Chiller Evaporator Approach & How to use it

แชร์
ฝัง
  • เผยแพร่เมื่อ 3 มิ.ย. 2024
  • Leave this video understanding what chiller evaporator approach is and how to apply it to your daily chiller troubleshooting process. I explain how I look at chiller evaporator approach as a chiller technician.
    Chiller Training at chilleracademy.com
    Troubleshooting Guides at hvactime.shop
    TruTech Tools Promo: HVACTIME

ความคิดเห็น • 19

  • @HVACTIME
    @HVACTIME  19 วันที่ผ่านมา +2

    Finish your chiller course understanding chiller systems and terminology at your pace to advance your career! chilleracademy.com

  • @zekenzy6486
    @zekenzy6486 19 วันที่ผ่านมา

    Great video. Thank you for sharing

  • @joshsansone5113
    @joshsansone5113 19 วันที่ผ่านมา

    Great information on the approach values. This is information I log daily, but unaware of the actual reason why it's important. Several chillers are on site but currently working with Trane Centravac from the 1970s. Tube and shell flooded. Size CV-12F-G5-H5.
    Current condenser approach 7-9°
    Current evaporator approach running 10-15°
    Condenser tubes punched yearly. However, I have no information last time that evaporator tubes were opened up.

    • @HVACTIME
      @HVACTIME  19 วันที่ผ่านมา +1

      Ya those approach valves aren't good but ive seen that older equipment run higher valves from where and lack of efficiency.

  • @sicknick282
    @sicknick282 19 วันที่ผ่านมา

    Great information. 👍🏼

  • @MrRoooodrigooo
    @MrRoooodrigooo 19 วันที่ผ่านมา

    Gracias por enseñar

  • @NaturalBeauty-ls3jw
    @NaturalBeauty-ls3jw 17 วันที่ผ่านมา

    Is Dx type chiller has same way to find.aproach like leaving water temp-saturation temp of gas as in flooded type or leaving water temp - suction temp of gas

  • @mrgreen9086
    @mrgreen9086 19 วันที่ผ่านมา

    What causes refrigerant to water or vice versa leak? Couldn't figure or find a lesk on a chiller i was wondering on until i used my detector on the water pretty crazy

    • @HVACTIME
      @HVACTIME  19 วันที่ผ่านมา

      If there is debris in the water it can puncture a hole through the thin tubes. Improper chemical treatment can create a hole. If the chiller was recovered but the barrel was not drained or did not have water flowing it could have caused a crack. Those are the most common reasons.

  • @zeeshanzahoor8247
    @zeeshanzahoor8247 19 วันที่ผ่านมา

    Sir my chiller york yaep air cooled have alaram current mp hpx how can fix

  • @beaverdamservices
    @beaverdamservices 19 วันที่ผ่านมา

    Are all these YT videos going into the chiller academy as well? I’m kinda confused.

    • @HVACTIME
      @HVACTIME  19 วันที่ผ่านมา +1

      Chiller Academy will have it's own version of this in a lesson. It's not the exact same video. The recent videos are to provide a free constructive resource to those that need it. Chiller Academy adds more to them and gives a structured and consolidated place to learn these concepts in depth. Great question, I should probably do a live stream to discuss these kinds of things further.

    • @beaverdamservices
      @beaverdamservices 19 วันที่ผ่านมา

      @@HVACTIME I purchased it my friend. Thank you for all you do bro. I’m looking to get hired here soon for a chiller company.

  • @sicknick282
    @sicknick282 19 วันที่ผ่านมา

    I got an approach of 28.7. What is a typical approach on that chiller?

    • @HVACTIME
      @HVACTIME  19 วันที่ผ่านมา

      Whats the model number and heat exchanger type?

    • @sicknick282
      @sicknick282 19 วันที่ผ่านมา

      @@HVACTIME I meant, that is what I calculated from the example on the display of the chiller video. Is that what you came up with?

    • @HVACTIME
      @HVACTIME  19 วันที่ผ่านมา

      ah I see, lol that chiller was off when photo was taken. Will be less than 3 when online.

    • @sicknick282
      @sicknick282 19 วันที่ผ่านมา

      @@HVACTIME 10-4, that makes sense now. I appreciate your videos and will learn from them.
      Thank you very much,

  • @kumarajayasinghe8153
    @kumarajayasinghe8153 19 วันที่ผ่านมา

    York vrf c3 error terbel