AIR CIRCUIT BREAKER PROTECTION SETTINGS - SCHNEIDER ELECTRIC MAKE ACB
ฝัง
- เผยแพร่เมื่อ 25 พ.ค. 2020
- AIR CIRCUIT BREAKER PROTECTION SETTINGS - SCHNEIDER ELECTRIC MAKE ACB
The long-time delay should be adjusted in such a manner that the inrush current should be allowed to pass through the circuit breaker without tripping when the motor starts. Ground Fault Pickup
Very good explain sir.. Thank so much
TQ sir. Kindly share this channel with your electrical team 🙏
Bhai very well explained 👍
Thank you Bhai 😄 please share the channel with your Electrical team
Very very good 👍 sir
TQ sir. Pl share with others electrical people 🙏
Wao buhat ashy sy smjya
Bahut hi achha video banaye hain sir thank you sir
TQ sir
Sir Great
TQ sr
Hi, I like your video. Thanks
TQ sr
superb....sir
super superb sir do more....videos
Sure sir 👍
Explain on white board with caliculations will be better.every one will understand.
Sure
Great
short tym me second wali ka bata dein on off 0to4 setting kaise kaam krti hai
Short time - agar ACB 0.4 second, Tak 2x times of rated current lega too ACB "short ckt fault" pe trip hoga.
Dear sir. We have MVS16N SCHNEIDER BREAKER .
IR - 0.6
TR - 1
ISD - 2.5
TSD-0.3
Ii - 5
Ig- B
Tg- 0.2
But breaker off suddenly when 400A load on while starting .
Please which setting have to check
Increase Ig to C or increase Tg (ground current limit)
Can you pls make more videos of ACB Troubleshooting
Okay... I will 👍
Tell me about the details of 6 Ir
Nice.
....
Thank you sir
Good
Dear sir, I am currently using schneider electric 6.0A/E, what advise do you have to set the ACB protection settings IR, TR, ISD, TSD, li, Ig & Tg ?
Keep the values as low as possible. IR is for total load and its relevant values for others.
Sir, big fan.
How can i set the values according to my connected load, please can you teach me the calculations?
@@bishantkumar12589 I found the user manual for micrologic 6.0A/E, I was thinking should I follow the threshold values as stated in the user manual?
Frequent off of breaker. What to check?
I'll check and revert sr
Time kaise decided krte he ki hme konse instant pe rkhna please clarify.
Instantaneous k liy koi time delay nai h sir, wo ek max current limit aane pe suddenly trip kar deta hai ACB ko,
Remaining settings k liye time delay customer khud set kar leta hai apne application k according.
Kitna Kam rahe utna safe rahega system.
Turkce açıklaması yaparmisiniz
English !!! Pl
What is @ 6 Ir ?????
6 times rated current
Acb breaker me ground fault show kar raha hai but breaker working hai to ky karna padega
Breaker trip nai hua. ? May be ground fault ka warning aa raha hoga, setting Kam kar do aap. Safe rahega equipment and person
@@bishantkumar12589 Maine ground setting off kar diye hai koi dikkat to nahi aayegi na?
@@dineshpanchal8728 sir, setting off mat karo, protection nai rahega. Agar koi chota Fault hoga too ye setting hi usko identify karega. Off karne se direct major problem ho jaega.
@@bishantkumar12589 ok sir thanks for your advice
@@dineshpanchal8728 welcome 🤗
Bhai on delay aur off delay to bata dete , wahi samajhne aaya tha yaha
Okay. Next video me cover karta hu
Apka namber bo sir
Sir. Please yahi msg kar do