Automatic Changeover Switch for Generator / Automatic Transfer Switch / ATS (With Circuit Diagram)

แชร์
ฝัง
  • เผยแพร่เมื่อ 17 ธ.ค. 2024

ความคิดเห็น • 393

  • @Ali_Haji_SouthAfrica
    @Ali_Haji_SouthAfrica 4 ปีที่แล้ว +15

    If the generator does not have an AVR (Automatic Voltage Regulator) I would incorporate a Delay Timer.
    Thank you for the well explained illustration 👏

    • @mickuljatheseagull
      @mickuljatheseagull 3 ปีที่แล้ว

      tell me an AC generator without an AVR? And the point of a delay timer to take the place of an AVR? Any AC generator without regulation will suffer high unregulated voltage.

    • @jjr897
      @jjr897 3 ปีที่แล้ว

      @@mickuljatheseagull t
      There is capacitor controlled voltage regulation. But still whould put a delay in so the generator doesn’t start immediately.

    • @kossieyramsegbefia
      @kossieyramsegbefia 3 หลายเดือนก่อน

      you can buil AVR TO Control the exciter and the speed of the Alternator okay

  • @jeralddalnay8168
    @jeralddalnay8168 3 ปีที่แล้ว +7

    You show us step by step and even the connection inside the contactor. you do great, clearly understandable very specific its so nice

  • @yoseph501
    @yoseph501 2 ปีที่แล้ว

    good work I saved 3500etb by your diagram thanks a lot

  • @jafaribori5428
    @jafaribori5428 4 ปีที่แล้ว +6

    I think is better to install a timer switch 3Second at least [ delay ON ] this timer will control a Utility magnet contactor and relay to avoid interaction between generator and utility power.

  • @amm9613
    @amm9613 3 ปีที่แล้ว +1

    Lots of time delay comments which I agree with but the elephant in the room is the 5 pin relay, if that failed the gen will start , collide with utility and then you’re going to need a new one. Great concept, just needs fine tuned.

    • @thekingwc
      @thekingwc 3 ปีที่แล้ว

      It’s weird setup. Seems flawed. I would hook up power companies contractor directly to its own coil instead and leave everything else the same. When power fails generator contractor will be allowed to close. As long as power company supplies power generator contractor can’t close, whether generator is on or off.

    • @thekingwc
      @thekingwc 3 ปีที่แล้ว

      Wait, it seems that they both can’t close at the same time. What I don’t like is, it doesn’t automatically transfer back to power grid when power comes back. My way is better.

    • @thekingwc
      @thekingwc 3 ปีที่แล้ว +1

      So, it just hit me that when power company comes back on the signal to the relay stops and the generator turns off. It will automatically transfer back to power company. There’s nothing wrong with this setup.

  • @007floppyboy
    @007floppyboy 3 ปีที่แล้ว +2

    You have electrical interlock between contactors, that is good. I would also have mechanical interlock between the contactors.
    Better still is have a set of N/O and N/C contacts on the contactor.
    Then its very simple to do change over.

  • @victormanueljimenezromero6441
    @victormanueljimenezromero6441 ปีที่แล้ว +1

    Cordial saludo desde Villavicencio Colombia; muy buen video.
    Una pregunta ésta transferencia da prioridad al estado en red publica?. O sea que si se diera el caso de tener tensión de planta estando activo el contactor de red, se mantiene en ese estado?

  • @mdseraj4784
    @mdseraj4784 2 ปีที่แล้ว

    Wah Bhai jaan must video 📷 thanks 👍

  • @akinpelumi4653
    @akinpelumi4653 ปีที่แล้ว

    Great 👍 job. But I have a question ❓ my question is this: this five pin relay would only start the gen but couldn't put it off, why? Pls modify it. Thanks

  • @IbrahimaDiop-g2e
    @IbrahimaDiop-g2e 4 หลายเดือนก่อน

    Merci du SENEGAL (WESTERN AFRICA) it's easy to understand

  • @kuaoteptv
    @kuaoteptv 4 ปีที่แล้ว

    Thankyou sir for nice informative tutorial more power satin mga ka electrical.

  • @gilbertduclayan7645
    @gilbertduclayan7645 3 ปีที่แล้ว +8

    should be installed ON DELAY/Timer on the genarator contactor so that the AVR of
    the genarator will not damage immediately

    • @LOF-ile
      @LOF-ile 3 ปีที่แล้ว

      They use interlocks.

  • @AungThantZin-no9vz
    @AungThantZin-no9vz 11 หลายเดือนก่อน

    Verygood Electrical Enginerring😊😊

  • @patrickkariavu1830
    @patrickkariavu1830 2 ปีที่แล้ว

    VERY GOOD DESCRIPTION AND WIRING

  • @paulmoffat9306
    @paulmoffat9306 3 ปีที่แล้ว +13

    Far simpler is to use a DPDT relay feeding the desired load, with the coil driven by the generator. Generator not running, power delivered to load through NC contacts, generator delivers through NO contacts (Load is on COM contacts). Fully automatic and completely isolated and functions on generator start/run only.

    • @MP-wy8ir
      @MP-wy8ir 2 ปีที่แล้ว

      Absolutely right, but the DPDT just work for the 1ph case

  • @briankinder9292
    @briankinder9292 2 ปีที่แล้ว +1

    Takes me back to 1985 when I introduced auto shore/generator change-over on our marine switch panels. Live back then was far simpler with regs, two pole 30 amp 240 VAC relay with coil wired to gen contacts. Start gen, when voltage came up it would close contacts and select gen, stop gen it returns to mains supply. Or you could wire to select mains if mains became available, otherwise gen supply was available.
    Like the graphics.
    Brian

  • @prasanthtsp
    @prasanthtsp 4 ปีที่แล้ว +1

    Really excellent explanation. This is the definitition that the words can't explain but the way teaching actions will be better..
    So keep it up..🤔🤔👏👏

  • @mubasshiryunus2241
    @mubasshiryunus2241 2 ปีที่แล้ว

    very helpful
    Kindly make a detail video on Lighting control panel (LCP) , DALI SYSTEM & KNX LIGHTING SYSTEM

  • @AM-dn4lk
    @AM-dn4lk 2 ปีที่แล้ว

    Awesome. Thank you for this tutorial on the ATS.

  • @ancii3182
    @ancii3182 2 ปีที่แล้ว

    Please what video editor did you use>
    great video by the way.

  • @jameskol48
    @jameskol48 4 ปีที่แล้ว +52

    Do not make an ATS without mechanical interlock and timer. Once the utility power fails the generator start signal to be given after a time delay. Mechanical interlock to be provided between the power contactor , we cannot rely on electrical interlock, its dangerous.

    • @augustinechika3881
      @augustinechika3881 4 ปีที่แล้ว

      How can mechanical interlock be achieved

    • @jameskol48
      @jameskol48 4 ปีที่แล้ว +1

      @@augustinechika3881 Mechanical interlocks are available from the power contactor suppliers.

    • @etiennejeangeorges4622
      @etiennejeangeorges4622 4 ปีที่แล้ว

      Vu

    • @junbee4984
      @junbee4984 3 ปีที่แล้ว +1

      Exactly! For additional safety.. good point

    • @harrisarmentano8007
      @harrisarmentano8007 3 ปีที่แล้ว

      Yes must use interlock magnetic contactor, I'll always use this when I'm doing auto generator

  • @doziedoziechinenye8197
    @doziedoziechinenye8197 4 ปีที่แล้ว +2

    You are correct but you need to add one more contactor and replay delay timer to the supply to d b

  • @jimmyaustria4019
    @jimmyaustria4019 3 ปีที่แล้ว +1

    great learning but im thinking about the two circuit breaker w/c is at ON position there might be some safety issue. please enlighten.

  • @cashbull59
    @cashbull59 2 ปีที่แล้ว

    one question, why are you switching the neutrals?
    shouldn't the system share the neutral and the ground?
    for a simpler setup all you need is DPDT relay powered by the generator manually started/offed when the main power goes off/on
    and please keep the neutral and grounds bonded?
    thanks for posting.

  • @julmispierrerichard2531
    @julmispierrerichard2531 4 ปีที่แล้ว +1

    Merci beaucoup pour cette prestation,on attend d'autre avec plus de source de courant si c'est possible.

  • @erdoganturk9262
    @erdoganturk9262 3 ปีที่แล้ว +9

    2 time relays should be installed in this system to prevent the phases from colliding.thank you.

    • @codybrasil
      @codybrasil 3 ปีที่แล้ว +3

      Do you mean an on-delay to make sure when the power comes back it turns off the generator and then this timer ⏲ counts let’s say 2 seconds to turn on the contractor from the energy company?

    • @harissirajbham5796
      @harissirajbham5796 3 ปีที่แล้ว +1

      Yes

    • @bramcoteelectrical1088
      @bramcoteelectrical1088 2 ปีที่แล้ว

      Needs adding if you dont want a fire..

  • @carloscea5238
    @carloscea5238 3 ปีที่แล้ว +1

    No, the idea is good but it does not work for commercial standard gasoline or diesel generators. The only way it works is for the generator to have the "Remote Start" option. A generator without "Remote Start" must consider a pulse for ignition and then bring the ignition coil to ground for shutdown. The ignition coil cannot be kept energized because the starter motor will burn out. And if the ignition coil is not grounded, the generator will only stop due to lack of fuel. I don't know of any generator for home use with the Remote Start option.

  • @antares1611
    @antares1611 4 ปีที่แล้ว +1

    GRACIAS por dar una explicacion entretenida y amena de la electricidad .Saludos de Chile

  • @williamreyes27125khz
    @williamreyes27125khz ปีที่แล้ว

    One phrase sums it all up: Hold open

  • @TUTORIALLISTRIK303
    @TUTORIALLISTRIK303 2 ปีที่แล้ว

    Good your tutorial my friends 👍

  • @grapepulp4504
    @grapepulp4504 3 ปีที่แล้ว +2

    This is a nice video tutorial for those electricians who doesn’t know much about this one like me uhm brother is it an automatic type of switch? When the main supply is off then the generator will it start automatically?? Thanks bro 👍👍

  • @ousmanfadera8310
    @ousmanfadera8310 2 ปีที่แล้ว

    Great, excellent, amazing and credible. indeed seeking for scholarship on electrical and electronic at your level or even at university level,

  • @aliasgarmotagam4058
    @aliasgarmotagam4058 ปีที่แล้ว

    The first time you have a chance at the top is the second one I just got to go in and do the second and third and I don’t have a lot to say but I’m going in to get a little more info about it so if I can 😮

  • @afnansiddiqui9158
    @afnansiddiqui9158 4 ปีที่แล้ว +12

    wiring need improvements you need to add timer relay other wise genator starter motor will not stop

    • @doziedoziechinenye8197
      @doziedoziechinenye8197 4 ปีที่แล้ว

      Yes it need one more magnetic contactor one timer one relay and one selector switch

    • @claudiogiovingo4903
      @claudiogiovingo4903 3 ปีที่แล้ว

      You need a 2 wire gen controller, it start and stop the engine with his delay ( for warming up prior Engaged to load house and cooling down prior shooting down the engine, and if gen is a gas engine it also control the choke

    • @analieromero
      @analieromero ปีที่แล้ว

      This [on the link] is better, I guess. The Generator starts and stops by itself depending on mains power supply.
      th-cam.com/video/BRf1j4KcWow/w-d-xo.html
      EDIT ==============
      The corrected explained video..
      th-cam.com/video/rHpZEmuHknQ/w-d-xo.html

  • @milordfanord1967
    @milordfanord1967 ปีที่แล้ว +4

    Wrong diagrams! You are missing electrical interlock between 2 contactors then you must have a time delay divice,,

  • @klimatbgt
    @klimatbgt 4 ปีที่แล้ว +3

    Generators nowadays have their own Auto Transfer Switch (ATS) installed in every unit if so required by the owner but its a must to have it so the load change over will take smoothly, easy with the convenience of the people in the building and the maintenance crew for their operation.

  • @liant9314
    @liant9314 3 ปีที่แล้ว

    Please help me out. I bought "KOZUKA SINGLE PHASE 60A DIGITAL KWH METER DDS3666" and electricians installed it under my air conditioning, but wiring is not the same with this video. They put line/brown wire together on the left side and neutral/blue wire together on the right side. It works, but is it correct?

  • @bronyakz2634
    @bronyakz2634 3 ปีที่แล้ว

    System electrician brohter 👍👍👍🙏🙏🙏

  • @manojdas265
    @manojdas265 4 ปีที่แล้ว

    help ful and good video but circuit diagram add this video all people best help ful

  • @dhammikas8435
    @dhammikas8435 3 ปีที่แล้ว

    Hi
    Thanks for the details, but my Generator haven't AMF , SO can you pls show diagram how relay to be contact to Generator? and if possible AMF diagram.

  • @johnlinawan4847
    @johnlinawan4847 3 ปีที่แล้ว

    very nice concept...this uses fewer apparatus

  • @engineer6877
    @engineer6877 4 ปีที่แล้ว +1

    beautiful video could you tell me what's the name of the software that you are using please

  • @knowhowspirit8589
    @knowhowspirit8589 2 ปีที่แล้ว

    Good...
    Channel "Knowhow Spirit"
    A learning and awareness based channel.

  • @SD-bv5tw
    @SD-bv5tw ปีที่แล้ว

    There is one little thing with this.Correct me if I am wrong. It seems that the generator starter will keep on turning that starter motor constantly until the grid voltage get back.

  • @FCyrille
    @FCyrille 4 หลายเดือนก่อน

    Great 👌 work ❤

  • @jmwathi3641
    @jmwathi3641 3 ปีที่แล้ว +4

    the generator starter relay should have a timer to avoid burning out the starter on the generator and also delay timer on the main power contactor to wait power to stabilize to avoid generator to turn on off when the mains power not stable

    • @ravideo3515
      @ravideo3515 3 ปีที่แล้ว

      Great idea

    • @bramcoteelectrical1088
      @bramcoteelectrical1088 2 ปีที่แล้ว

      100% needs a timer on the relay or a sea set controller thag looks for an increase in voltage so dont attempt a 2n or 3rd try to start.

  • @peterjesus9087
    @peterjesus9087 4 ปีที่แล้ว +3

    Why do you have to combined neutral line to phases?? That's the area i failed to understand, if you can explain it pls, otherwise appreciated

    • @bramcoteelectrical1088
      @bramcoteelectrical1088 2 ปีที่แล้ว

      There not connected when one is closed the other is open on the live and Netrual
      This method is Double pole so it switches on and off and keep the netrual and lives from the sources apart.
      This is good safe practice..still.needs interlock..

  • @tecnoservicessecurity8517
    @tecnoservicessecurity8517 3 ปีที่แล้ว +4

    WHICH SOFTWARE YOU USE TO ANIMATE YOUR LESSONS

  • @enghogantonio423
    @enghogantonio423 ปีที่แล้ว

    Diagram is ok. But I have simple comments.
    1. Is it advisable if normal power is "Off" the normally closed relay contact always triggering the starter generator?
    2. What if the normal power is back to online, the generator will automatically to "Off"?

  • @somasiriperumburiarachchig9628
    @somasiriperumburiarachchig9628 3 ปีที่แล้ว

    Thank you for the well explained illustration

  • @pradippathak41
    @pradippathak41 ปีที่แล้ว

    Very nice demo

  • @ammayapper
    @ammayapper 3 ปีที่แล้ว

    Super explain👌👌👌👌👌👌

  • @vicklime5375
    @vicklime5375 3 ปีที่แล้ว +1

    Very informative presentation.please let me know the software/apps you used in your presentation.

  • @AzeriZuriA
    @AzeriZuriA 3 ปีที่แล้ว

    I think the idea would be better if u change the single generator for another power source already regulated with more stable current. This way this prtotype should be working well.

  • @gabrieljonga9596
    @gabrieljonga9596 4 ปีที่แล้ว +3

    Well explained thank you.What if its a solar and you dont have that generator stator connection?Yet you want to work the same

    • @slengineeringacademy2234
      @slengineeringacademy2234  4 ปีที่แล้ว +1

      Thanks for watching and your significant comment..👍

    • @madanrajyadav9637
      @madanrajyadav9637 4 ปีที่แล้ว

      Yes it work on solar too. But it need AC supply

    • @juanpangui1007
      @juanpangui1007 4 ปีที่แล้ว

      @@slengineeringacademy2234 hola que tal, me llamo juan soy de Argentina, soy estudiante en electricidad industrial, el video esta muy bueno, lastima que esta en ingles, queria hacerte un par de preguntas sobre el video, ¿En que parte del generador van conectado el relay que va arriba del generador y del interruptor termo magnetico? Tiene algun nombre especifico donde van conectados?
      La otra pregunta es, ¿Que tipo relay lleva este circuito?

    • @bramcoteelectrical1088
      @bramcoteelectrical1088 2 ปีที่แล้ว

      Will work on a solar inverter that works on island mode..basically an inverter that is happy without a grid..

  • @a.malikchanel2921
    @a.malikchanel2921 3 ปีที่แล้ว

    good illustration for automatic start electric

  • @selloisaac6365
    @selloisaac6365 3 ปีที่แล้ว

    Hello nice 1,,,what amperes are your contactors,,,

  • @jdg5682
    @jdg5682 ปีที่แล้ว +2

    The starter will continuously run and the genset wont switch of if you break power to the starter you need to have extra pole to actuate cutout en delay on timer to controll the relay when swithing on and delay off relay to trip the cutout

  • @OdongoThomas-uw9qh
    @OdongoThomas-uw9qh 9 หลายเดือนก่อน

    Appreciate the nice work done

  • @mfilippos
    @mfilippos 3 ปีที่แล้ว

    Very nice. Do we have a layout with 3 phase 380v gen. for household use with mechanical interlock. All today ATS boards have installed an ATM (automatic control module) that regulate the time for the start and the preheat and other functions (output current,Amp, etc )

    • @bramcoteelectrical1088
      @bramcoteelectrical1088 2 ปีที่แล้ว

      Just copy the above and make it 4 pole
      L1
      L2
      L3
      N
      So basically copy above but have a 4 pole relay interlocked (expensive thou)

  • @Xxxcappie23
    @Xxxcappie23 3 ปีที่แล้ว

    Great video. BUT Was it necessary to use a relay, can it work without the relay ? Why the relay

    • @bramcoteelectrical1088
      @bramcoteelectrical1088 2 ปีที่แล้ว

      Need relay to tell genny to start but the diahram needs to add a timmer relay or you couod burn out the genny starter..

  • @clloyder
    @clloyder 3 ปีที่แล้ว +1

    Can I know what apps/software you used in white board animation. Thanks in advance.

  • @vishva8kumara
    @vishva8kumara 2 ปีที่แล้ว

    I use two 12V relays, and another in the inverter. 12V DC regulator introduces a delay in switching.

  • @AbdelmoulaLekehal
    @AbdelmoulaLekehal 3 ปีที่แล้ว

    thank you very much for this video it's the solution for automatic changeover

  • @Alimediaofficial100
    @Alimediaofficial100 3 ปีที่แล้ว

    Very nice job

  • @andrianapostol6055
    @andrianapostol6055 3 ปีที่แล้ว

    Nice sir I like ur video

  • @99andrianmonk
    @99andrianmonk 4 ปีที่แล้ว +3

    Would have been much more informative if as each step occurred you showed the effect of the relay being de-energized and the contacts closing / opening with the flow of electricity changing paths. Or, at least a voice over. All the work to put this together just came up short of being really effective.

  • @GunaSekar-nl5dj
    @GunaSekar-nl5dj 3 ปีที่แล้ว +3

    Both contactors are same or not?
    Symbol changed in circuit drawing.

  • @dharmendrapandeytaj4581
    @dharmendrapandeytaj4581 3 ปีที่แล้ว

    Best channel

  • @davidvermaakboogieman
    @davidvermaakboogieman ปีที่แล้ว

    Good explanation but generator starter wont stop running how do you fix that

  • @victormjimenezr217
    @victormjimenezr217 3 ปีที่แล้ว +2

    Si es importante el retardo para el contactor del generador. Se requiere darle unos 10 segundos al menos para que logre su máxima capacidad o potencia

    • @thecosmotm
      @thecosmotm 2 ปีที่แล้ว

      depende del generador y de la gama del mismo, además de su costo... Para uno económico si debería agregarse.

  • @haristokratah4687
    @haristokratah4687 4 ปีที่แล้ว

    Thanks for Education video. Appreciate it🙏👍

  • @ajmalwains2622
    @ajmalwains2622 4 ปีที่แล้ว +1

    Gen ma starter to continue chlta rhy ga phir wo damage ho jae ga

  • @chhunleang6928
    @chhunleang6928 3 ปีที่แล้ว +1

    Wow good video thanks

  • @Factshowofficialbd
    @Factshowofficialbd 3 ปีที่แล้ว +1

    Beautiful diagram

  • @repairingmaster6568
    @repairingmaster6568 3 ปีที่แล้ว +1

    great Work

  • @WPg.
    @WPg. 3 ปีที่แล้ว +1

    Good but there is to be corrected: we must normally turn off the power supply to the starter after starting the generator group either by a speed detector

  • @janjanboquia6738
    @janjanboquia6738 3 ปีที่แล้ว

    What software did you use to make the pictorial diagram sir.?

  • @jaimetemplo3726
    @jaimetemplo3726 2 ปีที่แล้ว

    we can used this diagram for both generator sir?

  • @michaelcostello6991
    @michaelcostello6991 2 ปีที่แล้ว

    Great video. Thanks

  • @xescferre7328
    @xescferre7328 4 ปีที่แล้ว +1

    Moltes Gracies. Tinc dues preguntes si es possible.
    Segons aquesta configuració, mai coincidiran les entrades de AC ? Vull dir o hi ha una o hi ha l'altre.
    Quin tipus de contactors son?
    Gracies altre cop

  • @dhammikas8435
    @dhammikas8435 3 ปีที่แล้ว

    Hi Is this circuit can be use for Diesel Generator?

  • @ГасанХалигов
    @ГасанХалигов 9 หลายเดือนก่อน +1

    Şəbəkədə gərginlik getdikdə startora bağlı olan rele qapandı generator çalışdı deyək ki,sonra startor necə ayrılacaq?

  • @bharatiyavidyabhavantvm8716
    @bharatiyavidyabhavantvm8716 3 ปีที่แล้ว

    we have a solar power system (Off Grid 1 KV) . It is mechanically operated with a two pole two way switch when the solar power diminishes in night time. Can this be altered automatically? if so kindly help me with the diagram and parts list. I have a basic knowledge of using electricity and hazards of using electricity.

  • @seanbrossard8178
    @seanbrossard8178 2 ปีที่แล้ว

    So I would have to have an additional relay on-demand side to start the generator

  • @peterjesus816
    @peterjesus816 2 ปีที่แล้ว

    Is this singlephase wiring the same as three phase wiring??

  • @davinaaldine1424
    @davinaaldine1424 2 ปีที่แล้ว

    I am so interested in your show

  • @gabrieliovan2795
    @gabrieliovan2795 4 ปีที่แล้ว

    Ce se intampla cand revine tensiunea de la retea?. Temporizarea pentru starter mentionata de cineeva mai jos... Scema. dvs este un interblocaj electric inter doua surse si atat. Pana a functiona ca un AAR adevarat mai sunt destule de facut. Succes!!!

  • @john-kneebee2143
    @john-kneebee2143 3 ปีที่แล้ว

    Sorry guys I have to shoot holes through this !!! #1 need to break(cannot rely on a contactor) the Neutral(or/and utility's ground) from the power company service (other wise the generator system will back feed on to the utility's system)(this will KILL a service utility worker) !!! and #2 because the generator is a separately derived system, a grounding electrode (Equipment ground)is required at the generator........However the conundrum for grounding loops comes into play with the grounding and bonding at the house panel(this has to be considered as well)...... look forward to feedback please !!! Thank you

  • @yoosufkm1716
    @yoosufkm1716 4 ปีที่แล้ว +1

    once engine start,how disconnect relay from starter?is,its work automatic inbuild timer control pls reply

    • @yaielgonzales4091
      @yaielgonzales4091 4 ปีที่แล้ว +2

      I think they need also timer to start the starter and stop wen the generator continous running.

    • @bramcoteelectrical1088
      @bramcoteelectrical1088 4 ปีที่แล้ว +1

      Definitely need a timer trigger 0.4 to 3 seconds adjustable then time out so you dont burn out starter

  • @blackpanther-um1uj
    @blackpanther-um1uj 8 หลายเดือนก่อน

    when genreator contactois is ON n/c terminal will be open,so how switch on main contactor when coming main power becuacse n/c is already opened in generator contactor?

  • @technicalexperience2785
    @technicalexperience2785 3 ปีที่แล้ว

    nice animation explanation

  • @mudasirhussain6560
    @mudasirhussain6560 2 ปีที่แล้ว

    bohot acha video

  • @dhammikas8435
    @dhammikas8435 3 ปีที่แล้ว

    HI
    Can you please draw the diagram connecting place on Generator? since my Generator doesn't have AVR how can connect? .

  • @priyankpatel8660
    @priyankpatel8660 3 ปีที่แล้ว

    Hi Can you Make video for operating 2 motors alternatively using remote start stop.

  • @binaryglitch64
    @binaryglitch64 3 ปีที่แล้ว

    Good information, could have done without the hand animation and music though.

  • @akhtarsayeed217
    @akhtarsayeed217 2 ปีที่แล้ว

    Is ke ellawa double phase staiblaser laga Diya zaye to dono sath me chlana chaye aur ek time me ek ek kr ke chale aur dono sath chle kiyunki double phase staiblaser laga Diya hai ye kaise hoga

  • @younmr5399
    @younmr5399 3 ปีที่แล้ว

    Very good 😊

  • @hermilitoburgo9592
    @hermilitoburgo9592 4 ปีที่แล้ว +1

    Please analyse the position of contact relay b coz the position still close

    • @gilbertduclayan7645
      @gilbertduclayan7645 3 ปีที่แล้ว

      normally close. when electric is cut relay will off.