Dangers of Multiwire Circuits 28.6

แชร์
ฝัง
  • เผยแพร่เมื่อ 25 ส.ค. 2024
  • “Multiwire” branch-circuits are advantageous in that they save money! But multiwire branch-circuits also present some unique hazards if not installed properly.
    Find out what you need to know about the dangers inherent with multiwire branch-circuits by watching the video where Mike and the team discuss the theory behind these circuits.
    This video is extracted from Mike Holt's Understanding Electrical Theory Library www.mikeholt.c.... For additional information call 888.632.2633.
    For decades, Mike Holt Enterprises has been the go-to resource for electrical training. Our mission is to empower electrical professionals like you to master the Code, excel in exams📝, and elevate your electrical knowledge..
    👉 Explore Exam Preparation Tips and Training at www.MikeHolt.c...
    🚀 Find Electrical CEU courses at www.MikeHolt.c...
    ⬆️ Level Up your school's electrical training program with Mike Holt Enterprises at www.MikeHolt.c...
    Whether you're gearing up for an exam or looking to enhance your electrical knowledge, we've got you covered. We offer instructor and curriculum support, a variety of continuing education options, free videos, graphics, and a wealth of valuable resources.
    📌 Stay Connected:
    / mikeholtenterprises
    / mikeholtenterprises
    / mike-holt-enterprises-inc
    🔗 www.mikeholt.com
    ✅ Don't miss out on the latest updates and exclusive content. Subscribe to this channel now - Click here to subscribe: / @mikeholtnec .

ความคิดเห็น • 18

  • @steven7650
    @steven7650 5 หลายเดือนก่อน +11

    I enjoy mikes law, The most expensive piece of equipment will sacrifice itself to save the least costly.

  • @mj625
    @mj625 5 หลายเดือนก่อน +4

    I'm thankful I learned these lessons early in my career. Not everyone does, and, unfortunately, this is why we have code changes that tend to bring everyone down to the lowest common denominator in skill set, while raising the cost of electrical installs in the process.

  • @bretgreen5314
    @bretgreen5314 2 หลายเดือนก่อน +1

    Thank you Mr. Holt. I will add E^2 over RP to my P over IE, and E over IR memorized formulas. I think of all the times I have taken the long way around.

  • @paulconvery680
    @paulconvery680 3 หลายเดือนก่อน +1

    The infamous brown neutral.
    Ran across a few of those and THAT is just one of the many examples of why the code updates are so important.
    Thanks for sharing, Mike and Co.

  • @theseattlegreen1871
    @theseattlegreen1871 4 หลายเดือนก่อน +2

    Great information Gentlemen

  • @33electric33
    @33electric33 4 หลายเดือนก่อน +2

    I've seen this a couple different times where the main neutral at the electrical panel or meter socket became so corroded at the termination point that it drops connection. Equipment burns up real quick.

  • @michaelhealy7005
    @michaelhealy7005 5 หลายเดือนก่อน +3

    I’ve seen overloaded neutrals many times due to what they talked about…. A 3 wire cable with both circuits on the same phase due to installing on a tandem breaker. I’ve also seen lots of expensive equipment burnt out due to losing the shared neutral when the circuit was wired on a proper 2 pole breaker so each wire is on their own phase. This stuff happens a lot.

  • @ChaplainDaveSparks
    @ChaplainDaveSparks 5 หลายเดือนก่อน +2

    Fun story. When I was growing up, the voltage used to drop rather low. We could tell because the picture in our (CRT B&W) TV would shrink horizontally. The TV repairman said it was due to low voltage. We called the utility and when they came out, they said that *every circuit* in the house was on *THE SAME BUS* of our 120/240 service! An electrician came out and remedied that.
    Maybe the panel was wired just before quitting time on a Friday … 😀

  • @harleyj3938
    @harleyj3938 5 หลายเดือนก่อน +4

    Anytime you install a tandem to create more space. You have to payatention to what your doing.

  • @dandearman2871
    @dandearman2871 4 หลายเดือนก่อน +1

    We didn't loose a neutral but lost a phase to out factory. The voltage to one of our furnaces was low enough that the heater contactors could not pull in but the voltage was still high enough that it burnt up the coils in the contactors because of the high current from not pulling in.

  • @PHILBUSHMASTER
    @PHILBUSHMASTER 5 หลายเดือนก่อน +1

    Good topic, I enjoyed the panel of “Toppers” LOL

  • @MrKen59
    @MrKen59 10 วันที่ผ่านมา

    Good news is many new devices can run between 120 and 240 with no change. Today’s computers support dual voltage for the most part as well. Probably has a lot to do with global market.

  • @NipkowDisk
    @NipkowDisk 5 หลายเดือนก่อน +3

    I still refer to them as Edison circuits... showing my age.

    • @professorg8383
      @professorg8383 5 หลายเดือนก่อน +1

      Edison did use 3 wire DC distribution. Back when they wee debating AC vs DC, Edison's 3 wire DC could easily be switched to split phase AC without modifications. Edison had a lot of installed lighting systems and many, many of his 110 volt DC bulbs in service. The bulbs worked fine with either AC or DC.
      Technically, Edison lost the war of the currents, but he still made a lot of money selling his light bulbs. In the long run, AC was better for distribution and 110 volts was safer than 220 volts. It worked out quite well and was a more efficient way to distribute power.

  • @walterbrown8694
    @walterbrown8694 3 หลายเดือนก่อน

    Your illustration showing the "Correct Way" of wiring of 2 branch circuits is also incorrect Mike. The way I've always done it is to use an individual neutral paired with a "hot" all the way from the respective panel for every branch circuit. (Your illustration seems to show a shared neutral for the 2 branch circuits)

    • @MikeHoltNEC
      @MikeHoltNEC  3 หลายเดือนก่อน

      Lol... a multiwire branch circuit is permitted by the NEC, so it's not incorrect. If my video is about a multiwire branch circuit, then I need to show the multiwire circuit. Not two separate 120V circuits. Hope this helps...

  • @jasonmarroking4357
    @jasonmarroking4357 3 หลายเดือนก่อน

    Does anyone know Mario’s Instagram or info ? I would like to follow him he gave some great information!

    • @MikeHoltNEC
      @MikeHoltNEC  3 หลายเดือนก่อน +1

      Mario is part of Mike Holt Enterprises and his personal Instagram account does not have anything electrically technical. His account is 'Mario.Valdes_'