Branch Circuit, Multiwire, NEC 2020 - [210.4], (19min:38sec)

แชร์
ฝัง
  • เผยแพร่เมื่อ 4 ก.พ. 2025

ความคิดเห็น • 321

  • @maz_uwu
    @maz_uwu 9 วันที่ผ่านมา +1

    This is the most boring entertaining thing on TH-cam. Thoroughly enjoyed it

    • @MikeHoltNEC
      @MikeHoltNEC  9 วันที่ผ่านมา

      Watch MikeHolt.com/Fundamentals and have more boring entertainment!

  • @OwensandCompany
    @OwensandCompany 4 ปีที่แล้ว +53

    I was working at a hospital, a maintenance electrician was working nearby. He opened a junction box and unbundled the neutrals while the circuit was energized. There was a nice POP ....... A few minutes later the Director of the Laboratory walked out into the hallway and asked why the power to a section of his lab just went out. At the end of the day, there was $120,000 worth of damaged equipment...It was a multi-wire branch circuit.

    • @MikeHoltNEC
      @MikeHoltNEC  4 ปีที่แล้ว +23

      Oh my gosh, this is the number one story on this topic! I'll share this in my next class.

    • @OwensandCompany
      @OwensandCompany 4 ปีที่แล้ว +6

      @@MikeHoltNEC when, during this video, Laboratory’s were mentioned specifically, I just laughed because of how practical the information was to me because of this experience. It’s a very real issue with that circuit. Edison didn’t have to worry about electronics in the 1890’s.

    • @defytyrantsofmississippi2198
      @defytyrantsofmississippi2198 2 ปีที่แล้ว +1

      Why not just flip the breaker to the off position before disconnecting the neutral on any type of branch circuit, multi-wire or otherwise?
      If not you always run the risk of having an energized neutral situation. I’ve seen energized neutrals on regular branch circuits where the power would come through the load and into the connecting neutral.

    • @krakenwoodfloorservicemcma5975
      @krakenwoodfloorservicemcma5975 2 ปีที่แล้ว

      120K is pretty bad but I got you beat. Working as a locomotive technician, we had a mixup on current software. Manager had me put the wrong control package on a locomotive and we burned up $750,000 worth of equipment.

    • @SwingboyPA
      @SwingboyPA 2 ปีที่แล้ว +5

      @@defytyrantsofmississippi2198 The point is that you don't necessarily know that a neutral is being used by another circuit unless you put an amp meter on it after you turn off the circuit that you want to work on.
      Even worse (though VERY unlikely), before you turn off the breaker you work on, you see 10 amps on the hot and 10 amps on the neutral ...BUT this is a neutral that is also being fed by 2 other circuits that are on opposite poles and also have 10 amps on each. The 10 amps on opposite poles cancel each other out so that your amp meter would read 0 amps after you turn off the breaker that you want to work on. Not much you can do about that other than measure amperage on the neutral while turning off each of the other breakers ...and nobody is going to do that.
      I work extensively in old houses and I have seen a few examples of more than 2 hots using a single neutral. I've seen things like 5 hots using 3 neutrals through various junction boxes. This sort of thing happens because an 'electrician' just randomly connects circuits in an old fuse box that gets turned into a junction box without maintaining the paired status of each circuit's hot(s) and neutral.
      THIS IS JUST ANOTHER REASON THAT AFCI AND GFCI PROTECTION IS SO IMPORTANT.

  • @bigtuck2009
    @bigtuck2009 2 ปีที่แล้ว +3

    3 mins in and my head hurts. Salute to you guys

    • @MikeHoltNEC
      @MikeHoltNEC  2 ปีที่แล้ว +2

      Suck it up... watch it again1

  • @crowlsyong
    @crowlsyong 3 ปีที่แล้ว +12

    Mike Holt gets me excited about electricity. Man I just love his vibe. Have a good day!

    • @MikeHoltNEC
      @MikeHoltNEC  3 ปีที่แล้ว +4

      Thanks, but I'm probably more excited than you are when I'm teaching!

    • @Femur15
      @Femur15 2 ปีที่แล้ว

      Yes he does. No way could anyone could get bored in his sessions.

  • @nyinfamous2k2
    @nyinfamous2k2 3 ปีที่แล้ว +11

    This guy is awesome, I would have paid much more attention if all my teachers were these good.

    • @MikeHoltNEC
      @MikeHoltNEC  3 ปีที่แล้ว +5

      Thank you, have a nice day and God Bless

    • @johnkellyjones1877
      @johnkellyjones1877 2 ปีที่แล้ว

      i sceptical of most people on youtube till they prove to be creditable but first time i watch his video i believed everything he had said. he knows code book forwards and backswards.he covers too much material for my old brain but thats on me

  • @neilbrookins8428
    @neilbrookins8428 4 ปีที่แล้ว +33

    Great video. Very helpful. One thing that may cause people to connect multi wire branch circuits wrong is the use of tandem breakers. If you connect the two hots to two tandem breakers you will over load the neutral because tandem breakers are same leg. But many people assume that any adjacent breakers are always opposite leg. Tandem is an exception to that.
    Also I was surprised that no one mentioned that shared neutral is not compatible with gfci. That’s a good reason not to do it.

    • @jeffhenson5471
      @jeffhenson5471 3 ปีที่แล้ว

      I guess if the 2 loads combined don't exceed the amperage of a single breaker, it wouldn't be an issue. An example would be a refrigerator and a dishwasher on a 20 amp tamden breaker. If the dishwasher pulls 10 amps and the fridge pulls 5 amps, the combined load on the neutral would just be 15 amps. But in that case the 2 could have been combined on a single 20 amp breaker and not a mwbc.

    • @SwingboyPA
      @SwingboyPA 2 ปีที่แล้ว

      @@jeffhenson5471 Not OK. The same argument could be made for ANY two wires on the same phase. Don't ever do this. The reason that you don't do it is because you don't know what the potential load is.. for example, what if someone plugs in a toaster oven with an extension cord going to the same receptacle the refrigerator is plugged into because there weren't enough counter receptacles?

    • @SwingboyPA
      @SwingboyPA 2 ปีที่แล้ว +1

      I'd like to reword this. If you connect the two hots to the two circuits on the same tandem breaker, then the neutral will be on the same leg (phase). However, if you use one switch from each of two separate tandem breakers, each hot would be on a different phase.
      That said, you still have not met the requirement that the two circuit breakers be tied together with a handle tie.
      There are devices called "quad breakers" which are essentially two tandem breakers bonded together in one case with the two inner breakers connected with a handle tie and the two outer breakers connected with the handle tie thereby allowing for (2) separate 240v circuits.
      In this case, if my description is poorly worded remember that "a picture is worth a thousand words", so simply Google "quad circuit breaker" and click on 'images'.
      In a full panel that accepts tandem breakers, these can be really handy when you're adding something like an electric dryer because they can come and configurations like 30 amps / 20 amps. :-)
      Not trying to be mean or arrogant here, but for new folks, this might be surprising information that is really helpful. :-)

    • @neilbrookins8428
      @neilbrookins8428 2 ปีที่แล้ว +2

      @@SwingboyPA yes tandem breakers can be very useful when used correctly. Your example of adding a dryer circuit is helpful. The problem is I’ve seen too many older houses with tandem used incorrectly by someone who didn’t understand what they were doing. A thorough inspection will often find various electrical problems even when the work was done by a professional.

    • @SwingboyPA
      @SwingboyPA 2 ปีที่แล้ว +2

      @@neilbrookins8428 yes, I run into that all the time. Almost all of my work is residential in houses over 100 years old ... So layers of work over layers of work. :-p
      I am constantly using double pole AFCI circuit breakers -literally as diagnostic tools- to find *additional* shared neutrals on circuits that are already shared neutral circuits.... Like I'm making sketch plans of people's houses with color coded circuits for shared neutrals and shared hots. LoL
      It's always nice to 'meet' another electrician who is thorough and thoughtful Neil. :-)

  • @timrxn5414
    @timrxn5414 8 หลายเดือนก่อน +3

    NOW I understand why I got zapped after killing a breaker and going into a box. Multi branch circuit but no handle-tie. I’m a diy’er but trying to learn what is ACTUALLY going on and not be just a hold-my-beer hack. Thanks for your excellent videos

  • @PowderMill
    @PowderMill 2 ปีที่แล้ว +2

    👍🏼 Thank you Mike and Company !!
    As a firefighter/paramedic who relies on your videos for extra knowledge, I must say you are a real lifesaver.

  • @marcfruchtman9473
    @marcfruchtman9473 2 ปีที่แล้ว +1

    This is such a great video. I just happened upon it because I was looking to help someone who was interested in multi-wire branch circuits and their dangers.
    As someone else commented below, these Multi-wire branch circuits are not compatible with GFCI... which thankfully means that over time, we will see fewer and fewer multi-wire branch circuits in the residential world as the NEC increases the requirements for more GFCI in the home.

    • @SwingboyPA
      @SwingboyPA 2 ปีที่แล้ว

      True, although any multi branch circuit must be put on a DP circuit breaker ...and I always suggest using a GFCI or AFCI DP breaker.
      As far as I know at this time that I'm writing, there are not yet Dual Function double pole circuit breakers ...but I predict there will be.
      Remember that a grounded receptacle (ie 3-prong) on a non-grounded circuit must be BOTH AFCI and GFCI protected. For now, with a shared neutral (multibranch) circuit, that means a double pole AFCI circuit breaker and a GFCI at the specific location.
      Given the many old houses have hard steel work boxes with beveled corners, I hope the industry will save us from installing GFCI receptacles in to overly stuffed wallcases and eventually provide double pole DF breakers.

    • @marcfruchtman9473
      @marcfruchtman9473 2 ปีที่แล้ว

      @@SwingboyPA I am not sure how it would be possible for a standard GFCI breaker to work in this configuration. Wouldn't any significant unbalanced load trip the GFCI?

    • @SwingboyPA
      @SwingboyPA 2 ปีที่แล้ว +1

      @@marcfruchtman9473 If by "standard" you mean "single pole", then yes, you are correct: it would trip. That's why you must use a DP (double pole) AFCI circuit breaker on a multi-branch circuit if you want to protect the entirety of both circuits. Same goes if you wanted to use GFCI.
      Make sense?

    • @marcfruchtman9473
      @marcfruchtman9473 2 ปีที่แล้ว

      @@SwingboyPA I have been trying to find a manual / users guide (for any 2 pole GFCI breaker) that states that it accepts / allows multiwire configuration. So, if you happen to have a link to a manual...

    • @SwingboyPA
      @SwingboyPA 2 ปีที่แล้ว

      @@marcfruchtman9473 You don't need a manual, it works because the breaker looks at both hots and justifies that against the neutral. AFCI or GFCI double pole breaker on a multiwire circuit...it will work. I've been an electrician for about 35 years and work almost exclusively in old homes in Philadelphia, PA. I use AFCI, GFCI, and Dual Function circuit breakers all the time on knob and tube circuits ...which are often shared neutral circuits. I'm not trying to be arrogant, but troubleshooting and remediating old wiring happens to be my specialty because I do it all the time. The guy who trained me is the same; we both really enjoy the niche of working in old houses so this is something I know very well. :-)
      If it doesn't work, there is something else wrong. ...And again, this is why I use AFCI and GFCI circuit breakers as a tool as much as a protective device.

  • @neutrodyne
    @neutrodyne 11 หลายเดือนก่อน

    What a great video. It explains in detail what every electrician should know about Multiwire circuits.

    • @MikeHoltNEC
      @MikeHoltNEC  11 หลายเดือนก่อน

      Thanks!

  • @rafaelcastro6466
    @rafaelcastro6466 3 ปีที่แล้ว +3

    Thank you Mike for all the technical support, information-Advice that you share! 👏

    • @MikeHoltNEC
      @MikeHoltNEC  3 ปีที่แล้ว +3

      You are most welcome.

    • @dianeprovencio5866
      @dianeprovencio5866 ปีที่แล้ว

      @@MikeHoltNEC Hello can you please recommend multiwire branch circuit quiz worksheet and answer book? Also can you please recommend a tutor who can teach circuits and conduit?

  • @TGUlricksen
    @TGUlricksen 4 หลายเดือนก่อน

    I love how Mike handles these people. I wish I could do this gracefully. This panel of people are cough They’re everywhere.

  • @visiblepulse
    @visiblepulse 2 ปีที่แล้ว +8

    Last year I opened a ceiling gang box to tap in for a doorbell transformer. When I removed the wire nut from the neutral, the home run white lifted. In a nearby study, a 6-outlet adapter with surge protection started sparking and smoking. I could not pull it out of the outlet as it was screwed in. I reconnected the neutral and was then able to remove the adapter and drop it outside while it continued to melt. The shared neutral condition had presented the surge protect circuit with over 120v.

  • @surfride101
    @surfride101 9 หลายเดือนก่อน +2

    I have wired a dozen or so homes ages ago for my father a gc. I messed up several jobs by overloading the neutral with breaker/leg misplacement. It was eventually caught, no damage done and corrected. Neutrals are anything but neutral, it should be called something else, like return, neutral minimizes the danger, much like interchangeably using grounding and bonding; that too is a deadly mistake. Just ask the families of the dead burned alive in the enclosed metallic bus stops with metallic grated benches... On a three phase panel, the 220 leg is orange and labeled stinger; a novice should head the messages; dont F with this. I digress; too many improperly trained, improper supervised and lazy inspectors create deadly hazards; like I did. Appreciate you!

  • @SwingboyPA
    @SwingboyPA 2 ปีที่แล้ว +4

    If you are just beginning to learn this stuff, I want to add 2 things:
    1). At 1:01, Mike does not finish the sentence: The equal voltage must be between each phase conductor *and the neutral*. If you're measuring voltage between 2 phases (as in the example), there is no "equal" to be had.
    Also worth mentioning:
    2). Single pole AFCI and GFCI circuit breakers will trip if you put them on either or both poles. I've seen people try to pigtail the neutral to go to each of 2 SP breakers; and that won't work. You must use a double pole breaker -and here's the best part: if you're working in an old house, you might have an extra hot on that circuit that trips the DP breaker. Like a hot sharing a neutral with another hot ...that is already sharing a neutral. This is serious and must be investigated because that means that at least 2 of the hots are on the same phase.
    I've also seen a GFCI receptacle where someone tried to spit the neutral at the GFCI or after it (instead of before it). The load side of the GFCI must use only the load from one phase and all the neutral current must be on that phase. That wasn't part of Mike's talk, but new folks have to know that this is also an important part of understanding the ramifications in a GFCI and AFCI world.
    I use AFCI and GFCI protection on shared neutral (multiwire branch circuits) knob & tube all the time as a diagnostic tool to find extra neutrals all the time ...because sometimes a neutral doesn't get shared where you can see it; it happens in a junction box somewhere else in the building.
    All that said, Mike is an awesome teacher and we're lucky to have him!

    • @marcfruchtman9473
      @marcfruchtman9473 2 ปีที่แล้ว +1

      Wow... what an interesting idea... to use the GFCI as a diagnostic tool to determine shared neutrals! Do you have some sort of "kit" you built that plugs in, or do you wire that up each time?

    • @SwingboyPA
      @SwingboyPA 2 ปีที่แล้ว +1

      @@marcfruchtman9473 You don't need a kit; I do it in the panel with a GFCI or DF circuit breaker.
      Keep in mind that if you try this 'locally' (like at a particular receptacle location) you might miss whatever happened *before* the location that you are testing. So it's always best to use a circuit breaker to test the entire circuit.

  • @commercialsparky7776
    @commercialsparky7776 3 ปีที่แล้ว +1

    The legend himself with another amazing video

    • @MikeHoltNEC
      @MikeHoltNEC  3 ปีที่แล้ว +2

      Thank you, it's you guys that drive me to excellence.

  • @DellAnderson
    @DellAnderson 4 ปีที่แล้ว +13

    I can vouch for the Murphy's law of multi-wire circuits. Had a variant of such a circuit in a 240/120V all electric motorhome. Some 120V receptacles had 3 volts, others had 208 volts. Finally found an open neutral in the opposite end of the 40 foot vehicle (it was a loosened critical neutral crimp connector!), but too late to save the $2000+ RV fridge. :-(

    • @barryomahony4983
      @barryomahony4983 3 ปีที่แล้ว +3

      I've had the most problems with open neutrals caused by the utility company. It's like some of the linemen don't think it's as important to securely tighten the split bolt on the neutral as they do on the hots.

  • @TRYtoHELPyou
    @TRYtoHELPyou 4 ปีที่แล้ว +7

    The Murphy's law thing made me lol, thanks for that.

  • @NipkowDisk
    @NipkowDisk 4 ปีที่แล้ว +7

    My house (built in 1978) has two MW circuits. Neither of them had handle ties for the breakers (they weren't even next to each other although they were on separate legs) AND the circuit to the laundry room used the device yoke for dividing it up!!. Needless to say, I fixed that very quickly.
    Neutral integrity is an absolute with MW circuits. Period.
    Reckon I'm showing my age here, but I also refer to these as "Edison" circuits.

  • @5_fun_facts123
    @5_fun_facts123 4 ปีที่แล้ว +9

    Ran into this today. Two separate breakers, one neutral.

    • @chrisE815
      @chrisE815 4 ปีที่แล้ว

      Brilliant

  • @theamericanhandyman3213
    @theamericanhandyman3213 2 ปีที่แล้ว +1

    I learned a lot at first it was hard to understand your English but I did catch on with the pictures I didn't even know that existed that answers a lot of questions really awesome video

  • @leisurelanemhp3853
    @leisurelanemhp3853 3 ปีที่แล้ว +1

    watched the whole show... excellent

  • @krakenwoodfloorservicemcma5975
    @krakenwoodfloorservicemcma5975 2 ปีที่แล้ว

    Thank you for the great instruction and positive outlook on health and life! They are equally important in my opinion!

  • @fayiznalu8411
    @fayiznalu8411 2 หลายเดือนก่อน

    Good refresher video. Thank you

  • @kahlil4745
    @kahlil4745 ปีที่แล้ว +1

    It's not only the panel you have to pay attention to but the phase as well. Some guys will land the ungrounded conductors on single pole breakers on the same phase which would make the unbalanced load additive on the neutral. So if you shut off one breaker thinking you are safe on that neutral you might have another hot wire out there still sending power back on it as well.

  • @dannylee5588
    @dannylee5588 4 ปีที่แล้ว +14

    I'm currently doing a remodel on a house. In two different locations I isolated the breaker and turned it off. But I was still reading a small amount of voltage 24 volts I believe. And one case I was able to find the other breaker and completely turn it off. Looks like this is a multi-branch but the breakers are not connected with each other. Very dangerous.

    • @richardprice5978
      @richardprice5978 3 ปีที่แล้ว +1

      yep common in older houses 🏡 as i have the same experience as you and it can start a fire 🔥 and damage equipment or hurt you ie 40v to 260v but not stable at that voltage as it was grounding funny ect. and its also common to see little to no safety bonding/grounding or improper neutral bonding

    • @phillipfessenden7705
      @phillipfessenden7705 3 ปีที่แล้ว

      I absolutely hate this rule. But I do understand the importance of if.

  • @moepow8160
    @moepow8160 3 ปีที่แล้ว +3

    As a home owner, any time an electrician works on my house...I unplug Everything. Not practical in larger commercial buildings, but I'm not losing my 80 inch TV.
    Multiple branch circuit should be tags somehow as a MB circuit. In aerospace industry we of course used wire diagrams that were consistent and you were trained how to read & understand them, and tag outs used when working with any circuit. Most overloads and shocks came from In-Shop repair were we worked on components on the bench.

    • @paaao
      @paaao 2 ปีที่แล้ว

      MB ckts are no longer allowed in commercial bldgs

  • @johncrunk8038
    @johncrunk8038 8 หลายเดือนก่อน +1

    Thanks for verifying something that I knew all along. I found one of these miswired circuits in my house and fixed it, but didn't relate it to the code.

  • @gregparker8349
    @gregparker8349 4 ปีที่แล้ว +5

    I have made it a habit to place a current clamp around any neutral conductor before disconnecting or lifting the neutral conductor from its connection when working in commercial or industrial settings. The best practice is to trace the neutral and be aware not every circuit you are encountering was installed to code!

    • @georgekolos5255
      @georgekolos5255 2 ปีที่แล้ว

      100% good practice!
      I learned to call these network circuits.
      Is this correct terminology? Not an electrician by trade but know more about electricity than most electricians I work with. + I never see these breakers even if on opposite legs tied together that would trip or turn them off together!

    • @paaao
      @paaao 2 ปีที่แล้ว

      If a multi wire branch ckt has equal load on each, you will read 0 amps on the shared portion of the neutral. So, be careful. The current cancels, which is why the whole thing works when using different sides of the split phase. If you share a neutral for two hots on the same phase, the current will add together.

    • @krakenwoodfloorservicemcma5975
      @krakenwoodfloorservicemcma5975 2 ปีที่แล้ว +1

      That is good thinking. Good way to trace down a neutral too.

    • @SwingboyPA
      @SwingboyPA 2 ปีที่แล้ว

      @@paaao Yeah, but if the hot measures (say) 5 amps and the neutral measures anything else (including 0 amps per your example), you'll know there is either a low grade short or a shared neutral. If the amperage changes when you turn off the breaker for the circuit you want to work on, you'll know it's a shared neutral. :-)
      Greg's method is a good one and most folks don't bother.

  • @tedlahm5740
    @tedlahm5740 9 หลายเดือนก่อน +1

    Exactly. Kirchhoff’s voltage law for series circuits. The load with the HIGHEST resistance (ohms) will have the highest (proportional) voltage drop.

  • @alfredofuentes8959
    @alfredofuentes8959 4 ปีที่แล้ว +7

    I just had an issue with a damaged receptacle on a 3 wire circuit, the receptacle was being use as a juction to feed the other receptacles on the other rooms, when I disconnected the neutral , the other room receptacles increased the voltage to 180 v. And the neutral going to the load was backfeding 108 v intermittently . Got me thinking about how easy one can damage equipment with this wirings Wich I guess it was normal in the old days.

    • @richardprice5978
      @richardprice5978 3 ปีที่แล้ว

      common in the older houses ( per-1990's ) iv live in sadly, and yes it can start fires 🔥 and or damage equipment or hurt someone

  • @ph33lix
    @ph33lix ปีที่แล้ว +1

    Fascinating forum!

  • @nickcheatle3927
    @nickcheatle3927 2 ปีที่แล้ว +1

    I'd like to add a note to Graphic 2. This rule is easily looked over when dealing with 120/240, 120/208, or 277/480. Where this becomes and issue is a High Leg Delta panel.

  • @mohameddoumbouya7367
    @mohameddoumbouya7367 3 ปีที่แล้ว +1

    This helped thank you Mr.Holt!!!

  • @snap-off5383
    @snap-off5383 2 ปีที่แล้ว

    Learned to tie the groups together when traversing a box. Thanks.

    • @MikeHoltNEC
      @MikeHoltNEC  2 ปีที่แล้ว

      I don't understand your comment.

    • @snap-off5383
      @snap-off5383 2 ปีที่แล้ว

      @@MikeHoltNEC 14:32 210.4d Probably my poor English.

  • @garza1367
    @garza1367 ปีที่แล้ว +1

    Where can I find more info/detail about the phase cancellation

  • @hippo-potamus
    @hippo-potamus 2 ปีที่แล้ว +3

    And all that DANGER just to save a neutral wire run.

  • @marcogodinez5412
    @marcogodinez5412 4 ปีที่แล้ว +1

    Thank you for your videos, very helpful!.

    • @MikeHoltNEC
      @MikeHoltNEC  4 ปีที่แล้ว +1

      You are most welcome, God Bless.

  • @jeffsmith8737
    @jeffsmith8737 3 ปีที่แล้ว +15

    I’m sure the guy with his manager buddy appreciates the shout out for their insurance fraud at the Best Buy lightning incident!

    • @benjamintorres9211
      @benjamintorres9211 3 ปีที่แล้ว +3

      Glad I’m not the only one that caught that 😂😂😂

    • @bigtuck2009
      @bigtuck2009 2 ปีที่แล้ว

      Lol 😆

  • @crack1270
    @crack1270 3 ปีที่แล้ว +6

    That makes me wonder how many tandem breakers i see are actually 20 & 15 amp multiwire branch circuits that are wired with 12/3 or 14/3

  • @Chris_In_Texas
    @Chris_In_Texas 4 ปีที่แล้ว +5

    Just a quick comment at 12:48 the wire is labeled 12-2 With ground however its clearly a 12-3 with ground. Just a typo in your graphic.

    • @MikeHoltNEC
      @MikeHoltNEC  4 ปีที่แล้ว +3

      You are 100% right! Wow, probably been that way for twenty years... Thanks.

    • @oomps_
      @oomps_ 4 ปีที่แล้ว +2

      She noticed it, I'm sure they'll change.

  • @alejandrosantiago4596
    @alejandrosantiago4596 ปีที่แล้ว +1

    crazy people! I am glad u are ok and safe.

  • @barryomahony4983
    @barryomahony4983 3 ปีที่แล้ว +1

    14:20 Line-to-line loads are permitted if the breakers are common trip 210.4(C) Exception 2.

  • @georgenarso3148
    @georgenarso3148 4 ปีที่แล้ว +2

    I've always wire the Multi-wire branch breakers as " Utilization equipment" only and saved myself headaches.

  • @sparkyjerred419
    @sparkyjerred419 4 ปีที่แล้ว +5

    I love the Murphy's law calculation

  • @globedimmer8286
    @globedimmer8286 3 ปีที่แล้ว

    Great video contents! This is where the handy electric circuit phrase comes. Before you should a gun, you have to know which end to place against your shoulder. Before you do anything electricity, you must understand what a circuit is…

  • @Bob.W.
    @Bob.W. 2 ปีที่แล้ว

    They were called appliance circuits years ago. Cheap way to run one cable to a kitchen to get two circuits. Much easier to understand when they were both in one double gang box with two receptacles, or one split receptacle, as opposed to all over the place.

  • @mechelb4158
    @mechelb4158 3 ปีที่แล้ว +1

    @mike holt
    Thanks!
    But by putting a clamp on meter to test the neutral in MBC won't help much cause there won't be a load...
    If a even load..

    • @MikeHoltNEC
      @MikeHoltNEC  3 ปีที่แล้ว +1

      A MBC neutral will always have current if the load are on.

    • @mechelb4158
      @mechelb4158 3 ปีที่แล้ว

      @@MikeHoltNEC of they are perfectly balanced??
      15 on 1 15 on 2, 0 on neutral..

    • @MikeHoltNEC
      @MikeHoltNEC  3 ปีที่แล้ว

      @@mechelb4158 I understand the 'theory' but let's get real, this is never going to happen.

    • @mechelb4158
      @mechelb4158 3 ปีที่แล้ว

      @@MikeHoltNEC possible!
      Somebody runs 2 heaters on a mbc...
      Possible to pls make a video on linear vs non linear.
      Thanks!

    • @MikeHoltNEC
      @MikeHoltNEC  3 ปีที่แล้ว

      @@mechelb4158 What percentage of the time do you think that when loads are on, the neutral conductor would show '0.00A?' I give it almost zero, but I'm interested in your thoughts.

  • @ronblack7870
    @ronblack7870 6 หลายเดือนก่อน +1

    so they should have mentioned that half breakers can't use this scheme. some manufacturers have half breakers where 1 breaker position has 2 breakers but they are the same phase so the neutral will be additive.

  • @Dolph-nv8oo
    @Dolph-nv8oo ปีที่แล้ว

    On the visual with one duplex above the other at 11:51 the 12/3 cable is marked 12/2. Just saying...

  • @CurtWelch
    @CurtWelch 2 ปีที่แล้ว

    I'm just learning about these multiwire circuits because I ran into one this week in our 1970s commercial building and I wanted to understand the code. Boy, the wording of the code is so confusing and non-obvious. When first learning this, a general introduction would be so useful, but can't be found in the code. A general intro should start something like this:
    Multiwire branch circuits are a cost-saving wiring technique that shares one common neutral wire between multiple branch circuits. This technique saves wiring costs but introduces a handful of dangerous side effects, including potential confusion, safety, and equipment damage risks.
    Multiwire branch circuits require each branch to be on different phase legs. Doing this guarantees their shared ground will never need to carry a higher current than any of the branch hot wires, which is why it is possible to use the same ampacity wires for all the current-carrying wires of the multiwire branch circuit. Preventing the need to use a larger neural, is where the cost savings happen, so this is only permitted by the code when the branches are on different phase legs.

    • @MikeHoltNEC
      @MikeHoltNEC  2 ปีที่แล้ว +1

      Excellent! I'll add to my book and TH-cam intro.

    • @SwingboyPA
      @SwingboyPA 2 ปีที่แล้ว +1

      The thing about the NEC is that it isn't meant to be an explanation of electrical techniques. It's a reference book for people who are already trained professionals, not a "how to" book. I'm not trying to be an ass, it's just important for people to understand. Mike (and others) have produced materials on "how to" that refer to techniques that you can use to comply with the NEC.

  • @lindazjunk
    @lindazjunk 2 ปีที่แล้ว

    I have my fan running and my LED recessed lights on. When I turn off the fan, on it's own switch, my LED lights also turn off momentarily (and then come back on). Why??? I have a switch for my fan, and a switch next to it for my LED recessed lights in my bedroom. Any insight would be appreciated.

    • @MikeHoltNEC
      @MikeHoltNEC  2 ปีที่แล้ว

      I suggest you try different LED lights, not the same brand.

  • @shieldcracker
    @shieldcracker 4 ปีที่แล้ว +1

    Looking at a the definition of article 100 we could infer that a 3-wire delta circuit and a 4-wire delta circuit are not MW circuits because in the former there is no neutral, and in the latter there are no L-N voltages. Yet a corner grounded delta could be considered a multi wire circuit because it has a balanced L-N voltages. Food for thought.

    • @MikeHoltNEC
      @MikeHoltNEC  4 ปีที่แล้ว +1

      Hum... never considered this angle, but you are right!

  • @jaypryor7322
    @jaypryor7322 2 ปีที่แล้ว

    I have observed in a wood shop 3 phase machinery where to save money in electricity the owner wired each phase to a different shop.

  • @NoferTrunions
    @NoferTrunions 3 ปีที่แล้ว +3

    The MWBC is unsafe. Period. This is because it cannot pass a one component failure analysis. A robust electrical system must be able to tolerate at least a single failure without catastrophic results, a single failure includes a severed or shorted wire.
    What is troublesome is that this brings the entire NEC Code into question: what other approved methods are dangerous?

    • @MikeHoltNEC
      @MikeHoltNEC  3 ปีที่แล้ว

      That's an instresting perspective... excellent.

    • @NoferTrunions
      @NoferTrunions 3 ปีที่แล้ว +2

      ​@@MikeHoltNEC I mean the NEC is all about nail plates, conduit, etc., devices and methods to protect and make the system survive attacks. And then NEC allows MWBC. Ironically, 2 neutrals in the same slot is safer than the MWBC - at least with 2 neutrals you know _Danger._
      But this video and situation reminds me of a perplexing situation in a small, old home with knob and tube wiring - you may find it interesting and may already know what the problem is.
      The house had 3 circuits done in K&T.
      Evidently back in the 30's, the house was wired on a single leg and they must have gotten creative.
      Balancing the circuits between legs on a new breaker panel would have lead to.... fire - without tripping a breaker.
      I have no theory how they could have wired things for this to happen.

    • @sglacf
      @sglacf 3 ปีที่แล้ว

      NEC was not meant to be used as design material, it was written to prevent fires

  • @gfy2979
    @gfy2979 ปีที่แล้ว

    really fascinating how the alternating phases can cancel out and not overload a neutral

  • @B81Mack
    @B81Mack ปีที่แล้ว

    Correct me if I'm wrong, but in theory, if the neutral leg to a 120/240 sub-panel from the main panel was lost, every branch circuit from that sub-panel would become 240 volts with the entire neutral bar becoming the shared pathway.

    • @MikeHoltNEC
      @MikeHoltNEC  ปีที่แล้ว

      Nope, please watch the video again.

    • @B81Mack
      @B81Mack ปีที่แล้ว

      ​@@MikeHoltNEC, please think about it, I believe I'm correct. Obviously an unlikely circumstance though but the same premise.

    • @B81Mack
      @B81Mack ปีที่แล้ว

      ​@@MikeHoltNEC, thank you for your reply. You have a great channel.

    • @B81Mack
      @B81Mack ปีที่แล้ว

      ​@@MikeHoltNEC, now that I think about it, there would probably just be a voltage imbalance on the L1 branches versus the L2 branches relative to the different load on each leg. Similar to what you showed with the different appliances in your example. With no neutral, only a dead short (0 ohms) would result in 240 on the opposing leg.

    • @MikeHoltNEC
      @MikeHoltNEC  ปีที่แล้ว

      This is a math problem, so work out the following to see if you are right. The load on Line 1 is 40A and the Load on Line 2 is 60A. What is the voltage from Line 1 to Neutral and Line 2 to Neutral? It's not 120V and it's not 240V.

  • @marknissenjr_A.Z.Electric
    @marknissenjr_A.Z.Electric หลายเดือนก่อน

    Can we get an explanation on why someone can not use a gfci or afci breaker on a multi wire circuit? Please

    • @MikeHoltNEC
      @MikeHoltNEC  หลายเดือนก่อน

      Of course you can see www.homedepot.com/p/Siemens-Type-QAF-20-Amp-Double-Pole-Combination-AFCI-Circuit-Breaker-Q220AFCP/202253104[www.homedepot.com/p/Square-D-Homeline-20-Amp-2-Pole-GFCI-Circuit-Breaker-HOM220GFIC/204355351](www.homedepot.com/p/Square-D-Homeline-20-Amp-2-Pole-GFCI-Circuit-Breaker-HOM220GFIC/204355351)

  • @georgekolos5255
    @georgekolos5255 2 ปีที่แล้ว

    Need to see a video on 3 phase and high or wild legs in a panel. Seen a lot of electricians give 240 to a lot of 120 equipment!

  • @ronblack7870
    @ronblack7870 6 หลายเดือนก่อน

    what about 120/208 v 3 phase panels . can you have a multiphase branch here where the phases are 120 degrees apart instead of 180 ? so not all the neutral current cancels out

    • @MikeHoltNEC
      @MikeHoltNEC  6 หลายเดือนก่อน

      See: th-cam.com/video/bVartPwUDNw/w-d-xo.html
      The neutral current for a three-phase 4-wire circuit is determined by the formula i_{n=\sqrt{I_{L1}^{2}+I_{L2}^{2}+I_{L3}^{2}}-(I_{1}-I_{2})-(I_{1}\times L_{3}-I_{2}\times L_{3})\).

  • @mikemiceli8574
    @mikemiceli8574 3 ปีที่แล้ว +2

    How do you find the shared neutral wire after the fact when they weren't grouped initially?

    • @MikeHoltNEC
      @MikeHoltNEC  3 ปีที่แล้ว

      Post your question on MikeHolt.com/Forum.

    • @SwingboyPA
      @SwingboyPA 2 ปีที่แล้ว +1

      I use an AFCI circuit breaker as a diagnostic tool.
      1). When a new AFCI trips, I leave everything connected and turn off all circuit breakers except the one that is tripping. If it stays on, I suspect another breaker was feeding current to that (now AFCI protected) circuit. I then turn on breakers 1 at a time to see if additional current trips the AFCI breaker by adding current to the neutral. Using an amp meter, I can measure changes in the neutral as well.
      2). Often the problem is 2 (or more) hots sharing 2 (or sometimes more) neutrals.
      Now I identify the (new) AFCI neutral in the panel and put an *amp meter on it* instead of leaving it open since the neutral will still conduct electricity from the other circuit(s) even when the AFCI is in the off position. I turn off all breakers, and then turn them on 1 at a time to see if I get any current on the neutral -thereby showing that the neutral is shared with whatever circuit I just turned on -and thereby also avoiding an open neutral.
      (At this point obviously I can use a double pole AFCI breaker to protect both circuits with a pigtail to the (2) separate neutrals)

  • @iampuzzleman282
    @iampuzzleman282 2 ปีที่แล้ว

    It seems a multi branch circuit involving two 20 amp outlets with a shared neutral going back to a double pole breaker is not really too dedicated circuits. I guess because the first outlet affectively has 120V going across it and the flow continues across to the other circuit in the neutral receives no current. Not sure I understand how 240 V is involved here. So basically the second outlet is Sharing power with the first outlet where the returning circuit off the second outlet flows back to the Second Circuit breaker to complete the loop.

  • @alunroberts1439
    @alunroberts1439 2 ปีที่แล้ว +1

    At 6:50 your numbers are not right. The hair driver is a resistive load the TV is not a resistive load as it don't use a transformer in side for the power drop it is a switch mode PSU. If L1 and L2 wired threw a hair driver or coffee pot as there using resistive load elements it will act like just a resistor So L1 threw the 12 to 20 ohm like a wire wound resistor then the TV. I am a spark in the UK and also a AV engineer my first work was in the TV trade. Strapping as you use as most of your 2 or 3 wire is from a center tapped transformer. To give you your 110 120 for you to get 230 240. We in the UK use most of the time TNCS. We're are neutral is grounded at the star side also at the home.

  • @jeffreystroman2811
    @jeffreystroman2811 4 ปีที่แล้ว +7

    It's amazing how few who work with electrical wiring actually understand this phenomenon of the Edison 3 wire system. To the point where when I wish to communicate my skill set I just say, "did you know when both branches are balanced the neutral current gets nulled out, down to zero." It wasn't until I was 40, looking at a panel and saw three 10 gauge wires heading to an apartment and it hit me. Why isn't the neutral bigger, won't it have twice the current? It was at this moment my teacher from RETS (radio-electronics-television-service) stopped by. I spent 3 days wrapping my mind around what's happening literally inside the wire nut where it goes from 3 wire to 4 wire.

    • @markgigiel2722
      @markgigiel2722 4 ปีที่แล้ว +2

      WOW, a RETS grad. I went to RETS in Nutley and graduated in 1979. We did a lot of partying in the parking lot, but I learned a lot and did very well. Retired now. It's a small world.

    • @ambull80
      @ambull80 3 ปีที่แล้ว

      Same here. Catonsville, MD. 1999

  • @AzeveidoMateus
    @AzeveidoMateus 9 หลายเดือนก่อน

    I don’t understand how even a properly wired multiwire branch circuit doesn’t overload the neutral. If two separate components are sharing a return path wouldn’t that double the current on that return path? Can someone explain this to me?

    • @MikeHoltNEC
      @MikeHoltNEC  9 หลายเดือนก่อน

      If Line 1 is 15A and Line 2 is 10A, then the neutral will be 5A. Basic electrical theory.

    • @surferdude642
      @surferdude642 9 หลายเดือนก่อน +1

      Think of a 240v circuit, there's no neutral because the load is always balanced when they are on opposite poles. When one side is supplying power, the other is returning and vise versa at 60 Hz. When a neutral wire is used, you have two 120v circuits. When line 1 is 15A and Line 2 is 5A, the returning electricity will be split between the opposite Line and the neutral. The opposite Line will return 10A, and the unbalanced load of 5A is returned on the neutral.

    • @MikeHoltNEC
      @MikeHoltNEC  8 หลายเดือนก่อน +1

      @@surferdude642 Exactly. Example: the heating of the circuit wires of a 240V 15A circuit is the same as the heating of multiwire circuit wires where L1 - 15A, L2 - 10A, and Neutral is 5A. Using the formula I squared R. That's why the neutral doesn't count as a current-carrying wire. Note: Heat is a function of current, not voltage.

  • @stevebrule6172
    @stevebrule6172 2 ปีที่แล้ว

    I have a tricky multiple choice question, hopefully someone with more knowledge can help me out
    A White/grey wire in a feeder circuit ________:
    A)Be bonded or have a circuit breaker
    B)Is the largest wire in that circuit
    C)Should not have a voltage to ground
    My notes:
    On the main panel, neutral is connected to the bar that is bonded with the panel, the green grounding wire is also connected to the same bar. (so does that mean the answer is A?)
    In the sub panel, the neutral wire is connected to the neutral bar which is isolated from the metal box with plastic between them, the Green grounding wire is separated and is connected to its own bar that is bonded to the sub panel box.
    In the circuit that this question applies to,
    --------- “The neutral wire is going to be sized larger than the Green grounding wire”
    (But that doesn’t mean it’s the LARGEST in the circuit right? Because the two hot wire could be the same size)
    --------"The neutral should have no potential difference(voltage) to the ground" (does that mean the answer is C?)
    (But that doesn’t mean it’s the LARGEST in the circuit right? Because the two hot wire could be the same size)

  • @RyanElectrician
    @RyanElectrician 10 หลายเดือนก่อน

    What if the GROUNDED conductor in the field is taking off. Is it the same if it's taken off in the panel???

    • @MikeHoltNEC
      @MikeHoltNEC  10 หลายเดือนก่อน

      What? Please just use the term 'neutral.'

  • @iampuzzleman282
    @iampuzzleman282 2 ปีที่แล้ว

    Are multi branch circuits good for to replace audiophile grade dedicated circuits

  • @uptowngregory6947
    @uptowngregory6947 4 ปีที่แล้ว +2

    We have used this on lights. 6 lights, 3 on one switch, 3 on another

  • @justinchamberlain3443
    @justinchamberlain3443 4 ปีที่แล้ว +1

    10:39 From a contractors stand point mbc’s are what’s most common

  • @hgbugalou
    @hgbugalou 3 ปีที่แล้ว +1

    I don't understand why anyone would choose to share a neutral in a residential split phase system like this. How much money are you really saving versus how many headaches and future problems you create. Just run 1 neutral per 1 circuit brewker and keep it fool proof. This is particularly true when dealing with home owners versus like a facilities manager. And with that, There is more of a valid argument with 3 phase for this, especially in large buildings.

  • @OthmanAlikhan
    @OthmanAlikhan 3 ปีที่แล้ว +1

    Thanks for the video =)

  • @jimthewindmillman9317
    @jimthewindmillman9317 3 ปีที่แล้ว

    I have a question about my inverter off grid.. and I am also connected to utility open ground on the inverter standard of the inverter question is about grounding

    • @MikeHoltNEC
      @MikeHoltNEC  3 ปีที่แล้ว

      Please contact a local Solar contractor.

  • @blackcrow573
    @blackcrow573 9 หลายเดือนก่อน

    Unless the two hot goes in the same terminal box with share neutral

  • @grumpycat_1
    @grumpycat_1 4 ปีที่แล้ว +14

    I used to run them everywhere... but my reading of the AFCI requirements make that prohibitively expensive for residential work. You have to either buy a 2 pole AFCI breaker (100-250$ per breaker or run EMT all to "save" a single 12g or 14g THHN wire....) Not a huge fan of handle ties b/c they seem to get removed when the grouped single pole breakers inevitably get moved. If there is a way to run them that makes sense (cost wise) and follow the AFCI requirements i would love to know.

    • @simmcowaPang122
      @simmcowaPang122 4 ปีที่แล้ว +3

      210.12 (A)(4) says that you can use a AFCI rated receptacle at the beginning of a branch circuit, up to 50ft for 14g and 70ft for 12g. Hope that helps.

    • @grumpycat_1
      @grumpycat_1 3 ปีที่แล้ว +1

      @@simmcowaPang122 I wish that was an interpretation I could hold I could be wrong (please let me know if I am)
      but 2019 was the last time I did heavy research into it.... So if its outdated PLEASE correct me
      I know there are jurisdictions that are allowing this (including my home jurisdiction). But other then using the single pole "Eaton Combination" I just don't see it actually satisfying 210.12(A)(4).
      Eaton have a listed "standard" breaker/AFCI 1st receptacle that when used in combination DO satisfy the requirements but Im not clear how ANY standard breaker/NMC/AFCI receptacle could.
      I believe (with strong evidence) that any "standard" breaker/NMC/AFCI 1st receptacle does not satisfy 240(A)(4) and allowing it is a miss interpretation on behalf of my jurisdiction and others.
      My reading/interpretation of the exceptions that would satisfy code would fall under sections 210.12(A)(4)... The only UL listed product that would meet the poorly worded code that are commercially available to allow use under this section (Specifically under 240(A)(4)) would be the "Eaton Combination" ...
      The Eaton combination's UL listing meets the requirements of 210.12(A)(4) as a "System Combination". In other words only when a specific Eaton only (non afci) breaker and the Eaton only AFCI device tested and listed as a combination as a listed system qualifies.
      I only install Square D for a number of reason so for me its not an option... Even though it would MAY pass inspection... and I would generally have to argue it up the chain... which makes the "cost savings" moot. I dont agree with the code wording and think the AFCI requirements are gov't mandated corporate welfare.. But I follow the code as written (in my interpretation) b/c in order to hold this strong ANTI-Post 1997 Code changes turned mfg sponsored marketing nonsense position and advocate for changes I think its a moral imperative to.
      We need to CHANGE the code its nonsense not find workarounds that will pass but DONT (in my interpretation) actually satisfy the code... The code is the problem and needs to have common sense safety not corporate sales as its primary purpose and that unfortunately has been the evolution of the code since about (at the latest) 2008... and I would argue 1997 was the last pure "safety" focused code. Its been downhill corporate shilling since.

    • @grumpycat_1
      @grumpycat_1 3 ปีที่แล้ว +1

      We used to run a standard 2pole breaker on 12/3 romex to GFCI 1st receptacles on the A leg and B leg and it worked great, was efficient use of materials and was less cost. in materials/labor and saved customers money... It worked well, safely and was highly efficient .. that changed when the AFCI requirements came into effect for Small Appliance Branch Circuits...
      In my opinion these code changes were made to sell MORE copper 2x 12/2s and 2x 10times more expensive AFCI/GFCI Combo breakers. There is no good argument for requiring AFCI protection on Small appliance circuits that already had GFCI requirements... its was all about SALES in the name of safety and is total corruption.
      Ohio for instance SPECIFICALLY EXCLUDES small appliance branch circuits from AFCI requirements b/c the justification for requiring them is ridiculous. The Qty., placement and amperage requirements for Small appliance branch circuits and the UL listing requirements for small appliance already address the supposed "dangers" used to justify AFCI requirements in the 1st place.
      Ohio has the exception to specifically allow the use of MWBCs to meet the requirements to provide the large numbers of separate Small appliance branch circuits in a safe and efficient way and to cost effectively allow installations that are arguably safer due to provided many separate 20amp circuits that will likely have large inductive and resistive loads simultaneously operated while connected to them.
      Arguably NMC(romex) does not require AFCI protection from the 1st receptacle to the service panel when installed properly according to codes as old as '95... . the only good argument is "at and after"the 1st receptacle.... so that crappy electronics and extension cords plugged into garbage quality back stabbed $0.99 duplex receptacles dont burn your house down...
      That was the ENTIRE stated premise for AFCI in the 1st place... It was not to protect branch circuit wiring from the panel to the 1st outlet. But of course now the code panels position is that "the tech exists so now you need AFCI to protect that "dangerous" NMC from undesired effect of arcing" Nmc that didn't become dangerous when properly sized and installed until 2008....
      Its not NMC (Romex) its the devices including and running from the 1st downstream receptacle and the equipment plugged into them are the problem..
      The problem IS NOT properly sized and installed Romex from the 1st outlet to the service panel... The code panel is making that argument now in the name of selling product as corporate shills.

  • @iampuzzleman282
    @iampuzzleman282 2 ปีที่แล้ว

    Does a multiwire branch make sense for the audio file system to reduce noise??

  • @arealmaintenanceandrepairl1103
    @arealmaintenanceandrepairl1103 2 ปีที่แล้ว

    So the only issue is when removing a neutral? If you were to relocate or add a outlet or light off a 10/2 12/2 you will be ok just be sure not to mess with the bundle of commons?

  • @larryroyovitz7829
    @larryroyovitz7829 ปีที่แล้ว

    I came here because I have a critical loads, 120v sub panel, where I want to bring just ONE more circuit over to the subpanel, but it's part of a multiwire branch circuit. And the second circuit, I don't want to bring to the sub panel - nor could I anyway, as it's a 120v panel, thus on a single phase. I'm dead in the water over this last circuit unfortunately.

  • @arealmaintenanceandrepairl1103
    @arealmaintenanceandrepairl1103 2 ปีที่แล้ว

    So on these circuits are they all ran with 3 wire or 2 wire and then they are able to split off into their own 2 wires…

    • @MikeHoltNEC
      @MikeHoltNEC  2 ปีที่แล้ว

      Please watch the video again.

  • @johnrackiewicz286
    @johnrackiewicz286 ปีที่แล้ว

    Why is this service referred to as single phase when you repeatedly refer to two phases?

    • @MikeHoltNEC
      @MikeHoltNEC  ปีที่แล้ว

      Single-phase is different than a reference to 'two phase conductors.' Watch MikeHolt.com/Systems

  • @VolpeInCalze
    @VolpeInCalze 4 ปีที่แล้ว +1

    Found a violation of 210.4D at my parents place when I upgraded the panel. 2 20A breakers feeding the garage sub panel. Not good!

  • @josephsteffen2378
    @josephsteffen2378 2 ปีที่แล้ว +1

    WOW! Disconnect the Neutral and you just made a 240V circuit. "Let's be practical, not perfect." Hey, just trying to earn a living...not make a killing.

  • @kefrenferrer6777
    @kefrenferrer6777 3 ปีที่แล้ว

    I think multiwire circuit is not planned for that kind of charges, but for apliances working as a whole like a panel for control of pumps, specific machine, or even small subpanels, or similar loads as suburban light distribution, for residencial distribution as in this video is better and marked individual monofasic circuits.

  • @NoferTrunions
    @NoferTrunions 3 ปีที่แล้ว +2

    NEC should require shared commons tagged or marked as such in panels.

    • @vlad1889
      @vlad1889 3 ปีที่แล้ว

      Well, the hots for that said nuetral should be on a 2-pole breaker or locked breakers so you should easily figure it out. If you can't you shouldn't be there in the first place.

    • @NoferTrunions
      @NoferTrunions 3 ปีที่แล้ว

      @@vlad1889 Nothing should be left for "figuring" when it comes to these types of circuits - the risk/danger is too high. An NEC Official red label or tag would make it crystal clear. NOTE: Don't forget, it is an assumption that the panel is wired correctly.

    • @georgekolos5255
      @georgekolos5255 2 ปีที่แล้ว

      That would be top perfect. And most O see do not have the 2 hots on two breakers common tripping. And some panels minies can be installed that the 2 in one breakers come off just on leg!
      On way too many where diy electricians do to add on circuits and they think all the neutrals are OK to tie together anywhere 🙄

  • @iwant2meetaliens
    @iwant2meetaliens ปีที่แล้ว

    Switching power supplies, which have become more and more common these days, tend to produce odd order harmonics that dont always cancel the way a nice symmetrical sine wave does.

    • @MikeHoltNEC
      @MikeHoltNEC  ปีที่แล้ว

      True, but with ‘tuning filters’ in the equipment, we don’t have the issues we had 20 years ago.

  • @sergeig685
    @sergeig685 2 ปีที่แล้ว

    Can someone please explain the problem of working on circuit A while circuit B is still on? How does the shared neutral make a difference? ALL of the neutrals are shared in the entire house since they are ALL joined together to the same neutral bar. The need for opposite poles and the open neutral make perfect sense, but this part about the need for simultaneous disconnect makes no sense at all.

    • @MikeHoltNEC
      @MikeHoltNEC  2 ปีที่แล้ว

      Post your question on MikeHolt.com/Forum, you'll get a timely response.

    • @Now_lets_get_this_straight
      @Now_lets_get_this_straight 2 ปีที่แล้ว

      Let’s see if I got this right, and see if it makes sense to you. If you turn off circuit A at the breaker to work on an outlet, and circuit B has something running on it, the neutral of the outlet in circuit A has current going thru it since it is shared with the neutral in circuit B. The other neutrals in the house are not completing the circuit for circuit A & B.

    • @sergeig685
      @sergeig685 2 ปีที่แล้ว

      @@Now_lets_get_this_straight Right. You can still touch the neutral on A/B just fine under load, as long as you don't disconnect its return to the panel and become in series with it.

    • @Now_lets_get_this_straight
      @Now_lets_get_this_straight 2 ปีที่แล้ว

      @@sergeig685 so your saying if you are grounded somehow, and you touch the neutral with A off and B has a load running, you won’t get shocked? How much you get shocked is determined whether you make a better return path than the neutral wire. It will take the path of least resistance.

    • @sergeig685
      @sergeig685 2 ปีที่แล้ว

      @@Now_lets_get_this_straight If your panel is correctly wired, the neutral has the same potential as the ground wire. Your neutral and ground bars are connected together, and to a grounding rod to top it off. Thus the potential between your grounded body and the neutral is exactly 0V. So, no, you won't get electrocuted. Now if the neutral was disconnected somewhere down the line then, yes, that would create a non-zero potential and shock you.
      "The pass of least resistance" is absolutely INCORRECT. If you connect several loads in parallel, with resistance of 10, 100, and 1000 Ohms, the current will flow through ALL of them. The difference is how much current. Current = V / R

  • @omargarcia4401
    @omargarcia4401 3 ปีที่แล้ว +1

    Computers have electronic boards and are non linear loads, technically the code prohibits the use of MWBC on circuits where the majority of the load is non linear. Code doesn’t care if your going to lose a bid. Do it right.

  • @pavel29jenny
    @pavel29jenny 3 ปีที่แล้ว

    We work at the museum write know: that building was built at 1920... with remodeling in 1930, 1950, 1970, and so on... imagine what a mess you have??! So: we move a neutral wire in the j’box, and in the 5 foot 8 inch pipe, the neutral wire is terns in wire nut, (!!) and that sheared neutral is discontinuing the circuit that was connected to it, and that cost Musium a $2,500 copy machine... just because there was a 120V outlet that was connected to that light circuit!! If you guys don’t believe me, I have a video about it! That’s a great show! I can tell you that!

    • @MikeHoltNEC
      @MikeHoltNEC  3 ปีที่แล้ว

      Please email me (Mike@MikeHolt.com) the video!

  • @jolyonwelsh9834
    @jolyonwelsh9834 4 ปีที่แล้ว +1

    In 3 phase Wye multiwire branch circuits with nonlinear loads, one can create high harmonic currents in the neutral. Can anyone elaborate on this?

    • @MikeHoltNEC
      @MikeHoltNEC  4 ปีที่แล้ว

      This is no longer an issue in todays wiring because 'tuning filters' have been added to equipment. But do a search for harmonics to gain more information.

  • @josephmelluso7414
    @josephmelluso7414 2 ปีที่แล้ว

    Is it now illegal to share neutral

    • @MikeHoltNEC
      @MikeHoltNEC  2 ปีที่แล้ว

      Of course not. Why do you ask?

    • @josephmelluso7414
      @josephmelluso7414 2 ปีที่แล้ว +1

      @@MikeHoltNEC thank you Mike, I didn’t think it was either, but In talking with some other fellow tradesmen (electrician) they were saying that it it illegal to share neutrals now, however they could not show me where they found that or heard that from. Thank you for the clarification

  • @garbo8962
    @garbo8962 3 ปีที่แล้ว +3

    Do not get creative. Thanks for that quote.Have homeowners to so called engineers get creative. Best one was on a Friday afternoon and project engineer said o yea you guys have to hurry up and get a 50 amp line ran for a tech coming in Monday morning to start up a new machine. Told him that would require triple time to have it done on Sunday. He said just grab power from the 3 hanging 20 amp cords hanging from ceiling. Say what. He said 20 + 20 + 20= 60 amps. Broke his heart when we told him you can not parallel #12 wire. 3 of us made 3 days pay for working that Sunday. Told him if you have the money we always have the time.

  • @oscar27ization
    @oscar27ization 3 ปีที่แล้ว

    Why can’t u remove the neutral on load first? Cause it’s load and ur voltage it’s on without a return?

    • @MikeHoltNEC
      @MikeHoltNEC  3 ปีที่แล้ว

      That is a different topic, not related to the discussion of a multiwire neutral circuit.

  • @johnnymalicoat754
    @johnnymalicoat754 4 ปีที่แล้ว +6

    Ive smoked a few pieces of equipment before i figured out what i was going on.

  • @frankymoreno8935
    @frankymoreno8935 4 ปีที่แล้ว +1

    So you can share a neutral on a 120/240 panel? I thought you're not supposed to on a single phase 'cause you would over load your neutral.

    • @kc9scott
      @kc9scott 4 ปีที่แล้ว +1

      You can share a neutral as long as the two hots are on opposite phases. The main point that I take from this video is that code now (and sensibly so) requires the two breakers to at least be handle-tied together. Even better would be to use a 240 breaker. When I bought my house in 1989, I saw that it had a multiwire branch circuit, but the two individual breakers happened to be placed on the same phase, which was not a good thing, since it would cause an overloaded neutral. Luckily there was no detectable damage to the wires.

  • @stormand
    @stormand 2 ปีที่แล้ว

    "the people on the TV will start moving very fast...." LOLOLOLOL

    • @MikeHoltNEC
      @MikeHoltNEC  2 ปีที่แล้ว

      'for a very short amount of time...' LOL

  • @nadermostafa3878
    @nadermostafa3878 ปีที่แล้ว

    So I guess even after watching this video - what is the actual benefit of using a multi-wire branch circuit, other than initial cost savings? Seems like all it causes is problems, confusion, and damage down the line. Just cause you can...doesn't mean you should.

    • @MikeHoltNEC
      @MikeHoltNEC  ปีที่แล้ว

      If the NEC permits a practice, then it's fine with me. I would always run a multiwire circuit because it saves money and reduces the circuit voltage drop.

  • @arlindkrasniqi3315
    @arlindkrasniqi3315 3 ปีที่แล้ว

    Pardon my ignorance but what's the difference electrically between this and the neutrals all connected to the neutral bar in the main panel.

    • @MikeHoltNEC
      @MikeHoltNEC  3 ปีที่แล้ว

      You need to watch the video again. A multiwire branch circuit always starts at the panel.

    • @johnkruton9708
      @johnkruton9708 2 ปีที่แล้ว

      I don’t think you understand that the L1 and L2 are 180 degrees opposite on the current side. That’s what AC alternating current stands for. So IF you are doing this type of circuit for design/build reasons you are sharing a neutral. Depending on loads you may or may not be seeing current go back to the panel. If you are not going to do this you are running another home run in 2 physical places. I used this in my own home to supply power to back to back side opposite wall that 1 leg is microwave and gas stove top loads and other is TV entertainment system. Used a 10/3 cable instead of 2 12/3. Easier and it was all the space I had in panel. Breaker is a double pole 20amp. Heavier wire is due to length and less voltage drop

  • @benmeuninck7410
    @benmeuninck7410 4 ปีที่แล้ว

    u know in the pic wire is labeled wrong is not 12-2 it's 12-3

    • @MikeHoltNEC
      @MikeHoltNEC  4 ปีที่แล้ว

      You are right! We'll fix for next video, thanks.

  • @joshuafrank9084
    @joshuafrank9084 3 ปีที่แล้ว

    Confused, you say the code states its ok to use multiwire branch circuits for office furnishings but nec code 605.9(d) states there not permitted? Am I misinterpreting this? Thanks

    • @MikeHoltNEC
      @MikeHoltNEC  3 ปีที่แล้ว

      I never discussed Office Furnishing, but 605.9(D) only applies to the internal wiring of Freestanding-Type Office Furnishings, Cord- and Plug-Connected. Freestanding-Type Office Furnishings, Cord- and Plug-Connected is wired by the manufacturer, not the electrician. So your comment is a moot point. Right?

    • @joshuafrank9084
      @joshuafrank9084 3 ปีที่แล้ว

      @@MikeHoltNEC Thank you for the reply, sorry for the confusion, it was Erik that was talking about office cubicles. And your response answered my question , I did not know that code reference only applied to the internal wiring. Thank you again!

  • @MarkLawry
    @MarkLawry 4 ปีที่แล้ว +9

    "Do not get creative."