    I have 3 inverters (MUST PRO inverter 5.5kW) connected in parallel to produce 3 phase power. With that, I have 3 PV18-5248PRO connected in parallel as well to create one battaery bank. Do i configure All 3 Inverters to set parameters 14 and 41? Also, should i connect communication cable CAN to COM from 1st battery to the 1st inverter only?

    • @MUSTENERGY
      @MUSTENERGY  8 หลายเดือนก่อน

      Hello, please consult our after-sales engineer to give you an accurate answer service@mustenergy.com

  • @crealpet972
    @crealpet972 5 หลายเดือนก่อน

    Where I can find protocols table for option 41?
    Protocol 0 is compatible with JKBMS CAN: in BMS app need select CAN protocol No 10. When connection established I have strange issue - invertor attempt load battery for maximum current 115A for several short impulses, may it try sold energy back to grid (but model is off-grid!).

    • @MUSTENERGY
      @MUSTENERGY  5 หลายเดือนก่อน

      @@crealpet972 Name:Anson Liu
      Customer Service
      WHATSAPP:+86 13302843818
      service@mustenergy.com

    • @agmkvm8005
      @agmkvm8005 5 หลายเดือนก่อน

      fully support the question. it would be much easy to simply select right protocol if we had a table of supported protocols!

    • @MUSTENERGY
      @MUSTENERGY  5 หลายเดือนก่อน

      @@agmkvm8005 We will give feedback and improve, thank you😊

    • @illyabuilds
      @illyabuilds 2 หลายเดือนก่อน

      @@agmkvm8005 Hi! Have you managed to get the protocol table? I have PV1900 EXP 4KW and LP16-24200, set parameter 41 to 0, but no results. Do I have to choose a protocol on the battery as well? @MUSTENERGY

  • @Ellfyn
    @Ellfyn 10 หลายเดือนก่อน

    Do you have a Manuel for the pv1800 5248 pro

  • @oleksandrmelnychenko645
    @oleksandrmelnychenko645 5 หลายเดือนก่อน

    Good afternoon, tell me the settings of the Must inverter to the dyness b4850 battery. I put the ones that are in the battery manual, when the inverter has already fully charged it, it gives an error (3), "battery voltage is high", then a few minutes pass and the inverter charges the battery again and gives the error again. Why doesn't the inverter turn off charging and stop charging on the SAN bus? Should the voltage be set higher or lower? Thanks for the nice info!

    • @oleksandrmelnychenko645
      @oleksandrmelnychenko645 5 หลายเดือนก่อน

      Perhaps it is necessary to set the value of Li in point [14], and not to set other parameters?

    • @MUSTENERGY
      @MUSTENERGY  5 หลายเดือนก่อน

      @@oleksandrmelnychenko645 Hello , can you send your question to our engineers and they will help answer it for you . service@mustenergy.com

  • @sbee9776
    @sbee9776 ปีที่แล้ว

    41 option set numbet pylon protocol?

  • @bimmer_k
    @bimmer_k ปีที่แล้ว +1

    I have an invertor ph18-5248 pro version 1.16. where I can get fresh firmware and how I can update it? thanks

    • @MUSTENERGY
      @MUSTENERGY  ปีที่แล้ว

      Hello, where are you from?
      Please email me the serial number the machine was sent to, and where you purchased it.
      email: must.sem.2018@gmail.com

    • @bimmer_k
      @bimmer_k ปีที่แล้ว

      @@MUSTENERGY I have sent the email and didn't get the answer yet

    • @MUSTENERGY
      @MUSTENERGY  ปีที่แล้ว +1

      @@bimmer_k Your email has been received, our engineers will reply to you as soon as possible.

  • @hasanhomidan7644
    @hasanhomidan7644 ปีที่แล้ว

    Is there compatibility between the battery and the voltronic inverter?

    • @MUSTENERGY
      @MUSTENERGY  ปีที่แล้ว +2

      yes😊

    • @hasanhomidan7644
      @hasanhomidan7644 ปีที่แล้ว

      I'm trying to connect them, but I'm getting an error. What are the steps for connecting the battery ?

    • @MUSTENERGY
      @MUSTENERGY  ปีที่แล้ว +1

      tips:
      drive.google.com/file/d/1lB9MQOOE7Gybv1XAKZ3J9wBlr8DFHB05/view?usp=sharing
      drive.google.com/file/d/13mNY5J-RVV6ydtOXoDGbr_ug-u9aYG0O/view?usp=sharing

  • @tolgahannsusur2534
    @tolgahannsusur2534 10 หลายเดือนก่อน

    For example if I have 10 x 48 volt battery connected in series, will dial 1 canbus send 480 volt to the inverter or only 48 volt?

    • @MUSTENERGY
      @MUSTENERGY  10 หลายเดือนก่อน

      Sorry, this question requires an engineer to answer. Please send your inquiry to service@mustenergy.com. If you have any pictures, you can also send them together. Thank you.

  • @ahmedsaad-ph5ll
    @ahmedsaad-ph5ll ปีที่แล้ว +1

    what is the number for huawei lithium battery 48v 100ah b1
    that i can set on option 41

    • @MUSTENERGY
      @MUSTENERGY  ปีที่แล้ว

      Hello , can you send your question to our engineers and they will help answer it for you . service@mustenergy.com

  • @ArtemZhechev
    @ArtemZhechev หลายเดือนก่อน

    It doesn't work for Must 3524 and LP16-24100. Any another CAN protocol in the battery settings doesn't fix it.

    • @MUSTENERGY
      @MUSTENERGY  หลายเดือนก่อน

      @ArtemZhechev Hello, please consult our engineer. Service@mustenergy.com

  • @sbee9776
    @sbee9776 ปีที่แล้ว

    is it possible to combine the inverter must ph18-5248 pro with the battery pylontech us2000c?

    • @MUSTENERGY
      @MUSTENERGY  ปีที่แล้ว

      Could you pls add our after sales engineer Mr. Cui and describe your problem details?
      email: cs-cds@mustpower.cn

  • @OleksandrShcherbatiuk
    @OleksandrShcherbatiuk 6 หลายเดือนก่อน

    Why the PCB_T on the battery increased up to 100 C even on low usage level?

    • @MUSTENERGY
      @MUSTENERGY  6 หลายเดือนก่อน

      You may need to consult R&D for specific details, but all batteries undergo strict safety inspections before leaving the factory.

  • @wolfehone
    @wolfehone ปีที่แล้ว

    does it work on Must PV1800 3kw?

    • @MUSTENERGY
      @MUSTENERGY  ปีที่แล้ว

      yes

    • @wolfehone
      @wolfehone ปีที่แล้ว

      i have tried but not working, can you give me some instruction please?
      @@MUSTENERGY

  • @PIX-p1f
    @PIX-p1f ปีที่แล้ว

    must pro 5.5kw inverter + 200ah with LiFePO4 (pace bms) battery - It is ok when I chose must inverter setting LI ? (PIN ASSIGN IS CORRECT). Other INV Such as Voltronic Inv, I chose PYL , It is ok. MUST INVETER is what protocol support ? for example , Pylontech Protocol?

    • @MUSTENERGY
      @MUSTENERGY  ปีที่แล้ว

      Support Pylontech protocol

  • @actiontower
    @actiontower ปีที่แล้ว

    I just bought two LP16-24100 batteries, and I want to connect them with my axitx inverter.
    is possible to connect them ?
    if not .. how can I connect the two batteries to be in sync so when I turn off master battery the other will turn off ?

    • @MUSTENERGY
      @MUSTENERGY  ปีที่แล้ว +1

      Hello, this brand of inverter is not our regular matching model.
      Could you pls add our after sales engineer Mr. Sven and describe your problem details?
      email: cs-lgy@mustpower.cn

  • @karirentid64
    @karirentid64 หลายเดือนก่อน

    Plz if you can give a approved list batteries for must pro inverter

    • @MUSTENERGY
      @MUSTENERGY  8 วันที่ผ่านมา

      Yes. Please send me an email if you need it. Thank you.
      sns@mustenergy.com

  • @asmelashselamawi8888
    @asmelashselamawi8888 ปีที่แล้ว

    How do we connect the comunication cable with Victron inverter?

    • @MUSTENERGY
      @MUSTENERGY  ปีที่แล้ว

      This inverter is not manufactured by us

    • @asmelashselamawi8888
      @asmelashselamawi8888 ปีที่แล้ว

      @@MUSTENERGY Thank you for your replay. What type of communication cable are we using to connect batteries in parallel. Is it an ordinary RJ45 cable?

    • @MUSTENERGY
      @MUSTENERGY  ปีที่แล้ว

      @@asmelashselamawi8888 yes

    • @asmelashselamawi8888
      @asmelashselamawi8888 ปีที่แล้ว +1

      @@MUSTENERGY Perfet! Then, how will I be able to know if all my batteries are already comunicating or not?

  • @lancerl2
    @lancerl2 6 หลายเดือนก่อน

    Hello!
    Could you help me?
    How can I connect my inverter Must PV18-5048VHM with battery DYNESS B3 LiFePO4 48V/75AH ?
    After installation it works, but inverter doesn't see battery and doesn't know information about it.

    • @MUSTENERGY
      @MUSTENERGY  5 หลายเดือนก่อน

      Hello, you can consult our engineers
      service@mustenergy.com

    • @ArtemZhechev
      @ArtemZhechev หลายเดือนก่อน

      It doesn't work even with Must battery. Do not try.

  • @stalkerwin
    @stalkerwin ปีที่แล้ว

    I have a MUST inverter PV 18-5248 PRO and a LiFePo4 Deye RW-M6.1 battery. Help me connect them so that the inverter can read the BMS batteries. Please tell me the cable pinout. Thank you.

    • @MUSTENERGY
      @MUSTENERGY  ปีที่แล้ว

      hello, If you encounter any post-sales issues, kindly send an email to our customer service engineer at service@mustenergy.com.

  • @shakertatari4622
    @shakertatari4622 ปีที่แล้ว

    Please I have LP16-48200 battery, and I connect it with my Voltronic inverter Axpert-KING II TWIN.
    and it stop charging on 98% ?
    can you help for that please ?

    • @MUSTENERGY
      @MUSTENERGY  ปีที่แล้ว

      There may not be a matching BMS protocol, it depends more on the compatibility of the inverter.

  • @torstenjaeckel5414
    @torstenjaeckel5414 9 หลายเดือนก่อน

    Thanks a lot!

  • @gypzyluffydanger1707
    @gypzyluffydanger1707 ปีที่แล้ว

    Plz Communication pin definitions for must pv18 5248 to must liop4 battery 48v 200Ah plz..

    • @MUSTENERGY
      @MUSTENERGY  ปีที่แล้ว +1

      Hello, this video has been fully recorded

  • @asmelashselamawi8888
    @asmelashselamawi8888 ปีที่แล้ว

    I have 5.2kw inverter and the top board is damaged. Is there any possiblity to get new board from your company? And is it possible to get a contact adress email or WhatsApp?

    • @MUSTENERGY
      @MUSTENERGY  ปีที่แล้ว +1

      Hello, you can email our engineer and provide the code of your machine so that we can judge whether there are spare parts.
      email: cs-cds@mustpower.cn

    • @asmelashselamawi8888
      @asmelashselamawi8888 ปีที่แล้ว

      @@MUSTENERGY Thanks!

  • @yukuz69
    @yukuz69 4 หลายเดือนก่อน

    In all your manuals for inverters CAN is 4,5 pins. Here you say 5,6. Where is wrong? In different versions of manuals for PV1900 6kW option 41 is 0 or 17 for the Must battery. Where is wrong? Fix your mistakes finally. And give the correspondence tables to your customers.

    • @MUSTENERGY
      @MUSTENERGY  3 หลายเดือนก่อน

      Customer Service Department
      service@mustenergy.com

    • @illyabuilds
      @illyabuilds 2 หลายเดือนก่อน

      Hi! Did you manage to connect the two? I have PV1900 4kW and LP16-24200 battery. Same problem, no connection between the two. Any progress on this on your side? BTW, I also had 17, but the manual says 0, set to 0, no effect. Would appreciate any help.

    • @MUSTENERGY
      @MUSTENERGY  2 หลายเดือนก่อน

      @@illyabuilds
      Hi, You can consult our engineers:
      service@mustenergy.com

    • @yukuz69
      @yukuz69 2 หลายเดือนก่อน +1

      @@illyabuilds There is the table from Must. The Pylontech CAN protocol is 8 in option 41. Goodwee CAN is 4.

    • @illyabuilds
      @illyabuilds 2 หลายเดือนก่อน

      @@yukuz69 thanks, will try 8, the LP16 battery is using Pylontech protocol currently. The docs also say the pins are 4,5 and 4,5 so the delivered cable seems to be wrong as well as it is 4,5 -> 5,6