  • @UmeshSingh-rg1qs
    @UmeshSingh-rg1qs ปีที่แล้ว +5

    Thanks for information...
    What about 24v DC system for DCS or any control panel..
    There are also same concept..
    If system is healthy condition...
    P -N = 24
    P- E =12
    N-E=12

  • @bharmalhtm
    @bharmalhtm ปีที่แล้ว +2

    Dear sir nice information..In addition I would say that in the battery chargers there is circuit for Earth fault detection which is using registor which is deviding voltage at half of total rated voltage. For example if 220V dc system than voltage should be 110V between earth to posative and earth to nagative.
    But sometimes if that resistor opened in Charger earth fault circuit than you will get zero voltage on both side.

  • @laroyrichardson
    @laroyrichardson 3 ปีที่แล้ว +3

    I work the power company here in Washington D.C. as relay technician.
    Cleared a battery ground today. Your video helped me a lot.
    Much love from D.C.

    • @reallifeindrajitpal
      @reallifeindrajitpal  ปีที่แล้ว +2

      Thank you very Much for support and share

    • @reallifeindrajitpal
      @reallifeindrajitpal  2 หลายเดือนก่อน +1

      Check the circuit with DC earth fault locator to identify the fault .very very important

  • @laroyrichardson
    @laroyrichardson 3 ปีที่แล้ว +2

    Good Video. Great for Substation Technicians.

  • @ROHIT-KUMAR.
    @ROHIT-KUMAR. 2 ปีที่แล้ว +1

    Great 👍

  • @surendrakverma555
    @surendrakverma555 2 ปีที่แล้ว +1

    Very good 🙏🙏🙏🙏🙏🙏🙏

  • @csgupta7017
    @csgupta7017 3 ปีที่แล้ว +3

    Sir If in a dc system positive is grounded/ earthed then how to detect earth fault between Negative and ground ? Please explain with diagram. Thanks : C S GUPTA

  • @mounabratabhowmick5258
    @mounabratabhowmick5258 10 หลายเดือนก่อน +1

    Sir ,ur technical videos is very much fruitful to gain our technical knowledge and ur voice is very good ..sir I am working in WBSETCL.u have also told that u also working in westbengal power dept..if u have no problem,just for curiosity want to know in which dept u are working..please make a video about Transfer bus coupler Trip transfer switch scheme elaborately that will be very needful to us..thanks a lot sir.

  • @technicalexperience2785
    @technicalexperience2785 2 ปีที่แล้ว +1

    good1

  • @laxmikanthac
    @laxmikanthac 2 ปีที่แล้ว +2

    Sir how voltage devided positive and negative terminal plz clarify...

  • @PramodKumar-zl4gq
    @PramodKumar-zl4gq 2 ปีที่แล้ว +1

    Good

  • @narayananbiju3224
    @narayananbiju3224 2 ปีที่แล้ว +1

    Sir, for a 30 v DC system where there is no mid point earthing,the phase to earth is 30v ,but nuetral to earth will be zero.

  • @lalitgalani575
    @lalitgalani575 3 ปีที่แล้ว +1

    good information

  • @naveedsaleem2023
    @naveedsaleem2023 2 ปีที่แล้ว +2

    Sir how to recover the positive to earth fault and negative to earth fault if it's been occuring??
    Kindly help me sir

  • @ketanpatel6709
    @ketanpatel6709 4 ปีที่แล้ว +3

    If Positive to Earth voltage shows 70 volt and Nagative to Earth shows 40 volt that what is required to check and what is reason behind it???

    • @reallifeindrajitpal
      @reallifeindrajitpal  4 ปีที่แล้ว +1

      May it be normal conditions. as possible tight the terminal of all dc jb . problem will be balance..

  • @jasimkhan5903
    @jasimkhan5903 2 หลายเดือนก่อน +1

    i work in a power plant.
    in our DC system it’s show positive and negative voltage difference. what is the positive & negative voltage difference?

  • @DeepakVjthrissur
    @DeepakVjthrissur ปีที่แล้ว +1

    Hello sir thank for sharing this info. I would like to know what would be the fault current in 1500v DC system having a load current of 2000Amps.
    Case 1 +ve to earth
    Case 2 -ve to earth
    Case 3 +ve to -ve fault(if it does exist)

  • @ranjansahu2362
    @ranjansahu2362 4 ปีที่แล้ว +2

    If leakage is present that means.. of +ve to earth is not zero... Then how to tresh the leakage where it presents.. plz explains with a pannel drawing..

  • @VarreeManikumar
    @VarreeManikumar 8 หลายเดือนก่อน +1

    How to find negative terminal and postive terminal

    • @reallifeindrajitpal
      @reallifeindrajitpal  8 หลายเดือนก่อน

      Terminal has been mentioned by the manufacturer

  • @dineshsuthar3427
    @dineshsuthar3427 4 ปีที่แล้ว +1

    Nice

  • @codevathi2714
    @codevathi2714 2 ปีที่แล้ว +2

    Sir, thank you for your help,I have one quary, if I find the dc earth fault how can I rectify it,?

  • @srinivasburri9149
    @srinivasburri9149 ปีที่แล้ว +1

    Sir
    When +ve earth fault in the dc system, at that time +ve to -ve voltage how much. (220V DC)

  • @VarreeManikumar
    @VarreeManikumar 8 หลายเดือนก่อน +1

    How to find may be negative fails or positive fails

  • @mangeshjalekar6086
    @mangeshjalekar6086 4 ปีที่แล้ว +2

    Why normal condition (without Earth) 220VDC system Earth to positive 110 v and Earth to negative 110 v what is earth base

  • @sunilkumar-md7rj
    @sunilkumar-md7rj 6 หลายเดือนก่อน +1

    How to remove DC positive or DC Negative earth fault

    • @reallifeindrajitpal
      @reallifeindrajitpal  6 หลายเดือนก่อน

      You have to identify the location where from the positive or negative fault just present. Rectify the positions as per.

  • @parmodyadav9966
    @parmodyadav9966 2 หลายเดือนก่อน +1

    Sir I am working in substation.we are used 24 voltage.so it's mean i am check in our substation
    Positive to Earth 12 volt and
    Nagative to ground 12 volt.what is I will be right there.

    • @reallifeindrajitpal
      @reallifeindrajitpal  2 หลายเดือนก่อน

      No fault persist in the system

    • @parmodyadav9966
      @parmodyadav9966 2 หลายเดือนก่อน

      @@reallifeindrajitpal but sir I check out that's positive to ground 26 voltage and nagitive to ground zero voltage in vcb pannel and main battery Bank

  • @manishjanagal2755
    @manishjanagal2755 3 ปีที่แล้ว +2

    sir please tell why for a healthy dc system positive to earth & negative to earth is half the dc voltage . 55 v in 110 v dc system?

    • @reallifeindrajitpal
      @reallifeindrajitpal  11 หลายเดือนก่อน

      In DC system Positive to earth and negative to earth are same as per the potential difference

  • @thesilkvoice
    @thesilkvoice 3 ปีที่แล้ว +2

    Can u please explain how positive to earth show 55 voltage by help of diagram?

    • @reallifeindrajitpal
      @reallifeindrajitpal  11 หลายเดือนก่อน

      If no earth fault in the system means potential difference same with earth

  • @shivkumarchaturvedi5619
    @shivkumarchaturvedi5619 4 ปีที่แล้ว +1

    Sir
    Please explain why 55v potential comes wrt earth in 110v isolated dc system of substation

    • @reallifeindrajitpal
      @reallifeindrajitpal  3 ปีที่แล้ว

      Thanks for watching ,please subscribe my channel and share

  • @sidharthadehury2248
    @sidharthadehury2248 4 ปีที่แล้ว +1

    Dear sir ty for this information. Our substation battery charger shoes p-E 1.234 & N-E - 1.11 or - 0.96 then what happened in this case

    • @reallifeindrajitpal
      @reallifeindrajitpal  3 ปีที่แล้ว

      Thanks for watching ,please subscribe my channel and share

  • @sitalroy3348
    @sitalroy3348 ปีที่แล้ว

    If in a 110 DC battery source negetive to earth voltage is less than positive to earth voltage.
    Then how I find the fault?

  • @cpleng7
    @cpleng7 2 ปีที่แล้ว

    May I know what is the risk if have positive DC earth fault or Negative DC earth fault ?

  • @NamdeoPatil
    @NamdeoPatil 10 หลายเดือนก่อน +1

    Need better explanation

  • @deepakrawat1953
    @deepakrawat1953 4 ปีที่แล้ว +1

    I think you are currently working in Government Electrical Substation

  • @kunchamvenumadhav8587
    @kunchamvenumadhav8587 4 ปีที่แล้ว +1

    How to rectify

    • @reallifeindrajitpal
      @reallifeindrajitpal  3 ปีที่แล้ว

      Thanks for watching ,please subscribe my channel and share

  • @ranjansahu2362
    @ranjansahu2362 4 ปีที่แล้ว +2

    If leakage is present that means.. of +ve to earth is not zero... Then how to tresh the leakage where it presents.. plz explains with a pannel drawing..