How to Wire 4-20mA 2 Wire Current Loop or 4 Wire Current Source Analog

แชร์
ฝัง
  • เผยแพร่เมื่อ 6 ส.ค. 2019
  • How to identify and wire analog 4-20mA 2 wire and 4 wire devices.
    Don't forget to like and comment on our videos and subscribe to our channel.
    th-cam.com/users/TimWilbo...
    Support these videos while you advance your skills courses.twcontrols.com/
    Items used in this video:
    Analog Simulator controls.tw/lunt9
    PLC Trainer controls.tw/rpfs9
  • วิทยาศาสตร์และเทคโนโลยี

ความคิดเห็น • 19

  • @nollyo3901
    @nollyo3901 4 ปีที่แล้ว +1

    Hi tim,can you do a video on how to use the multimeter to read and troubleshoot faulty transmitters in a plc control loop system.

    • @TimWilborne
      @TimWilborne  4 ปีที่แล้ว

      It is coming soon Nonso, thanks for watching!

  • @darnellwalker880
    @darnellwalker880 4 ปีที่แล้ว +1

    Hey Tim can you do some videos on how to tune PID loops? I have a Honeywell UDC 3500 controller I would like to get more familiar with.

    • @TimWilborne
      @TimWilborne  4 ปีที่แล้ว

      Hi Darnell. We are planning on it after the current analog series. Thanks for asking!

  • @kennalindia5604
    @kennalindia5604 3 ปีที่แล้ว +1

    Hey Tim
    Should I connect active / passive analogue output of an ABB flowmeter to my Micrologix 1400 IF4 module . The flowmeter is 230 powered.

    • @TimWilborne
      @TimWilborne  3 ปีที่แล้ว

      Chances are it is an active or 4 wire device but you need to check the manual to be sure. In that case + goes to + and - goes to -.

  • @chickenz4604
    @chickenz4604 3 ปีที่แล้ว +1

    Hi Tim, Is it possible to use 24V DC Supply OUT from PLC to power HMI, electromagnetic flowmeter, and ph meter? or I should use different DC supply for these sensors?? Thankss!!!

    • @TimWilborne
      @TimWilborne  3 ปีที่แล้ว +1

      While possible, I would advise against it. It gives your PLC less isolation. Some PLCs memory will become corrupt of you short their internal 24V power supply.

    • @chickenz4604
      @chickenz4604 3 ปีที่แล้ว

      @@TimWilborne Thank You for your advice Tim! I will just use different DC supply for these sensors

  • @dancrane4318
    @dancrane4318 4 ปีที่แล้ว +1

    I have a transmitter that is a 4-20mA 2 wire loop and I wired it as you've shown in the video with the 24vdc positive to transmitter positive, then transmitter negative to my multimeter positive, then multimeter negative to 24vdc negative and everything works as advertised, is what I can't figure out, or if it's even possible is that my analog input needs to be 1-5vdc, is there a way to wire this or place in a resistor somewhere to make it work or not? Thanks for all of your videos!

    • @TimWilborne
      @TimWilborne  4 ปีที่แล้ว

      Hi Dan, see link below. Thanks for watching!
      www.theautomationstore.com/measuring-a-4-20ma-signal-with-a-voltmeter/

    • @dancrane4318
      @dancrane4318 4 ปีที่แล้ว +1

      @@TimWilborne The problem when I do this with a 250 ohm resistor is that my transmitter loses power. I've been scratching my head on this for a while.

    • @TimWilborne
      @TimWilborne  4 ปีที่แล้ว

      @@dancrane4318 Send me a sketch of your circuit. contactus@twcontrols.com

  • @alejandromartinez3947
    @alejandromartinez3947 3 ปีที่แล้ว +1

    ¿Where did you get that loop simulator professional? I'd like to get one to do troubleshooting

    • @TimWilborne
      @TimWilborne  3 ปีที่แล้ว +2

      Hi Omar, you can find the PLC Tools SIM-ALP2 at the link below.
      plctools.com/analog-simulator-and-generator-with-lcd-0-10vdc-and-4-20ma/

  • @DerekPaz
    @DerekPaz 4 ปีที่แล้ว +1

    If I had a 2-wire sensor that had 4 wires coming out of it, how would I know how to wire it? Or are all sensors with 4 wires coming out 4-wire sensors?

    • @TimWilborne
      @TimWilborne  4 ปีที่แล้ว

      Chances are you have a 4 wire sensor but do you have a part number?

    • @DerekPaz
      @DerekPaz 4 ปีที่แล้ว +1

      @@TimWilborne no, it was just an idle question. I wondered if there was a quick rule of thumb or something, but it sounds like the answer would be to read the spec sheet and just become familiar with the part.

    • @TimWilborne
      @TimWilborne  4 ปีที่แล้ว

      Yes, it is probably safest to check the spec sheet.