Daikin Minisplit Not Cooling Normally. Finding and Repairing a Refrigerant Leak EP92

แชร์
ฝัง
  • เผยแพร่เมื่อ 3 ต.ค. 2024
  • Found a Daikin Minisplit was not cooling properly. Weighed the charge and found the unit was short 1 lb and change. I performed a nitrogen pressure test found and repaired the leak. Also how to use a CPS torque wrench.
    nighthawkhvac
    nighthawk_hvac
    Intro and Outro Music
    "Alive" by CHOIX
    #nighthawkhvac #hvac, #hvaclife, #airconditioning #maintenance, #trane #varitrac #heating, #cooling #refrigerator, #refrigeration #refrigerationcycle #airflow #refrigerant #techlife #installation, #hvachacks, #tools, #furnace, #tech, #electric, #residential, #commercial, #heat, #comfort, #ac, #hvacservice, #hvactools, #repair#toolreviews #fieldpiece #aircon #zoning #honeywell #zonedamper#packageunit #howto #VAV #exhaustfan #Ignitor #trane #TXV #expansionvalve #Intellipak #Trane #Self-contained #Boiler #Coolingtower #noisyinducer #noisyidm #failedIDM #condenserinattic #failedinducerdraftmotor #howtocleancoils #condensercoilcleaning #sparkignitor #nospark #minisplit #mitsubishi #ductless #powerboard #powerboardreplacement #short #outdoortxv #watersourceheatpump ###highpressuretrip#bloweralwayrunning #daikin #torquewrench #sparkignitor #ICM #reversingvalve #nucalgon #iwaveR#iwave
  • แนวปฏิบัติและการใช้ชีวิต

ความคิดเห็น • 16

  • @nethoncho
    @nethoncho 2 ปีที่แล้ว +1

    Thanks for sharing your video. Nice to find an easy fix

  • @williamhawkes7194
    @williamhawkes7194 2 ปีที่แล้ว +1

    Great looking pressure kit

  • @scottk0623
    @scottk0623 ปีที่แล้ว +1

    Nice job👍

  • @tonydelgrego2906
    @tonydelgrego2906 2 ปีที่แล้ว

    Nice troubleshooting and repair

  • @deanmartin1966
    @deanmartin1966 2 ปีที่แล้ว

    Nice job. Thanks for sharing.

  • @washinton2008
    @washinton2008 หลายเดือนก่อน

    Is this a multizone mini split if so how can I recover the Freon into the unit from the main line

  • @NTalache
    @NTalache ปีที่แล้ว

    Do you not remove the schrader cores? The access to service valves on these units are horrible for a 5/16 Schrader core remover. Is it easier to just leave them in and use the 45 ball valves like you got here?

  • @sameermohammed3949
    @sameermohammed3949 ปีที่แล้ว

    What torque wrench is that that you're using ?.

  • @eddiegomez3628
    @eddiegomez3628 2 ปีที่แล้ว +1

    I have a question about vacuum and getting under 500 microns. Since you pulled under 500 micron mark, Does it matter that the micron numbers jump back up as your getting ready to charge the system?

    • @NighthawkHVAC
      @NighthawkHVAC  2 ปีที่แล้ว +1

      As long as it stays well below 1000 microns you’re good.

    • @eddiegomez3628
      @eddiegomez3628 2 ปีที่แล้ว

      @@NighthawkHVAC Thank you for that 😀

  • @sergiodoordie319
    @sergiodoordie319 8 หลายเดือนก่อน

    My recovery machine is a home depot bucket

  • @kellsieevans3847
    @kellsieevans3847 ปีที่แล้ว

    I have three daikin heads. They all connect to the compressor outside. My two bedroom heads are perfect and blow ice cold. My living room only blows ice cold when they top it off with refrigerant . A week later it goes from blowing warm air for a while then back to cool air but never ice cold like the bedrooms. They came out snd said they found a leak. But a week later here we are and the same thing is happening. What is going on !!!

    • @bolinsapark
      @bolinsapark ปีที่แล้ว

      probably like an electrical issue. did they fix it ?

  • @Thomas-iq8zk
    @Thomas-iq8zk 2 ปีที่แล้ว +2

    Daikins are forever leaking

    • @jonjensen6036
      @jonjensen6036 ปีที่แล้ว +1

      This is clearly installation error, daikin didn’t make those flare joints..