York YMC2 Service Needed || That Doesn’t Sound Good

แชร์
ฝัง

ความคิดเห็น • 15

  • @springws14lbss
    @springws14lbss หลายเดือนก่อน +7

    Sounded like the Titanic engine room at the start!

  • @TBJK07Jeep
    @TBJK07Jeep หลายเดือนก่อน +1

    Loss of subcooler seal is when your drop leg temp gets lower than your condenser temp. It basically is calculating that there is flash gas instead of a full liquid seal. Also on your drive heat exchanger, pull both heads when brushing it. One side may look ok, but when you pull the other, it will look like shit. It’s more work, but in the end its better.

  • @thesilentonevictor
    @thesilentonevictor หลายเดือนก่อน +4

    That sound at the start had wondering what the issue i was saying must be surging lol

    • @subcoolHVAC
      @subcoolHVAC  หลายเดือนก่อน +1

      Yep, with high pitch tap from check valve.

  • @zekenzy6486
    @zekenzy6486 หลายเดือนก่อน +1

    Great video. Thank you for sharing. Those are big chiller

    • @subcoolHVAC
      @subcoolHVAC  หลายเดือนก่อน +1

      Thanks for watching!

  • @jasonjohnsonHVAC
    @jasonjohnsonHVAC หลายเดือนก่อน +1

    Cool video. Glad to see they raised the liquid level....60% seems a tad high, but i get it. During start up, it seems like they always set it to 35%-37%. We do the maintenance and repairs on our customers YK's. Did they clean the heat exchanger for the VSD coolant. That can get pretty nasty over time. A lot of people wait till they get high temp alarms before doing it though. Enjoyed the video...thanks for sharing

    • @subcoolHVAC
      @subcoolHVAC  หลายเดือนก่อน +2

      Yeah, it ran better at 42% but JCI tech settled on 50% , they backwashed the exchanger, I did see some high motor baseplate alarms in the history after they left… probably from air. The old coolant was dark . Thanks Jason! 👊

    • @jasonjohnsonHVAC
      @jasonjohnsonHVAC หลายเดือนก่อน +1

      @@subcoolHVAC 42% seems to be the sweet spot here.

  • @ericbaker5619
    @ericbaker5619 หลายเดือนก่อน +1

    Thought you were in a factory or so.ething at first lol.

    • @subcoolHVAC
      @subcoolHVAC  หลายเดือนก่อน +1

      🤣 yep, it was definitely an unexpected kind of surge

  • @dragonstorm9968
    @dragonstorm9968 หลายเดือนก่อน +1

    Sounds like that there is the EMERGENCY STOP BUTTON FOR to immediately stop a machine.

    • @subcoolHVAC
      @subcoolHVAC  หลายเดือนก่อน +2

      That’s the last button to push