and the same thing can happen. With 240 V there is another problem. Remember the neutral and ground are connected. What is in the neutral will be on the equipment cases. In single phase 240 V that is full 240 V. Now one can avoid this by not connecting the neutral and the ground and relying on RCDs.
      In the UK EV charging points need to be protected against the broken neutral or PEN-fault as it is called there. This can be done by using a ground rod for ground. As it is RCD protected it will be safe. There are also more sophisticated methods.

    • @DezsikeDevil1
      @DezsikeDevil1 14 วันที่ผ่านมา

      We had this on a 3 phase 240 V European system. Something was blown at the transformer and the lights were dim. We had a heavily loaded phase with the dishwasher turned on where everything survived and two almost unloaded phases where many power supplies were blown. Since most switching mode power supplies can operate on 240 V without issues it's not a huge issue in the US nowadays, but here in Europe we get over 400 V which blows most of the power supplies. Luckily if it's manufactured correctly the high voltage will make a component short to the earth (and sometimes a capacitor will also blow up), protecting the electronics behind so only the power supply needs to be replaced.

    • @jbarner13
      @jbarner13 12 วันที่ผ่านมา

      @@okaro6595 In all the US service panels I have seen, it is impossible to separate the neutral from the ground, electrically, unless you insulated the neutral bus bar from the panel, and I would think that would be a code violation. I was wondering as I watched this if the building ground wouldn't mask a lost neutral, as the neutral is also grounded at the pole. Granted, many if not most buildings have inadequate grounding, but I would think that in a properly grounded system it would be impossible for a lost neutral to cut all current flow on the neutral on the building side of the system.

  • @vmax4575
    @vmax4575 9 หลายเดือนก่อน +3

    Excellent explanation/demonstration. Congrats and thank you.

  • @DrBilly90210
    @DrBilly90210 5 วันที่ผ่านมา

    Learned something today! Thanks! How would a panel mounted surge protection device affect this situation?

    • @morganinspectionservices3840
      @morganinspectionservices3840  5 วันที่ผ่านมา

      I can’t imagine that it would change anything. Surge protectors are designed to shunt very high voltages. 240 or 250 V would not even be detected by a surge protector, I don’t believe.

  • @metalrobnj
    @metalrobnj 14 วันที่ผ่านมา +1

    I worked as a cable tech for 16 years. I also worked in a beach area where the grid was copper but all there service lines were aluminum. The two different metals would cause the neutral to fail fairly often. Very dangerous, if you were not careful. Low volt guys get little to no training on this. Most of the time the connection point at the bond would completely melted and that was a dead give away. But sometimes it wouldn't be and if you didn't hit it with your FVD you would get sparks flying when the wrench touched the coax fittings.

    • @thedave1771
      @thedave1771 14 วันที่ผ่านมา

      Ouch, that’s terrifying.

    • @morganinspectionservices3840
      @morganinspectionservices3840  13 วันที่ผ่านมา

      Very interesting. Thanks for watching, and thanks for your comment. Yes, these lost neutrals can be very dangerous.

  • @victorbruce5772
    @victorbruce5772 11 วันที่ผ่านมา

    Friend bought an old house, old 2 wire no ground romex. Some later wiring added with ground. Got shocked in bathroom, even though had working GFI outlet. It tested okay, but everything supposed to be grounded, was HOT, intermittently. Overhead fixture, device frames, cover screws, etc.
    After looking around, what was rewired, added over the years. The bathroom had been rewired with floating ground wire not connected back to panel. Along with added ceiling fans in nearby living room. A single tiny strand of hot wire on fan was sticking out of wire nut, touching floating ground wire. Creating intermittent shock hazard whenever fan switched on. Fixing that fault, running ground wire to panel, that problem was repaired.
    Hard to tell what hazards lurk in walls and attics. Even if things seem to be working.

    • @morganinspectionservices3840
      @morganinspectionservices3840  10 วันที่ผ่านมา

      Wow! What a story. That definitely was a dangerous situation. Sounds like a hard thing to track down.

  • @petermoore8811
    @petermoore8811 18 วันที่ผ่านมา +3

    Absolutely makes sense. Awesome.

  • @odieFeng
    @odieFeng 10 หลายเดือนก่อน +3

    I think I finally understand this. Thank you.

  • @okaro6595
    @okaro6595 10 หลายเดือนก่อน +4

    Not only that. As the neutral is bonded to the ground wire the voltage on the neutral gets to any grounded equipment case. This could in worst case kill. Here the instruction is to get out and call the power company and not to return until it is fixed but we have higher voltage.

    • @morganinspectionservices3840
      @morganinspectionservices3840  10 หลายเดือนก่อน

      You are correct. Thank you for clarifying that.

    • @VavrMar
      @VavrMar 15 วันที่ผ่านมา

      I don't know about US but in Czech (EU) you have to have 3 wire system and connecting neutral to ground is forbidden. Yes there still might be old houses to have it but in own interests should rewire it asap. Also every house have to have "ground protector" which measure current leak from main to ground and Tripp in matter of milliseconds.

    • @okaro6595
      @okaro6595 14 วันที่ผ่านมา

      @@VavrMar You mean the ground wire? That is known as TT. It is used in many countries in Europe. Others use TN-C-S where the ground wire connects to the neutral at the entry. Such a system does not require RCDs to work though they now are mandatory as additional protection.

  • @syitiger9072
    @syitiger9072 ปีที่แล้ว +2

    Lost neutral situation can happen also on 240volt circuits or anything sharing the neutral like 12/3 circuits

  • @terryenyart5838
    @terryenyart5838 วันที่ผ่านมา

    This is a wonderful explanation & video!

  • @TheRotorhound
    @TheRotorhound 14 วันที่ผ่านมา

    Nice video. Power company came out today and ran a temporary neutral to my meter and they will bury wires in a few weeks. Have had flickering lights for some time.

    • @morganinspectionservices3840
      @morganinspectionservices3840  13 วันที่ผ่านมา

      Thanks. Glad that you discovered that you had a problem before it got any worse.

  • @jasonhale4639
    @jasonhale4639 14 วันที่ผ่านมา

    My brother had this happen at his house when a lady hit the power pole across the street and he also had a bad ground at the breaker panel which caused the whole house to try and back feed through the 14 gauge ground wires on the furnace and dish washer as one was connected to a gas line and the other a copper water line into galvanized iron water line. Needless to say, I am glad that his daughter skipped school that day as she quickly went back and turned off the main after seeing smoke start rolling out of everywhere. I had to go up and replace all the wiring on both appliances and ended up installing a new ground rod outside along with bonding it to the gas and water lines.

    • @morganinspectionservices3840
      @morganinspectionservices3840  13 วันที่ผ่านมา

      Wow! That’s scary. Good thing the daughter knew to turn off the power. These situations can definitely be dangerous.

  • @jimboinsa
    @jimboinsa 11 วันที่ผ่านมา

    Excellent explanation and demonstration.

  • @juans6639
    @juans6639 15 วันที่ผ่านมา +1

    Excellent, precise explanation. Thank you.

  • @canuckfixit7722
    @canuckfixit7722 วันที่ผ่านมา

    Great demonstration! Is there a monitoring unit that you can install on your load centre that would cut power the instant neutral was lost, for example due to a fallen branch in a storm or perhaps an ice storm?

    • @morganinspectionservices3840
      @morganinspectionservices3840  วันที่ผ่านมา

      Thanks for the feedback. I am not aware of anything that monitors for this. I will have to do some research.

    • @canuckfixit7722
      @canuckfixit7722 20 ชั่วโมงที่ผ่านมา

      @morganinspectionservices3840 I envision that it would be simple. Perhaps monitoring neutral to ground in a strategic location outside that would pass a small current and when that current stops, you could have a lost neutral condition.

  • @pauldow1648
    @pauldow1648 3 หลายเดือนก่อน +3

    Call the power company as the problem is their neutral.
    If you call a electrician you will be stuck for service call $ , and they don't work on power company lines.. This could be over $100 for a minimum call
    The power company will service and fix the neutral connection.no charge.
    These electrical neutral problem s are dangerous and eerie.
    Our aluminum framed screen porch was measuring 40 to 70 volts. My dog yipped as she went outside because the aluminum frame and door was electrified.
    I put my fluke black lead into the nearby ground (soil) and the red lead on some aluminum - ac voltages were all over the place. I think the electricity found a ground but also found a ground that energized the aluminum frame which was also grounded. 😮😮

  • @challenger-rta3761
    @challenger-rta3761 14 วันที่ผ่านมา

    Thanks for the good demonstration.This will help other save themself. Can be a very dangerous situation. I have seen this happen a few times. One has to learn this before one plays with it. The fist thing he taught me was to respect it and treat like it is HOT!
    I was 12 years old Back in the 60's and I was wiring houses with my father. {unknown to me at the time. When he was in the USN he was a an EM and also was an electrical instructor. I wounder way he had all those books around that I read.) As a teenager I joined the USN and was an Electricians Mate and advanced right to C school. and Aced it was not much to right home about. Skipped A school all together. Any navy guy knows what that is. later in life acquired a BS Electrical Engineering. Build power plants and switch yards and control yards. Sorry about ringing my own bell. May next do 3 and 4 way switches. I just shake my head at times when it's not understood by someone that call's themself and electrician.

    • @morganinspectionservices3840
      @morganinspectionservices3840  13 วันที่ผ่านมา

      So true. Thank you for your service. I too am former navy. Nuclear propulsion officer on the submarine USS Florida back in the early 90’s. Learned a lot about electricity doing that.

  • @vince6829
    @vince6829 2 หลายเดือนก่อน +1

    Nice demonstration. Thank you for sharing your knowledge.

  • @BaronVonSTFU
    @BaronVonSTFU 2 วันที่ผ่านมา

    Would a whole house surge protector help at all with preventing this?

  • @maxenielsen
    @maxenielsen 7 วันที่ผ่านมา

    Thanks for the great video. Well thought out. Well demonstrated.

  • @thetruthhurtsmyselfincluded832
    @thetruthhurtsmyselfincluded832 9 วันที่ผ่านมา

    Excellent video Man, I learned a lot. Much appreciated.
    You have a new subscriber.

  • @dhg247x1
    @dhg247x1 13 วันที่ผ่านมา +2

    How does the ground affect this? The neutral and ground are bonded at the panel.

    • @morganinspectionservices3840
      @morganinspectionservices3840  13 วันที่ผ่านมา

      You will have some current flowing from the panel into the earth due to the groundingelectrode conductor. Since the earth has a high level of resistance, there will not be a lot of current flow, but probably a few amps.

    • @hueywallop2461
      @hueywallop2461 10 วันที่ผ่านมา

      @@morganinspectionservices3840 Thanks for your answer and this great video. But I'm still a bit confused. What then is the purpose of connecting the panel neutral bus bar to a local ground rod?

    • @13_13k
      @13_13k 4 วันที่ผ่านมา

      ​@@hueywallop2461 ---- the neutral busbar shouldn't be connected to the ground rod. The neutral busbar should be connected to the neutral from the meter. The ground wire comes from the ground rod and either cold water pipe before the shut off valve(residential) or building steel (commercial) and up into the service panel hitting a ground hub on the connector used for the ground entrance into the panel then to a ground busbar or to a ground lug attached to the panel box with a nut and bolt or a hole that has been tapped with threads for a screw to tighten into.

  • @wm437
    @wm437 14 วันที่ผ่านมา

    Excellent demonstration. Thank you for sharing.👍🏽

  • @chintakpatel505
    @chintakpatel505 6 หลายเดือนก่อน +2

    Thanks for video. I have a follow up question. Does bonded grounding and Neutral at service panel help to mitigate serious consequences laid out?

    • @morganinspectionservices3840
      @morganinspectionservices3840  6 หลายเดือนก่อน +2

      No. When your service loses a neutral, nothing done at the panel that I can think of will change the fact that you will have the two legs in series on a 240-volt service.

    • @TheOmengod
      @TheOmengod 4 หลายเดือนก่อน

      How do you test for loss of neutral?

    • @jyao5409
      @jyao5409 14 วันที่ผ่านมา

      If neutral is still bonded to ground, the ground can serve as a return path to the transformer, though it's not an efficient path due to earth's high impedance.

  • @brianlittle717
    @brianlittle717 26 วันที่ผ่านมา

    ⁠maybe this is a better way to explain and understand. If you remember ELI the ICE man we know that a reactive load causes voltage and current to be out of phase with respect to one another by some amount of angle. That is to say they are out of time with each other. Voltage happens first or current happens first. This is because a capacitive circuit delays the voltage and an inductive circuit delays the current.
    With 3 phase, the 120* angle between each phase comes from the power company with their generators being 120* out of sync with each other.
    In the case of a single phase transformer secondary, this is not a load but rather a voltage source. There is nothing in it that would cause a delay in time.
    I did watch your video and your meat and potatoes of what you’re explaining is spot on. It’s just that when things are taught with misunderstandings, it causes confusion to set in and the confusion gets taught to the next group and so on.
    When I studied in the 90s I went above and beyond what was taught in the classrooms and I missed a lot of test questions because of it. One that I remember was marking a question false that said current can only flow in one direction through a diode. I knew how a voltage regulator works by flowing current through the diode backwards so I marked it false. My teacher had no clue what a zenor was. I’m an hvac contractor now and work with electricity every day but I’m not an electrician. Sometimes I wish I’d learned that trade instead.

    • @morganinspectionservices3840
      @morganinspectionservices3840  26 วันที่ผ่านมา

      Whatever you are, you sound like you really know your stuff. I was guessing you were an electrical engineer. I honestly have always heard and believed, and therefore thought that the two 120 V legs were 180 degrees out of phase. I learned that because of one being wound clockwise and the other being wound counterclockwise that they are 180° out of phase, and that makes total sense to me. You have gotten me to thinking, and I am going to do some more research, and get ahold of an oscilloscope. I will probably make a new video based on this discussion and what I learn. I hope to talk to you more.

  • @chromypone
    @chromypone 15 วันที่ผ่านมา +1

    One thing that I didn't see really mentioned, though no real good electrician would run into this problem, is that the "neutral" of the right side of the circuit will now be positive with respect to ground. So if you think you can touch or work on that neutral and be safe, you better think again

    • @morganinspectionservices3840
      @morganinspectionservices3840  14 วันที่ผ่านมา +1

      Very true. I do think I mentioned somewhere that there can be voltage on the neutral. I did recently release a new lost neutral video. It specifically covers and even measures the voltage on the neutral.

  • @christianlohmann8577
    @christianlohmann8577 15 วันที่ผ่านมา

    Great demo. Scary too. Is there not a way to detect that ? Or protect ? Specially if lost neutral can be an external event.

    • @morganinspectionservices3840
      @morganinspectionservices3840  15 วันที่ผ่านมา

      Thank you. I don’t know of any way to detect it other than noticing lights dimming or brightening, or other things running faster or slower than normal.

  • @Sparky-ww5re
    @Sparky-ww5re ปีที่แล้ว +5

    A few years back went on a service call where the homeowner had smoked up a flat-screen, DVR, and stereo system after a 1500 watt electric fireplace had been running for about an hour. It was a lost neutral on a MWBC feeding the master bed & living room with backstab connected receptacles. A backstab connection upstream burned out on the neutral. Home was built sometime in the 1970s if memory serves me right. This expensive ordeal would have been avoided had the receptacles been installed in accordance with 300.13 (B) which states the neutral of a MWBC cannot be interrupted by removing a wiring device.

    • @morganinspectionservices3840
      @morganinspectionservices3840  ปีที่แล้ว

      Great info/example. Thanks.

    • @stringlarson1247
      @stringlarson1247 16 วันที่ผ่านมา

      Thankfully, I live in Chicago, where everything (almost) is in conduit, and MWBCs are not as common, especially in older buildings.
      I do run into hack jobs where someone had scabbed in an illegal 14 or 12/3 'BX' and either ran both legs on a tandem or 2 separate breakers where the handles were not tied together. The Chicago NEC upped the allowable length for 'BX' to 25' from 6' (whips) for 'enclosed/protected' spaces. I expect to see more problems popping up as people (either DIY or remodeling cos.) run new circuits without the knowledge of how to do it properly and/or use 'backstabbing' on devices.

    • @aspensulphate
      @aspensulphate 8 วันที่ผ่านมา

      MWBC = Multi-Wire Branch Circuit

  • @philipoakley5498
    @philipoakley5498 13 วันที่ผ่านมา +1

    Interesting. Here in UK the consideration is typically diverted neutrals because of subtle differences in the way you & we feed supply current. In the UK case it's where neutral currents end up flowing in the ground/earth/protection wiring (as most distributions have repeated connections to Earth).

    • @mysterycrumble
      @mysterycrumble 11 วันที่ผ่านมา

      does this prevent or mitigate the issue or is the issue just happening differently? i sound stupid i know but apart from being able to wire a plug i am an electrical idiot.

    • @philipoakley5498
      @philipoakley5498 11 วันที่ผ่านมา

      @@mysterycrumble In the US system you have two live or 'hot' feeds which are anti-phase (opposite polarity) so that you can have ~240V power hungry devices connected between them.
      When you 'lose the neutral' then you have your two sets of 120v loads connected in series, so 240V, without the neutral stabilising the 'mid point' voltage at zero (the two hots being +120 and -120v relatively speaking). At this stage the weaker side of the two hots tends to 'blow' from having over voltage, and hence on that spur, over current.
      Meanwhile back in UK we have far more domestic circuits distributed from local substations where the neutral and earth are connected for multiple household supplies (often US supplies being a local transformer so only one or two with the common neutral/earth at the supply pole). so..
      Now with our older infrastructure we have more cases where the supply cable has lost the neutral ("broken PEN") and instead the local 'earth' conductor is doing the work of the return path. And that return path (i.e. the whole supply current for other properties & services that neutral also fed) can prefer to run through your household earth wiring, especially if you have rock solid earth bonding, earth rods, copper water piping etc.
      An example could be the (faulty) street lighting that is seeking to return via your household wiring which isn't sized to carry such currents. Also makes for EV charger risks (an outside power point nearer the street light than the house) requiring extra detection for spurious earth voltages and sneak current paths and multi-way isolation).
      Everything is great when it works as designed. We're just getting better at being concerned about real world faults!

  • @cemobili1
    @cemobili1 วันที่ผ่านมา

    Thank you excellent information delivered 👏

  • @supahfly_uk
    @supahfly_uk 16 วันที่ผ่านมา

    Wow that's scary I never thought about that. Very well explained thank you.

  • @MikeMorgan-o1f
    @MikeMorgan-o1f ปีที่แล้ว +3

    Thank you. Great video.

  • @jacquesmillard
    @jacquesmillard 13 วันที่ผ่านมา

    Is this an issue you have to only worry about in North America or if you have a 3 phase supply?

    • @defiik
      @defiik 12 วันที่ผ่านมา

      usa is 3 phase

  • @erihsehc2
    @erihsehc2 หลายเดือนก่อน

    Thanks for the video. I tested the plugs of my home and I found that a few plugs have 50v between neutral and ground (220v power supply) , may I ask why the voltage is not zero between neutral and ground lines?

    • @morganinspectionservices3840
      @morganinspectionservices3840  หลายเดือนก่อน

      Are the outlets where you’re getting the 50 V close together where they could all be on the same circuit? If so, it’s likely that there is a bad neutral connection somewhere so you’re getting some resistance on the neutral wire. As current flows through the neutral wire, you will get a voltage drop, which will put some voltage on one side of the neutral.

    • @erihsehc2
      @erihsehc2 หลายเดือนก่อน

      @@morganinspectionservices3840 Thank you. I guess they are in the same circuit. Btw, would that be a hazard if it is a bad neutral connection that I should be concerned?

    • @morganinspectionservices3840
      @morganinspectionservices3840  หลายเดือนก่อน +1

      @@erihsehc2 It certainly can be a hazard, but it’s not definitely a hazard. It just depends on exactly what’s going on. Loose connections can result in arcing which creates heat which can result in a fire. It also puts voltage on neutral wires switch can, under certain conditions, cause somebody to get shocked. If you’ve done any electrical work and feel comfortable, you could check the affected receptacles to see if there’s a loose connection there, or it could also be in the electric panel where the wire is connected to the bus bar. Best thing to do would be to call an electrician.

  • @jimmybaker4610
    @jimmybaker4610 3 วันที่ผ่านมา

    Happened at my friend's house a couple yrs ago,strange things started happening to lights etc.wind caused limb to break the neutral at the pole

    • @morganinspectionservices3840
      @morganinspectionservices3840  3 วันที่ผ่านมา +1

      @@jimmybaker4610 yes, It definitely create some crazy symptoms - especially if you don’t know what it is.

    • @jimmybaker4610
      @jimmybaker4610 3 วันที่ผ่านมา

      @morganinspectionservices3840 we tripped main service first thing.didnt take long for power co. to locate problem.

  • @joecummings1260
    @joecummings1260 10 วันที่ผ่านมา

    Not a lost neutral, but an overvoltage story. I went out on a call to a small concrete plant, served by an open delta 120/240 with the high leg. There was a detached office in a prefabricated shed on the property with a 30 amp 120 volt feeder going to it for lights, a fridge, microwave, office machines. Two 120 volt branch circuits in the shed, each one feeding a ground fault receptacle first before daisy chaining to the other receptacles.
    Well the reason they called me was because they replaced the ground faults after they fried, and they immediately fried again. I check and there is 208 volts on the branch circuit going to the office between hot and neutral. Turns out they added a 3 phase circuit in the plant to run a little welder, and when they did it they moved the breaker for the feeder for the subpanel in the shed to one of those breaker spaces that somebody had skipped. They didn't know the reason those spaces were skipped when installing the single phase breakers was because every 3rd space was the high (208 v) leg.
    Thankfully it was the early 90's and not really anything with an electronic board, so nothing got damaged other than the ground faults. But anyway I know 208 volts will smoke a ground fault and possibly protect stuff downstream, But I don't know how fast it's going to smoke and open the circuit, or at what voltage, or how reliably. But a bunch of fried ones could be a good indication of overvoltage caused by a loose neutral

    • @morganinspectionservices3840
      @morganinspectionservices3840  9 วันที่ผ่านมา

      Wow! Great story. Lucky nobody got hurt or nothing else got fried. About two months ago, I put a video on this channel after I found 240 V on a 120 V receptacle in a bathroom, but it was only 240 V when the exhaust fan was turned on. With the exhaust fan off, there was only 120 V. Kind of a crazy situation. Scary when people who don’t know what they’re doing do electrical work.

  • @tedlahm5740
    @tedlahm5740 ปีที่แล้ว +1

    The three (3) bulbs on either leg are wired in parallel.
    (Although the two (2) legs are now in series to each other with the lost neutral.)
    When one bulb is turned off, the Resistance goes up and the Current
    goes down (in that leg) because they are in parallel.
    Naturally the leg with the highest resistance (series circuit) has the highest voltage drop.

    • @hewking
      @hewking 5 หลายเดือนก่อน

      "When one bulb is turned off, the Resistance goes up and the Current
      goes down (in that leg) " - i understand that resistance goes up if we swich off 1 light in the circuit because its parallel so it is as if we closed 1 of the 3 roads for the current - so more resistance. More resistance means less current in that leg but both legs are in series so the current is the same. So if the same current is flowing while the voltage is much higher means that a lot more energy is on the side when 1 light is off. Does it make sense the way i rephrased it?

  • @NickFrom1228
    @NickFrom1228 12 วันที่ผ่านมา

    I've had to happen to me. A storm broke off a tree limb, which fell and broke the neutral from the transformer. It was a wild ride. My wife and I had a light fixture above the bed with incandescent bulbs in it. When the event happened we both were laying down but we sat up when the lights started going crazy and about one second later the bulbs in the fixture exploded and the glass fell onto our pillows. I jumped out of be do run down and flip the main disconnect but out of habit I hit the light switch for the stairway light. Poof, another bulb blows. I had to grab a flashlight to get to the panel which extended the time it took and I'm sure that caused some of the other devices to fry. I lost tv, vcr, some of the stereo, relay board in the range and who knows what else. A guest staying with us said the vcr was crackling like bacon frying and the tv looked like it was in the poltergeist movie. Honestly I'm surprised more devices didn't fry.

  • @Rovibronique
    @Rovibronique 15 วันที่ผ่านมา

    Interesting, but if the current in the phase/hot wire is not the same as in the neutral wire, your differential circuit breaker should trip at millisecond timescale. Or in your country you do not have this kind of protection mandatory?

    • @morganinspectionservices3840
      @morganinspectionservices3840  15 วันที่ผ่านมา

      It sounds like you’re basically referring to a ground fault circuit interrupter breaker. We do have these in the US, but when a neutral is lost, it is lost prior to the panel. You will still have current flowing back on the individual branch circuit neutrals, so a GFCI would not help in that situation.

  • @26hrishi
    @26hrishi 2 วันที่ผ่านมา

    what is the impact on the consumer meter reading if in a three pages meter, neutral wire is directly connected from supply to the wire of consumer i.e input neutral is not connected to the meter input and neutral output of meter is not connected to the consumer neutral wire? Pls note the three phases are still connected via the consumer meter.

  • @dmf37207
    @dmf37207 4 หลายเดือนก่อน +2

    Thank you, great information. Neutral for dummies.

  • @tjairicciardi9747
    @tjairicciardi9747 10 วันที่ผ่านมา

    awesome video, great explanation

  • @Taluvian
    @Taluvian 17 วันที่ผ่านมา

    How would you get a lost neutral condition? Don't these circuits typically have independent neutrals back to the breaker? Also I thought the neutrals and grounds are bonded at the breaker panel.

    • @morganinspectionservices3840
      @morganinspectionservices3840  17 วันที่ผ่านมา

      A lost neutral occurs before the breaker panel. As a video explains, a lost neutral can occur anywhere between the transformer and the breaker panel. Maybe the neutral gets corroded or pulls loose at the weatherhead. Maybe a tree rubs on it, and overtime breaks it. There is also a situation called an open neutral, and that’s something that affects an individual circuit or a portion of a circuit. That is a very different situation.

  • @wdmm94
    @wdmm94 2 หลายเดือนก่อน +1

    Now can I ask an electrical engineer a question. It has always seemed to me that AC voltages of 120 or even substantially lower are very easy to get shocked from, but DC current don't seem to be this way at these voltages. What I am asking is this, is messing around with batteries that are 90 volts or 130 volts a dangerous shock hazard? Landline telephones operate at 60 volts DC power. Antique 20's era radios had battery banks that operated up to 135 volts. I have been powering old radios like this by putting together 9v batteries in series to about 90 volts but have always been a little leery about the safety of handling such things. I have carefully tested lower DC voltages on the back of one hand and couldn't seemingly feel any current. I have somewhat assumed that 60volt DC may not be quite as dangerous for the simple fact that phone wiring is pretty wide open in the public sphere. Could someone clarify this. I have looked quite a bit online a few times to try and find some discussion of this.

    • @morganinspectionservices3840
      @morganinspectionservices3840  2 หลายเดือนก่อน +3

      I will start off by saying that both AC and DC voltage can be dangerous and fatal, however, the human body seems to tolerate DC voltage better. One study I read says that the human body can withstand approximately five times the DC voltage than it can AC voltage. If this is correct, then it would take approximately 600 V DC to give the equivalent shock that 120 V AC gives. AC voltage, which is alternating current, seems to affect the body more than direct current does. Alternating current has a greater tendency to cause atrial fibrillation than DC voltage does. The human body seems to have a higher impedance (resistance) to direct current than it does to alternating current. Having said this, every body is different, and low DC voltages can sometimes be fatal to some people.

    • @markhischier2750
      @markhischier2750 หลายเดือนก่อน

      When I was building electric cars 35 years ago, I got shocked by a 72V DC battery pack. Not bad, but shocking. It's about as bad as getting hit with az24V AC (thermostat or sprinkler valve). I can feel 42V DC as well.

    • @michaellacaria910
      @michaellacaria910 หลายเดือนก่อน +1

      I was taught it takes approx 40v before you feel anything, having said that, the current is what hurts you so it depends on the power supply. For example, static electricity is thousands of volts but is very low current so you feel a “pin prick” at worse. The North American public telephone system was around 40v DC (?), it gave you a bit of a buz under the right conditions enough to feel it but no kill you (depended on individual circumstances, humidity and skin resistance). The path the current takes in the body is most important too. If in doubt and you must touch the wires, I was taught to use the right hand thumb and index finger or just one finger, the idea there is that the loop urgent would be localized and not travel through the body across the chest through the heart down to the legs into the ground. Current needs a path through you to another conductor, usually ground in most cases of shock. Having said all this, the safe way is to not touch wires above 30v (I was taught that) and gamble with fate, there’s enough testers out there to safely indicate live wires.

    • @okaro6595
      @okaro6595 15 วันที่ผ่านมา +1

      Generally voltages below 50 V AC and 120 V DC are safe in case of an accidental exposure. The primary safety method is always to avoid the exposure. Laptops operate at 19.5 volts because 20 V has been considered the limit below it is safe.
      If you operate with 90-130 V treat it like it was mains voltage like have no exposed contacts.

  • @edwardblair4096
    @edwardblair4096 14 วันที่ผ่านมา

    Am I correct that if you turned off the third light on leg 1 that all the lights on leg 2 will turn off due to being an open circuit?

  • @fritzmiller9792
    @fritzmiller9792 3 วันที่ผ่านมา

    It's called an 'Open Neutral'. And yes, it's the most important connection in any system that has a Neutral. Always identify and connect the neutrals first when doing any kind of switching,controls,loads to minimize problems. If you make a mistake the circuit/logic may not perform correctly but at least if the neutals for the loads are connected the chance of a dead short or a shock are greatly reduced. The neutral is the most important connection.

  • @Shorby99EK
    @Shorby99EK 12 วันที่ผ่านมา +1

    Took my electric company sending 6 guys out over months to figure out they had never tightened my neutral in my meter panel. Whole time they blamed me. Took a new guy to find it and replace it.

    • @morganinspectionservices3840
      @morganinspectionservices3840  11 วันที่ผ่านมา

      Wow! Glad they finally found it. Sometimes those lost neutrals can be difficult to track down.

  • @ecospider5
    @ecospider5 4 หลายเดือนก่อน +1

    I had a shared neutral on 6 plugs in my garage. A wire nut failed and I had a lost neutral in my house but just on 4 plugs. It destroyed a charger before I noticed the problem.

    • @morganinspectionservices3840
      @morganinspectionservices3840  4 หลายเดือนก่อน

      If a neutral becomes disconnected inside the home, then that’s actually a different situation than what this “lost neutral“ video discusses. We typically call your situation an open or disconnected neutral. I have a separate video on that. Sounds like you were already able to solve the problem. However, if you need it, here is a link.
      th-cam.com/video/BVcNnBKfC8Q/w-d-xo.htmlsi=7Gb7tGew_n87GCKy Temperature

    • @ecospider5
      @ecospider5 4 หลายเดือนก่อน

      @morganinspectionservices3840
      That video did a good job describing a lost neural on a 120v circuit. I’m referring to a shared neural. Which acts more like this video. So imagine this.
      You install a 240v circuit breaker. Then you take a 14-3 from the circuit breaker box to an electrical box with 2 receptacles in it. So going into that box you have red, leg1; black, leg2; white, which is a neutral shared between the black and red; then green, your ground.
      Red goes to a 120v plug on the right. Black goes to 120v plug on the left. Both plugs have a pigtail going to the single shared white wire.
      Now disconnect that white wire inside the electrical panel. Plug a lightbulb into both 120v sockets. The energy follows this path.
      Black wire
      Light bulb
      White pig tail
      Second white pigtail going to the other plug
      Second lightbulb
      Red wire
      So you have 240v going through 2 120v lightbulbs. Being protected by a single 240v breaker.
      Now you have your demonstration but inside a house. Fun fun watching things smoke. 😁

  • @childlikefaith7257
    @childlikefaith7257 2 หลายเดือนก่อน

    Great video, I have been having problems, I had the electric company come out they said on their side it good, so I bought a multimeter and sure everything is good until I turn on the microwave on certain days some days the microwave doesn't change anything and other days it makes the fan speed up so I go to the meter pole and leg L-1 is 132 and L-2 is 117 so is the problem on me or electric company and could the bad neutral come from half a mile away i don't share a transformer i live way out in the mountains.

    • @morganinspectionservices3840
      @morganinspectionservices3840  2 หลายเดือนก่อน +1

      You definitely have a lost neutral. However, the symptoms are the same whether it’s on your side or the power company side, so it is impossible to say where the problem is originating. It’s just going to take some investigation. I will tell you this that you would not be the first person I have heard of the power company saying that it’s not their problem and then later discovers that it is.
      And the reason that you have the problem on some days and not on other days, depends on the load distribution of what is currently running in your home. If you have a heavy load running such as air conditioning,clothes dryer, or things like that, then turning on the microwave will have a much smaller effect on the voltage than it will when very few things are running.
      I wish I could help you more, but long distance troubleshooting is very difficult. If you can give me any more information, I will help you as much as possible. I would definitely be interested in hearing what you find.

    • @childlikefaith7257
      @childlikefaith7257 2 หลายเดือนก่อน

      @@morganinspectionservices3840 Thank You so much, and I will give the update of the cure if I ever find it, today I turned everything I could find to bring one leg down, but it would only drop 2 points, the kitchen is on leg 2 so I had hot plates refrigerated, space heater , L 1 at the meter pole showed 120 L-2 showed 124 nothing was running on L-1 but in a few days seems it is usually a hot day it will actually up again. I can measure the house or at the meter pole it's always the same, I was told if the legs are unbalanced at the pole it would be the electric company problem.

    • @childlikefaith7257
      @childlikefaith7257 2 หลายเดือนก่อน

      I have both legs hooked up again in order to find the problem.

  • @robertstonebreaker8394
    @robertstonebreaker8394 10 หลายเดือนก่อน +3

    Good information thank you .

  • @azuokwutempleokwesurueze2042
    @azuokwutempleokwesurueze2042 15 วันที่ผ่านมา

    Someone please respond to me.
    Okay so over the weekend, precisely on Morning My client discovered that the extractor fan in his toilets got burnt, like burnt to the ground and because of that incident, his socket outlets were no longer working,his AC too, there was total black out on most of the lighting circuits while in some other circuit, the lights were just flickering. So I was called upon to troubleshoot what was wrong, my findings are as follows
    - there was current in all of the neutrals in the consumer unit
    - After isolating all the MCBs that controls the lights and leave every other MCB closed, the neutral no longer have current.
    - When I turn off the entire MCBs and turn on the Mains and read each bar connected to the MCBs with the neutral, everything is okay but immediately I turn on the identified MCBs introducing that current into the neutral line, then the readings are no longer accurate
    Note: I’ve checked the phases from the main incomer I.e RYB and also read them with the main incomer neutral . The readings are all perfect.
    PS.. Intermediate level.

    • @morganinspectionservices3840
      @morganinspectionservices3840  14 วันที่ผ่านมา

      You’re obviously not in the US, because some of the terminology I don’t completely understand, but I will try to respond and help. You said, “after isolating all the MCB that control the lights and leave every other MCB closed, the neutral no longer has current.” Just want to clarify. Did you intend to say current or did you mean voltage. If you’re saying that they still have voltage, then you may have an open neutral somewhere in the circuit.

    • @azuokwutempleokwesurueze2042
      @azuokwutempleokwesurueze2042 14 วันที่ผ่านมา

      @ yeah the neutral voltage

  • @peep39
    @peep39 8 วันที่ผ่านมา

    This happened to me and it smoked every 120v transformer and motor in my house, including the hvac blower. What a pain that was. Even the refrigerator fan, and it took me a few months to even realize that one.

    • @morganinspectionservices3840
      @morganinspectionservices3840  8 วันที่ผ่านมา +1

      Wow! Another example of just how much damage this situation can cause. Thanks for watching, and thanks for your input.

  • @childlikefaith7257
    @childlikefaith7257 2 หลายเดือนก่อน

    I kept having a imbalance on the two legs about once a week so I disconnected L 1 and that seems to fix it but now one side of my house has no lights or outlets, and L 2 pulls down to about 115 volts when using the microwave. So will that hurt anything?

    • @morganinspectionservices3840
      @morganinspectionservices3840  2 หลายเดือนก่อน

      115 volts should not be a problem. What are you going to do about having electricity to only half of your house?

    • @childlikefaith7257
      @childlikefaith7257 2 หลายเดือนก่อน

      @@morganinspectionservices3840 I have lived that way for 2 weeks

    • @childlikefaith7257
      @childlikefaith7257 2 หลายเดือนก่อน

      Yesterday I hooked up both legs and everything seems fine but it won't be long.

  • @TheOmengod
    @TheOmengod 4 หลายเดือนก่อน

    Are there any simple uncomplicated tests that I can do in my house to determine whether I have a lost neutral or not? How do I determine if it's on my end or the power companies end?
    All the receptacles I've tested so far are reading around 120 (120 in and out) but my refrigerator won't run. I've plugged the refrigerator into different outlets and it's the same. Tried plugging my Skillet into different outlets around the house and it won't work.
    Thank you!

    • @morganinspectionservices3840
      @morganinspectionservices3840  4 หลายเดือนก่อน +1

      This is a test that I would do in my house, but I will caution you that you must be very careful. I don’t want anyone getting electrocuted. If it were my house, I would remove the cover from the electric panel and measure the voltages at each main lug. Test between one lug and the neutral, and between the other lug and the neutral. See if you have 120 V on both legs of your electrical system. And make sure you have 240 V between the two lugs. If those tests are good, but you do not have 120 V at the outlets in your house, then I would say the problem is inside your house. If you do not have 120 V when measured as described above, then the problem is likely with the power company.

  • @tsclly2377
    @tsclly2377 12 วันที่ผ่านมา

    Partial 'lost neutral' can be caused by having an inadequate ground, such as a grounding rod that is too short and in a rocky base (such as your grounding rod going into dry limestone).. also, this is why fueled gensets have a neutral grounding post..

    • @morganinspectionservices3840
      @morganinspectionservices3840  11 วันที่ผ่านมา

      The lost neutral and poor grounding should have nothing to do with each other. In fact, there’s a lot of older houses still around without a ground rod. Typically the ground lack of a ground rod doesn’t cause a problem - unless there’s a voltage spike or some transient voltage on the powerlines.

  • @johnfalconer4846
    @johnfalconer4846 18 วันที่ผ่านมา

    A really great video, Bravo!

  • @heronimousbrapson863
    @heronimousbrapson863 หลายเดือนก่อน

    The current flow at 3:45 is backward for a balanced load with no neutral current. The diagram shows the neutral current as additive when it should be subtractive.

    • @morganinspectionservices3840
      @morganinspectionservices3840  หลายเดือนก่อน

      I had to go back and watch the video. I’m not following you because I am showing balanced loads on the two legs and then no current flowing on the neutral so I am showing it as subtractive. Please explain a little more and we can discuss this.

  • @rl69782
    @rl69782 6 วันที่ผ่านมา

    I had a bad neutral at the transformer. The symptoms were a voltage difference between the phases. I showed the lineman the voltage differences, but he didn't seem to believe me. Took the bucket up to the transformer and shook the neutral. A shower of sparks confirmed the diagnosis. They replaced the transformer.

  • @MervynPartin
    @MervynPartin 7 วันที่ผ่านมา +1

    Back in the 1970s, at a railway locomotive shed owned by a railway preservation society in Britain, an idiot decided to turn off the yard lights by removing the neutral link on the lighting fuseboard (3-phase 415V supply), with the result that there was an immediate cascade of blown lamps.

  • @tom8592
    @tom8592 6 วันที่ผ่านมา

    It's for this reason I leave my 240 V generator neutral bonded to ground at the generator, when connected to my home, I understand that's not proper, but if the neutral gets lost the ground will take over the job, I've seen a microwave get cooked and a few other items when a neutral failed.

    • @morganinspectionservices3840
      @morganinspectionservices3840  6 วันที่ผ่านมา +1

      But if the ground takes over the job, then you’ve got current running on that ground wire and on the frame/chassis of every grounded device in your house, such as your refrigerator and washing machine. That’s a pretty dangerous thing.

  • @johnzangari3432
    @johnzangari3432 หลายเดือนก่อน

    How would things/symptoms with and without a ground?

    • @morganinspectionservices3840
      @morganinspectionservices3840  หลายเดือนก่อน

      Before I answer, let me ask if you are specifically asking about a ground or a neutral. If you’re asking about a ground, the presence or absence of a ground really does not affect things because the ground and neutral are connected to each other in the electric panel, and with the neutral disconnected upstream of the panel, the ground has very little effect on the situation.

    • @johnzangari3432
      @johnzangari3432 หลายเดือนก่อน

      Your animation showed no ground and I couldn't tell from looking at the mockup if there was a ground. So, by having no ground in the circuit and then having a ground in the circuit yield the same symptoms in both cases?

  • @Andrewthecommentator
    @Andrewthecommentator 12 วันที่ผ่านมา

    Is there no ground on the transmission lines?

  • @maxenielsen
    @maxenielsen 7 วันที่ผ่านมา

    I had to call the power company several times before they fixed a lost neutral external to my house. In the meantime, I lost two ovens, possibly also a third.
    They never took responsibility, telling me everything looked good each time they came out.

  • @keacoq
    @keacoq 12 วันที่ผ่านมา

    Which country are you talking about? What type of installation?

    • @morganinspectionservices3840
      @morganinspectionservices3840  12 วันที่ผ่านมา

      This is the type of system used in the US.

    • @keacoq
      @keacoq 12 วันที่ผ่านมา

      @@morganinspectionservices3840 Problems of that kind are very dependent on country and distribution system, so it is context one needs to know before voewing a video like this.

  • @l.crossjr
    @l.crossjr 11 วันที่ผ่านมา

    Excelent! Thanks for sharing

  • @victorsteerup4582
    @victorsteerup4582 13 วันที่ผ่านมา

    A long time ago, turning my microwave on made the CRT TV picture bigger, opposite of what you would think would happen if they were on the same circuit. Also, this is why the house furnace heater is on one leg, and the refrigerator on another, to balance the load.

    • @morganinspectionservices3840
      @morganinspectionservices3840  13 วันที่ผ่านมา

      Interesting. It is definitely best to split the larger loads between the two legs. Since the largest of loads use both legs because they run 240 V, this is not an issue with those.

  • @Sparky-ww5re
    @Sparky-ww5re 9 หลายเดือนก่อน +1

    Worst case scenario from a floating neutral at the service drop could be electrocution from energized water pipes and metal case appliances with 3 prong plugs, because until I believe the 1978 NEC, a cold water pipe could serve as the sole grounding electrode if at least 10 feet was in contact with the earth, and the connection to the grounding electrode conductor is made within 5 feet where it enters the building, and plastic pipe could have been used to replace a section of corroded metal pipe. Because the neutral and ground are bonded at the main service panel, a double loss of ground and neutral could have lethal consequences. To combat this, a water pipe used as a grounding electrode must be supplemented by grounding electrodes in contact with 8 feet of earth with a resistance not to exceed 25 ohms.

    • @morganinspectionservices3840
      @morganinspectionservices3840  8 หลายเดือนก่อน

      Thanks for the info. I really appreciate it.

    • @okaro6595
      @okaro6595 15 วันที่ผ่านมา

      Water pipes still are bonded and that is for safety. In case of broken neutral you do not want 120 volts between your stove and the water tap. It is safer to raise the potential of the water pipe.

  • @derekness7900
    @derekness7900 15 วันที่ผ่านมา

    I am in the UK and we have 240V. One day the lights in my house went really bright and buzzing. I called the power company and they came. The guy put a volt meter into a socket and I saw 480V on the gauge - scary! It blew my hiking but apart from that everything else was OK amazing

  • @LykeArgy
    @LykeArgy 16 วันที่ผ่านมา

    8:48 damn i really need to go back to school, but why is the resistance higher with 2 lights compared to 3? Isn't light burning cause it has a resistance so if you remove 1 of those resistances how is there more resistance all of a sudden ?

    • @morganinspectionservices3840
      @morganinspectionservices3840  16 วันที่ผ่านมา

      With three lights on you have three equal paths for the current to flow. With only two lights on, you only have two of those paths for current to flow. The more paths, the lower the resistance.

  • @younglavernable
    @younglavernable 9 หลายเดือนก่อน +1

    What is that device you have wired to the lights that is showing voltage.

    • @morganinspectionservices3840
      @morganinspectionservices3840  9 หลายเดือนก่อน +2

      It is a SureTest circuit analyzer. It’s made to plug into a receptacle and measure voltage, voltage drop, and to tell if the circuit is wired properly.

  • @randychapman2309
    @randychapman2309 ปีที่แล้ว

    An open or high resistance neutral conn in the panel or meter can will also cause this. Not always upstream. I've been on many trouble calls where the nipple between the two was glowing because of a loose neutral in the panel. Some were never actually tightened by the original installing electrician.

    • @morganinspectionservices3840
      @morganinspectionservices3840  ปีที่แล้ว

      Great info. I guess when I said upstream of the panel, I actually intended prior to any of the branch circuits, so yes the neutral lug on the panel would certainly qualify. Thanks for the clarification.

    • @randychapman2309
      @randychapman2309 ปีที่แล้ว

      @@morganinspectionservices3840 You are correct though. Probably 90 percent of my trouble calls were due to homeowners allowing trees to grow up into the service wire and either breaking the neutral, or rubbing it in two midspan on the drop. People don't understand that the power company isn't responsible for their negligence.

  • @TheOmengod
    @TheOmengod 4 หลายเดือนก่อน

    I have a pole behind my house with a breaker box and a meter box above it. Two wires run from the pole behind my house out to the main pole on road with the transformer. Am I responsible for everything on the pole behind my house? Thank you!

    • @morganinspectionservices3840
      @morganinspectionservices3840  4 หลายเดือนก่อน +1

      Typically, the homeowner is responsible for everything after where the wires connect to the weather head just before the electric meter. The electric company is responsible for everything just before the connection at or near your electric meter.

    • @TheOmengod
      @TheOmengod 4 หลายเดือนก่อน

      @@morganinspectionservices3840 what about the meter box itself? And the wires that run up the pole from the meter? Ty.

  • @victorbruce5772
    @victorbruce5772 11 วันที่ผ่านมา

    Lost shared neutral backfeeds through load to other circuit when it's breaker is off, energizing wires turned off.

  • @scottcates
    @scottcates 10 หลายเดือนก่อน +2

    thank you

  • @mikelyons5632
    @mikelyons5632 15 วันที่ผ่านมา +1

    Good video, but one bone to pick on the diagram: the two lines are 180° out of phase... so the fake "electrons" (the dots) should be travelling in OPPOSITE direction... not the same. The way you have the "with neutral" shown shows the current meeting up from both sides at the neutral and then just vanishing... this is wrong. You should also have the dots alternating directions on both sides, but line 1 & line 2 always exactly opposite. You could do it without the alternating directions, but you definitely should not show them flowing the same direction as eachother.

    • @Mothara
      @Mothara 15 วันที่ผ่านมา +2

      Well, Ithink he didnt want to overcomplicate things. Since this is AC, there is no mass flow of current.

    • @thedave1771
      @thedave1771 14 วันที่ผ่านมา +1

      I was pondering the same thing, but I’m not sure that it matters for A/C in a meaningful way. I believe that you’re right, but I don’t think understanding the difference matters for a lay-person (me!) to understand the concept, while I expect that this is a lot less confusing of a visualization.

    • @morganinspectionservices3840
      @morganinspectionservices3840  11 วันที่ผ่านมา +1

      You’re absolutely right about the direction of current flow! I just tried to make this as simple to understand as possible. I do appreciate you watching and your feedback.

  • @youtubeaccount5153
    @youtubeaccount5153 2 วันที่ผ่านมา

    Seems like a lot of people here that know their stuff. Don’t worry. I won’t blindly take advice.
    Question, on a 240v plug in the US, typically red and black I believe, does it matter which the red is connected to and which the black is connected to?
    In other words, on a working circuit could I arbitrarily switch the red and black connections?

    • @morganinspectionservices3840
      @morganinspectionservices3840  2 วันที่ผ่านมา +1

      No. It does not matter which one the red is connected to and which one the Black is connected to. All that matters is that the neutral and ground (if there is one) is connected in the right location.

    • @youtubeaccount5153
      @youtubeaccount5153 2 วันที่ผ่านมา

      @ thank you.

  • @BobP3PE
    @BobP3PE 8 หลายเดือนก่อน +1

    Nice job Mike!!!

  • @DanielSmith-lv5ed
    @DanielSmith-lv5ed 10 วันที่ผ่านมา

    A simular thing happens with telescopes.
    As you adjust your comcave lens and other lenses you notice if you blink, you lose the zoom.
    I know, sounds crazy.
    But if you blink when you have multiple lens focused, it also inverts your vision rightside up again.
    Idk

    • @morganinspectionservices3840
      @morganinspectionservices3840  8 วันที่ผ่านมา

      I don’t understand what you’re saying exactly, or how this is similar to the situation in the video.

  • @alzaidi7739
    @alzaidi7739 5 วันที่ผ่านมา

    I heard of this happening at another's house, but never understood how an over voltage could happen.

    • @morganinspectionservices3840
      @morganinspectionservices3840  5 วันที่ผ่านมา

      I hope after watching this video, you have a better understanding.

    • @alzaidi7739
      @alzaidi7739 5 วันที่ผ่านมา

      @@morganinspectionservices3840 I did.

  • @mojorochi
    @mojorochi 12 วันที่ผ่านมา

    I got these symptoms but no electrician was able to diagnose. I had to change many cables hoping the problem went away, and yes, at the end it was a broken cable coming from the street. The more you know

  • @MikeMorgan-s8z
    @MikeMorgan-s8z ปีที่แล้ว +5

    Great animation!!

  • @johng.1703
    @johng.1703 16 วันที่ผ่านมา

    so what you have is a single 240v supply with a centre tap ground voltage divider. when you lose the centre tap ground aka neutral you have what is called a floating neutral.

    • @morganinspectionservices3840
      @morganinspectionservices3840  16 วันที่ผ่านมา

      Yes, I agree with you. A floating neutral is another way to define this situation. I appreciate you watching and I appreciate the comment.

  • @AmericanOne9621
    @AmericanOne9621 หลายเดือนก่อน

    This happened years ago at my brother in laws house. I was open at the lift pole before the service drop ever reached his house. It smoked his television but the utility company never claimed the fault even after they corrected it. The story is longer but I'll leave it at that.

    • @morganinspectionservices3840
      @morganinspectionservices3840  หลายเดือนก่อน

      Thanks for watching and commenting. Yes, a lost neutral can cause a lot of problems. They are dangerous.

  • @franklofarojr.2969
    @franklofarojr.2969 3 หลายเดือนก่อน

    When devices do get overvoltaged, what have people seem happen? I have heard of everything from explode, to still work fine (global/universal devices rated 100-240 for example). I had a friend who had some lights go real bright and a frig smoke with a terrible smell as parts burned (not a full fire thankfully)

    • @morganinspectionservices3840
      @morganinspectionservices3840  3 หลายเดือนก่อน

      I just helped a friend diagnose that he had a lost neutral at his home. He was measuring voltages upwards of 200 V. He that somethings stopped working completely while his home had the lost neutral, but once the lost neutral was corrected, everything worked perfectly. I cannot say that that will be the case every time, but at least in his situation it was.