Daikin Minisplit Not Cooling Normally. Finding and Repairing a Refrigerant Leak EP92
ฝัง
- เผยแพร่เมื่อ 3 ต.ค. 2024
- Found a Daikin Minisplit was not cooling properly. Weighed the charge and found the unit was short 1 lb and change. I performed a nitrogen pressure test found and repaired the leak. Also how to use a CPS torque wrench.
nighthawkhvac
nighthawk_hvac
Intro and Outro Music
"Alive" by CHOIX
#nighthawkhvac #hvac, #hvaclife, #airconditioning #maintenance, #trane #varitrac #heating, #cooling #refrigerator, #refrigeration #refrigerationcycle #airflow #refrigerant #techlife #installation, #hvachacks, #tools, #furnace, #tech, #electric, #residential, #commercial, #heat, #comfort, #ac, #hvacservice, #hvactools, #repair#toolreviews #fieldpiece #aircon #zoning #honeywell #zonedamper#packageunit #howto #VAV #exhaustfan #Ignitor #trane #TXV #expansionvalve #Intellipak #Trane #Self-contained #Boiler #Coolingtower #noisyinducer #noisyidm #failedIDM #condenserinattic #failedinducerdraftmotor #howtocleancoils #condensercoilcleaning #sparkignitor #nospark #minisplit #mitsubishi #ductless #powerboard #powerboardreplacement #short #outdoortxv #watersourceheatpump ###highpressuretrip#bloweralwayrunning #daikin #torquewrench #sparkignitor #ICM #reversingvalve #nucalgon #iwaveR#iwave - แนวปฏิบัติและการใช้ชีวิต
Thanks for sharing your video. Nice to find an easy fix
Great looking pressure kit
Nice job👍
Nice troubleshooting and repair
Nice job. Thanks for sharing.
Is this a multizone mini split if so how can I recover the Freon into the unit from the main line
Do you not remove the schrader cores? The access to service valves on these units are horrible for a 5/16 Schrader core remover. Is it easier to just leave them in and use the 45 ball valves like you got here?
What torque wrench is that that you're using ?.
I have a question about vacuum and getting under 500 microns. Since you pulled under 500 micron mark, Does it matter that the micron numbers jump back up as your getting ready to charge the system?
As long as it stays well below 1000 microns you’re good.
@@NighthawkHVAC Thank you for that 😀
My recovery machine is a home depot bucket
I have three daikin heads. They all connect to the compressor outside. My two bedroom heads are perfect and blow ice cold. My living room only blows ice cold when they top it off with refrigerant . A week later it goes from blowing warm air for a while then back to cool air but never ice cold like the bedrooms. They came out snd said they found a leak. But a week later here we are and the same thing is happening. What is going on !!!
probably like an electrical issue. did they fix it ?
Daikins are forever leaking
This is clearly installation error, daikin didn’t make those flare joints..