Automatic Balancing Valves | HVAC | in Urdu/Hindi

แชร์
ฝัง
  • เผยแพร่เมื่อ 13 ก.ย. 2024
  • This is an HVAC conceptual video about the "Automatic Balancing Valves/Hydronic Balancing" regarding the HVAC system valves which are commonly used in hydronic chilled/hot water loops at AHUs and FCUs with accessories. This video is in the Urdu/Hindi language. It is basic learning detailed information for new or fresh engineers or technical field persons. It is also important for HVAC / MEP technical staff to leaning points of view. Here sharing my experience and knowledge that will be helpful to learn & grow for Engineers & Technical staff. If you found anything which is inappropriate then convey it in the comments for my information and rectification in the future.
    Tanweer Ahmed has explained the following in this video:
    1. What is an Automatic Balancing Valve?
    2. Application of an Automatic Balancing Valve.
    3. Function of an Automatic Balancing Valve.
    4. Setting of an Automatic Balancing Valve.
    5. Actuator Automatic Balancing Valve.
    You can watch my videos through the following links:
    1. How airlock and water reduced in pipes?
    Video link: • How airlock and water ...
    2. Where PRV is required as per Pressure in Firefighting System?
    Video link: • Where PRV is required ...
    3. Difference Between Pressure Relief & Pressure Safety Valve
    Video link: • Difference Between Pre...
    4. Difference Between Pressure Reducing & Pressure Restricting Valve
    Video link: • Difference Between Pre...
    5. Converting Pump Head to Pressure or Vise Versa
    Video link: • Converting Pump Head t...
    6. Globe valve Vs Balancing valve
    Video link: • Globe valve Vs Balanci...
    7. Black Steel Pipe Detail | Standard ASTM A53 | Part-1
    Video Link: • Black Steel Pipe Detai...
    8. Black Steel Pipe Detail | Standard ASTM A53 | Part-2
    Video Link: • Black Steel Pipe Detai...
    9. Black Steel Pipe Detail | Standard ASTM A53 | Part-3
    Video Link: • Black Steel Pipe Detai...
    10. Two-way valve of HVAC
    Video Link: • Two-Way Valve of HVAC ...
    11. Three-way valve of HVAC
    Video Link: • Three Way Valve of HVA...
    12. Double Regulating Valve - DRV
    Video Link: • Double Regulating Valv...
    #TanweerAhmed #HVAC #BalancingValve #MEP #Valves #balancing #regulatingvalve #DRV #valve #mep
    = YOU CAN FOLLOW ME ON SOCIAL MEDIA =
    WEBSITE: engineertanwee...
    FACEBOOK: web.facebook.c...
    INSTAGRAM: / tanweersethar
    LINKEDIN: / tanweer-ahmed-00142631
    TH-cam: / tanweerahmed
    TIKTOK: vm.tiktok.com/...
    TELEGRAM GROUP: t.me/hvacmepenggg

ความคิดเห็น • 66

  • @TanweerAhmed
    @TanweerAhmed  3 ปีที่แล้ว

    Double Regulating valve (DRV) link: th-cam.com/video/R8IzybBiSLg/w-d-xo.html

  • @sybergamer1820
    @sybergamer1820 2 ปีที่แล้ว +1

    G bhae sab good effort and thanks

  • @tajkhan-jm9fe
    @tajkhan-jm9fe 2 ปีที่แล้ว +1

    We're nice teaching

  • @qamarkhan5807
    @qamarkhan5807 ปีที่แล้ว +1

    Masha Allah. Very interesting and Very explanatory video.

  • @shahrukhkhan-zd1gb
    @shahrukhkhan-zd1gb 3 ปีที่แล้ว +1

    WA ALAIKUM MUSSALAAM

  • @sajjadansari2772
    @sajjadansari2772 3 ปีที่แล้ว +2

    May Allah increase your knowledge

  • @rajeshmohan7881
    @rajeshmohan7881 2 ปีที่แล้ว +1

    Very very informative Ahmad sahab. Please continue uploading this kind of video.

  • @m.raheel110
    @m.raheel110 22 วันที่ผ่านมา +1

  • @syedkarim1105
    @syedkarim1105 2 ปีที่แล้ว

    Bro, I am your big fan... Ma sha Allah.. You are helping so many. Adil from India

  • @TAHIRHUSSAINMEPINDUSTRY
    @TAHIRHUSSAINMEPINDUSTRY 3 ปีที่แล้ว +2

    Excellent video, I have used these valves. Before purchasing these valves, we are giving our gpm requirements to supplier or manufacturer, then manufacturer adjusting cartridge as per given flow

  • @usmankhalid1806
    @usmankhalid1806 3 ปีที่แล้ว +2

    AsalaamuAlaikum Sir keep it up and keep going upto the mark

  • @shahrukhkhan-zd1gb
    @shahrukhkhan-zd1gb 3 ปีที่แล้ว +1

    WA ALAIKUM MUSSALAAM WA REHMATULLAH HI WA BARAKAATUH

  • @reasmeingor1962
    @reasmeingor1962 2 ปีที่แล้ว +1

    Thanks you for sharing. I have a question regarding alowen the maximum pressure drop of picv. Please advise me. Thanks

  • @ZeeshanAhmad-de3sm
    @ZeeshanAhmad-de3sm 3 ปีที่แล้ว +2

    Pls make a video on PICV, its purpose and uses in hvac

    • @TanweerAhmed
      @TanweerAhmed  3 ปีที่แล้ว +1

      Insha'Allah will make video on it

  • @asifjutt8824
    @asifjutt8824 3 ปีที่แล้ว +2

    👍

  • @fightforreality-kg4pk
    @fightforreality-kg4pk ปีที่แล้ว +1

    How to Testing, Adjusting, Balancing and commissioning..?

  • @abrarahmad3357
    @abrarahmad3357 2 ปีที่แล้ว +1

    Dear sir please make a video on Actuator valve and also differentiate between Balancing valve and Actuator Valve.

  • @merajmoqueem5828
    @merajmoqueem5828 3 ปีที่แล้ว +1

    Types of balancing valve

    • @TanweerAhmed
      @TanweerAhmed  3 ปีที่แล้ว +1

      Watch my video double regulating balancing valve. I have explained types also

  • @waniji5684
    @waniji5684 3 ปีที่แล้ว

    Great job sir

    • @TanweerAhmed
      @TanweerAhmed  3 ปีที่แล้ว

      Thanks

    • @waniji5684
      @waniji5684 3 ปีที่แล้ว +1

      Sir can you help us to solve a isues in fan coil unit ????

    • @TanweerAhmed
      @TanweerAhmed  3 ปีที่แล้ว

      @@waniji5684 What is issue in FCU?

    • @waniji5684
      @waniji5684 3 ปีที่แล้ว +1

      Can i get your WhatsApp contact no
      Actually we are working in a building
      And one part of building we have 5 fcu different capacity
      3 of them is working perfectly
      But last 2 fcu we didn't get proper cooling we are feeling there is water flow issue

    • @TanweerAhmed
      @TanweerAhmed  3 ปีที่แล้ว

      WhatsApp 🇵🇰 +923332472721
      Water balancing issue is there, you should install balancing valve

  • @fahadchandio5606
    @fahadchandio5606 3 ปีที่แล้ว +1

    Dear, Sir why do we use balancing valve on the outlet side.? What if we use that on valve on inlet?

    • @TanweerAhmed
      @TanweerAhmed  3 ปีที่แล้ว

      Placing a balancing valve on the supply side will give you satisfactory results, but choosing the return side can be more effective because it can reduce air and noise problems while achieving better heat transfer across the coils. Moreover, the coils can remain fully flooded and there will be less turbulence due to less free air trapped in the coils. Due to several above benefits, Highly recommends to install the Balancing Valves on the Return side of the coil whenever possible.

  • @Adnankhan-no3ln
    @Adnankhan-no3ln 3 ปีที่แล้ว +1

    Sir PICV valve ur is main kya farq hoa, donu ka tou funtion same hi lag raha ha?

    • @TanweerAhmed
      @TanweerAhmed  3 ปีที่แล้ว

      Let me check and later update you

    • @TanweerAhmed
      @TanweerAhmed  ปีที่แล้ว

      If the temperature actuator is connected with this balancing valve then it is called PICV

  • @sajjadansari2772
    @sajjadansari2772 3 ปีที่แล้ว +2

    Assalamualaikum sir please explain the pump head calculation in easy way if possible

    • @TanweerAhmed
      @TanweerAhmed  3 ปีที่แล้ว

      I have uploaded two videos on hydraulic calculation for pump head. Watch these videos and hope these to be helpful for you. Available in Firefighting playlist

  • @sagarsuryavanshi2393
    @sagarsuryavanshi2393 3 ปีที่แล้ว +1

    U hv kept 2/3 way modulating valve in supply line instead of return...why??? What is the effect???
    Also where to place automatic balancing valve...before or after 2/3 way modulation valve????

    • @TanweerAhmed
      @TanweerAhmed  3 ปีที่แล้ว

      3-way diverting valve shall be install in supply line of AHU or FCU and 2-way valve shall be installed in return line of AHU or FCU

  • @m21543
    @m21543 2 ปีที่แล้ว +1

    Kaha kaam karte hai Bhai aap

  • @mdsadabalam9434
    @mdsadabalam9434 3 ปีที่แล้ว +1

    Why do we use Balance valve In Return line and not in supply line ?

    • @TanweerAhmed
      @TanweerAhmed  3 ปีที่แล้ว +1

      Balancing/2-way/3-way vales are used for control chilled water flow as per design requirements which is installed return pipeline.
      It is normally installed on return because of the following reasons:
      1. ASHRAE Recommendations.
      2. The coil of the unit should be flooded in case the valve is closed.
      3. With a control valve on the return side, the water is at a higher pressure through the coil, reducing off gas, thereby lowering dissolved oxygen content. Lower dissolved oxygen extends equipment life by minimizing the air entrapment.
      4. In coil return line, after AHU/FCU install

    • @mdsadabalam9434
      @mdsadabalam9434 3 ปีที่แล้ว

      @@TanweerAhmed Thanks Taweer sir,You gave me deep explanation.❤️

    • @TanweerAhmed
      @TanweerAhmed  3 ปีที่แล้ว

      @@mdsadabalam9434 Welcome

  • @muhammadnouman519
    @muhammadnouman519 2 ปีที่แล้ว

    Is it same to PICV valve

    • @TanweerAhmed
      @TanweerAhmed  2 ปีที่แล้ว

      Not the same, if the temperature actuator is connected then same as PICV

  • @Excellentvlogsandconsultant407
    @Excellentvlogsandconsultant407 3 ปีที่แล้ว +1

    Sir aslmk

    • @TanweerAhmed
      @TanweerAhmed  3 ปีที่แล้ว

      What do you want to say?

    • @Excellentvlogsandconsultant407
      @Excellentvlogsandconsultant407 3 ปีที่แล้ว +1

      @@TanweerAhmed bhai am from India am working in refrigeration field since 1998 I have come across maximum refregeration appliance,but am not aware about central air conditioning maintenance can u plz share and help if u have a trouble shooting guide on my number 8073540604 jazakallah Khair

    • @TanweerAhmed
      @TanweerAhmed  3 ปีที่แล้ว

      Join my WhatsApp group HVAC|MEP Engineering. Link is given in community tab