    You can see the compressor on the left....the paint is gone on the head of the compressor....she's been cooking that oil a time or two. Looks like those junk accuators are getting slightly restricted. I agree this rtu should be put to bed....permanently

    • @dumptrks
      @dumptrks 3 หลายเดือนก่อน +3

      Damn @jasonjohnsonhvac your so harsh

    • @markbeiser
      @markbeiser 3 หลายเดือนก่อน +3

      It is the natural state of Carlyle scrolls!🤣

    • @throttlebottle5906
      @throttlebottle5906 3 หลายเดือนก่อน +3

      I'd say the right one was replaced/failure/burnout. left likely original. possibly a brownout or phase loss/brownout, banged the fuse. even the wires were all rubbed out, none looked to have shorted. the overheated(blown) fuse could have been poor disconnect contact, either tension loss on the blade or the fuse holders. many had hardened spring steel clips that fail with rust, and age from thermal cycling, once tension is lost game over. that happens often on circuit breakers also, at the end which plugs onto the bus bar, when it breaks and loses tension it start overheating and cooks itself, usually wrecking the breaker case and the panel bus terminal. (aka new panel time)

  • @grashoprsmith
    @grashoprsmith 3 หลายเดือนก่อน +36

    @09:25 "they're all rubbing out on each other...that's a mess"...😅😳

  • @jamesnorris1272
    @jamesnorris1272 2 หลายเดือนก่อน +3

    Mister, you are one Hell of a troubleshooter and technician; I hope your customers realize this when you talk to them about repair vs replacement (even in CA). You are going to get another call on this same unit (I'm an old 'motor man' and, yes, change the blower motor if they'll let you and 'stiffen' the base if you can). Very nice work on repairing, rerouting & securing the control & power wiring (somebody else has been there before you). Ah, and SPARE 60Amp Fusetrons; Abondanza, Brother!

  • @HfJax
    @HfJax หลายเดือนก่อน +1

    I like how you go through everything and share tips with us techs out there, and also not just going like some other TH-camrs who just change so many parts that didn’t need to be changed. Thanks so much keep them coming.

  • @LandonShipp
    @LandonShipp 3 หลายเดือนก่อน +6

    You're really good. I am an 18 yr old who has been doing hvacr since his freshmen summer in hs. The cutouts made of the compressors say it all! I'm also trying to get my ham radio operator license. Thank you for sharing this and teaching me so much and being such a great inspiration. THANK YOU!

  • @YuShudNoe
    @YuShudNoe 3 หลายเดือนก่อน +14

    I saw the right fuse discolored right away and knew the disconnect wasn’t making good contact. I win ! Haha . Gotta love HVAC!

  • @richardbartlett6932
    @richardbartlett6932 3 หลายเดือนก่อน +4

    There were times I really enjoyed this kind of mess and others where I thought "Why me?"
    Great work, you can only do so much but you did way far more than most.

    • @HVACRVIDEOS
      @HVACRVIDEOS  3 หลายเดือนก่อน +2

      Thanks

  • @davidrogers8401
    @davidrogers8401 3 หลายเดือนก่อน +5

    Nice to see how thorough you are. Way to go

    • @HVACRVIDEOS
      @HVACRVIDEOS  3 หลายเดือนก่อน +1

      Thanks

  • @Thesecret101-te1lm
    @Thesecret101-te1lm 3 หลายเดือนก่อน +26

    Great video as always!
    It would cost like $1 to $2 for the manufacturer of the lockout boards to add LEDs that indicate incoming call, outgoing call and a lockout situation. Add $1 more and you could have two color LEDs that gradually switch color to indicate if a call came within the last few seconds, or a lockout happened within the last few second.
    Not sure if it would had helped in your particular case, I didn't get which order the lockouts and the economizer control thingie are hooked up, but still.
    P.S. an argument for repairing instead of replacing is that some parts are fairly new and those that have survived for 20 years are probably good enough to survive almost until eternity.

    • @_iLLuSiv3_
      @_iLLuSiv3_ 3 หลายเดือนก่อน +4

      It's like they get off making people guess!

    • @markbeiser
      @markbeiser 3 หลายเดือนก่อน +4

      From a manufacturing and assembly cost perspective, I think having an LED to the board, instead of the wire running out to the terminal block, could actually work out to be cheaper at scale...

  • @kg4muc
    @kg4muc 3 หลายเดือนก่อน +4

    Thanks for sticking with doing it the right way!

  • @raysolovic3629
    @raysolovic3629 3 หลายเดือนก่อน +11

    Another thing to check is the motor pulley, especially for blown fuses and excess vibration. And yeah that compressor looks like its been overheated for a long time.

  • @gdrriley420
    @gdrriley420 3 หลายเดือนก่อน +7

    I saw that GE distribution panel and electrical space and I was reminded of work in all the wrong ways.

  • @tirbomax
    @tirbomax 3 หลายเดือนก่อน +5

    always great content on your process to NOT screw the customers...very few true honest people these days!

    • @HVACRVIDEOS
      @HVACRVIDEOS  3 หลายเดือนก่อน +1

      Thanks

  • @gringoloco543
    @gringoloco543 3 หลายเดือนก่อน +7

    I actually did have one blow up in my face.
    I was replacing a Trane contactor with an aftermarket contactor with all the aux switches. I accidentally attached the 24v signal wire to a 480v terminal. The circuit board made a big bang 💥....
    I'm new to this industry, BTW... and wondering if I'm cut out for it.

    • @Jason-wc3fh
      @Jason-wc3fh 3 หลายเดือนก่อน +2

      Well you identified your problem with why it blew up in your face. Obviously 480v going into 24v is going to make the 24v side very unhappy. You said you're new, so mistakes are going to happen.

  • @ErickHernandez93
    @ErickHernandez93 3 หลายเดือนก่อน +4

    Possibly just a weak compressor chris, megometer would come in handy
    Also possible bad crankcase heater, those could also easily blow a fuse, seen it a happen before

  • @markbeiser
    @markbeiser 3 หลายเดือนก่อน +10

    I tried R-407C in a mineral oil system once about 5 years ago to see what would happen, with the full consent of the owner.
    It is still working great!
    Still the only one I'll do that with though.

  • @ChrisV-
    @ChrisV- หลายเดือนก่อน +1

    Love the channel bro. You have one of the best channels and I always learn something from you.

  • @Sperkowitz
    @Sperkowitz 2 หลายเดือนก่อน +1

    I love how you inspect as to why a fuse blew. Many just replace it. Sure something like a rolling blackout or brownout can cause a surge but if not known it's good to try to find out why. It's not always possible and the should call back if something happens again then you know for sure there's a deeper issue that wasn't found the first time.

  • @terryh8421
    @terryh8421 3 หลายเดือนก่อน +3

    I like the way you find weird problems as interesting!

  • @robertarnold6672
    @robertarnold6672 3 หลายเดือนก่อน +1

    That was a tough service call but I learned some really good pointers from this video, definitely things that will make me a far better technician than my coworkers, who do not watch this channel or invest in themselves by taking online classes or going to school. Only problem is that I get hit with all the more difficult calls but you can’t grow from only dealing with the easy stuff. Thanks again Chris for making these videos. My abilities & knowledge have greatly increased since Ive been a subscriber!

  • @HVACR559
    @HVACR559 2 หลายเดือนก่อน +1

    Got an evaporateor change out on one of these next week. Multiple techs have been in this unit over years. It was way over charged, no one seemed to diagnose the plugged accurator's. Low suction add gas. Customer doesn't want to pay for R22. Looking at R422b. If i remember correctly that's like a 10% loss in efficacy. You mentioned not using replacements on a fixed metering device. Compressor has been changed I'm going to dump the compressor it seems like there's too much oil in it. Dripps out of both ports.

  • @JantjeVloet
    @JantjeVloet 3 หลายเดือนก่อน +5

    These are the video's i love, I love working on old shit fixing it and making the customer happy :)

    • @HVACRVIDEOS
      @HVACRVIDEOS  3 หลายเดือนก่อน +2

      Me to, thanks for watching

  • @ThatTransistorGuy
    @ThatTransistorGuy 3 หลายเดือนก่อน +10

    My favorite parts of your videos are when you take apart the compressors! If you could make a playlist of all the videos where you take apart the compressors, that would be amazinggggggggg

    • @HVACRVIDEOS
      @HVACRVIDEOS  3 หลายเดือนก่อน +4

      I'll see what I can do about that when business slows down a bit

    • @ThatTransistorGuy
      @ThatTransistorGuy 3 หลายเดือนก่อน

      @HVACRVIDEOS thanks! I really like this channel! Keep up the amazing work. I learn from every video.

  • @darthdzl
    @darthdzl 3 หลายเดือนก่อน +34

    You do realize that, as much as we don't want anything bad to happen, lots of people are subconsciously giddy at the prospect of the magic smoke escaping every time you say "1, 2, 3, please don't blow up". 😁 May that phrase never doom you. (knocks on wood)

  • @tonitighe4008
    @tonitighe4008 2 หลายเดือนก่อน +1

    It’s so kind of you to leave extra fuses for the power switch

  • @gordonrockafellow1211
    @gordonrockafellow1211 หลายเดือนก่อน +1

    Those Carrier units have a collector tube that ties all the evaporator coil distributor connections to the coil together.. I have connected the condenser liquid outlet line to the evaporator line with a txv if the unit is cool only or a check valve and a txv if the unit is a heat pump. It is a fairly easy work around to put a txv in parallel with the defective fixed orifice s and bring the subcooling down to normal

  • @ShukenFlash
    @ShukenFlash 3 หลายเดือนก่อน +8

    It could well have been a combination of all those things. None of them may have been enough to take it down on their own, but if a couple had it right on the edge already any little thing could have tipped it over. I agree, that thing has given them 20 years, it's time to retire and replace it. 20 years is a good run for an AC.

  • @rdalemd76
    @rdalemd76 2 หลายเดือนก่อน +1

    Here in Maryland, It’s not unusual to see Restaurants Milking a RTU that is 35 to 40 years old. The Request will usually be they want the Unit repaired and how much. What usually forces their hand to replace the RTU is Water intrusion, Compressor failures coupled with known Refrigerant leaks. That seals the deal every time. Good Video.

  • @Kevin19700
    @Kevin19700 2 หลายเดือนก่อน +1

    Another great and informative vid. Thanks for taking the time to thoroughly explain the situation and all of the possible fix’s. A cost estimate for all the repairs VS. what an entire new ten ton unit would cost would be very interesting to know.

  • @thomasmann3560
    @thomasmann3560 3 หลายเดือนก่อน +4

    I agree with the jade causing the problem. I see the relays on them doing stupid stuff all the time. I'm in AZ so we only bring in minimal fresh air, so bypassing failing jades is common for us

    • @markbeiser
      @markbeiser 3 หลายเดือนก่อน

      I've had to bypass 3 of them this year, hardly anyone wants to fix them.
      2 of them never worked anyway, because they were side return units with the economizer installed for return through the curb, and I'm not even going to try to fight the battle of finding the bits and pieces needed to convert them that the installer trashed.
      I just wish people would leave the damn bypass plug with the unit when they install it!

    • @thomasmann3560
      @thomasmann3560 3 หลายเดือนก่อน

      @@markbeiser crazy, yeah. I had 1 customer want their jade replaced. We had to get it special ordered thru siglers(carrier) and it took forever. It was so dumb.

  • @richardbrooks3569
    @richardbrooks3569 3 หลายเดือนก่อน +1

    I'm always impressed with your troubleshooting skills.

    • @HVACRVIDEOS
      @HVACRVIDEOS  3 หลายเดือนก่อน

      Thanks Bud

  • @karellfernandez73
    @karellfernandez73 3 หลายเดือนก่อน +1

    When I think :" I'm learning". Then I watch this video and I know that I don't know what I know because I didn't know ttyty24V, +480 ; restrictions @ bad bearing +100, degres😂😂.
    Now seriously. Thank you for all your videos, as a new technician trying to have the opportunity to work in the field, I'm learning from every single one. Thank again.

    • @HVACRVIDEOS
      @HVACRVIDEOS  3 หลายเดือนก่อน

      I'm glad these videos help in some small way

  • @brianmcdermott2430
    @brianmcdermott2430 3 หลายเดือนก่อน +1

    Great info. And troubleshooting. Thank you Chris.

  • @2packs4sure
    @2packs4sure 3 หลายเดือนก่อน +6

    It's these types of units and situations that made me walk away from commercial air conditioning about 10 years into my career back in 1997..
    I was tired of working on garbage that was just one patch after the other on top of the other before I got there..
    For the next 20 years it was 98% residential..

    • @Rico-oy3dc
      @Rico-oy3dc 3 หลายเดือนก่อน +2

      Must be lucky. In my area, all the residential are poor clients and patchwork. Commercial is gravy here in WV upper panhandle

    • @2packs4sure
      @2packs4sure 3 หลายเดือนก่อน +3

      @@Rico-oy3dc I had a good mix of 90% middle and upper middle class clients with a few shit show customers thrown in,, but very few..

    • @markbeiser
      @markbeiser 3 หลายเดือนก่อน +3

      It gets real "fun" when the property manager has a "maintenance" guy that takes care of most things, and only calls you after the guy has really mucked it up.
      VRF systems "maintained" by in house maintenance staff can be pretty extra spicy to deal with.

    • @2packs4sure
      @2packs4sure 3 หลายเดือนก่อน +1

      @@markbeiser I can only imagine.. lol
      I saw some incredible shit but 99% of it was analog old school equipment in my day so there were less unknowns and mysteries but still a rat's nest of incompetence to unravel on a smoking hot Houston roof...
      I DON'T miss it !!!

  • @nightshadelenar
    @nightshadelenar 3 หลายเดือนก่อน +2

    new viewer to the channel, however not the first time i've seen some ratty AC units (military legit has some of the more foul ones!) Older units like that one generally are a menace to keep running past 18-20 years due to parts and other things not being made anymore.
    Just be glad it isn't pouring water into the building! had a residential AC unit in a home i use to live in had it's coil drains fail, where something came loose and plugged up a pinhole drain. Flooded the entire lower level one week and the military housing people didn't want to fix it. Long story short, we got a new floor and a new unit with proper installers after some angry phone calls to managers of managers.

    • @HVACRVIDEOS
      @HVACRVIDEOS  3 หลายเดือนก่อน

      That sounds horrendous

  • @alantorrance6153
    @alantorrance6153 3 หลายเดือนก่อน +2

    My background is not heat engineering (it is office work, and sundry vehicle repairs), but your programme is quite interesting. Thank you.

    • @HVACRVIDEOS
      @HVACRVIDEOS  3 หลายเดือนก่อน

      Your welcome

  • @marcusmcduffie2106
    @marcusmcduffie2106 3 หลายเดือนก่อน +1

    Hello sir a quick shout out to you for being detailed and straight forward with your process.
    Thanks to your videos and the BIG PICTURE mindset I installed my 1st belt driven commercial blower motor . Keep doing what you do sir your youtube brother/tradesman from ga appreciate you. God bless you see you on the next one. .

  • @LordMondegrene
    @LordMondegrene 2 หลายเดือนก่อน +1

    I don't understand a damn thing, but these are oddly fascinating... thanks. Subscribed.

  • @kens.3729
    @kens.3729 3 หลายเดือนก่อน +5

    This Equipment looks Nothing Short of a Nightmare. Your Strong 💪 Efforts are Appreciated by your Customers and your Viewers. Thanks! 👍🙏

  • @helmsajr
    @helmsajr 3 หลายเดือนก่อน +1

    Great job Chris has always.

  • @peterhodgkins6985
    @peterhodgkins6985 3 หลายเดือนก่อน +8

    407C absolutely does NOT work well with mineral oil. Good call, Chris.

    • @PhantomDragonX
      @PhantomDragonX 3 หลายเดือนก่อน

      Yea that's what MO89 is for. if you know it has og mineral oil, don't use a poe spec refrigerant

    • @davidhoward2282
      @davidhoward2282 2 หลายเดือนก่อน

      407C + SuperChange. I used on a 2 ton rtu 6 years ago still working good.

  • @stevenhorne5089
    @stevenhorne5089 3 หลายเดือนก่อน +4

    I've never really been conscience of rub outs. But going forward, I always will. I want to go outside and check all the wires in my machine right now.

    • @HVACRVIDEOS
      @HVACRVIDEOS  3 หลายเดือนก่อน +1

      May not be a bad idea

  • @BeastCY2
    @BeastCY2 3 หลายเดือนก่อน +1

    Very good Teacher. Dont know anything as Im from the IT field but after years of watching you im trying to follow and understand.
    Thanks for the great videos

    • @HVACRVIDEOS
      @HVACRVIDEOS  3 หลายเดือนก่อน

      Thanks for watching

  • @joeydinner
    @joeydinner 3 หลายเดือนก่อน +4

    If your blue line voltage wire would have rubbed through with your low voltage, you would have seen an issue with your low voltage. More than likely would have lost a component on the low voltage because with that short, you’re sending 120v or high voltage to your low voltage circuit. Ask me how I know… Thanks for sharing your day to day service calls. I’ve learned a lot here.

    • @markbeiser
      @markbeiser 3 หลายเดือนก่อน +2

      Q: How many of the low voltage components would fail if that occurred.
      A: Yes!
      Most of us have had that particular brain shart.
      The rest are lying, or newbies that just have not gotten around to it.

    • @HVACRVIDEOS
      @HVACRVIDEOS  3 หลายเดือนก่อน

      Thanks for watching

  • @DelticEngine
    @DelticEngine 3 หลายเดือนก่อน +5

    Interesting and informative video, Chris. That RTU looks like it's been patched up and modified numerous times making it a pain in the proverbial to determine if something is what it appears to be or the result of a 'creative repair' in the past.
    Regarding the low voltage side, why not get some 24V AC/DC LED indicator lamps and put clips or backprobes on them? Some of these indicator lamps are prewrired and need only suitable termination of the wires. Careful positioning in the circuit would show exactly what is happening and when as well as where any issues occurring. If a camera was set up you would then be able to easily prove what the problem is and what needs replacing to remedy the situation.

    • @pigalex
      @pigalex 3 หลายเดือนก่อน

      This. Cheap automotive/hobby lamps that are rated for 24v DC will also run on 24v AC. Could be a cheap tool to add to the arsenal!

    • @DelticEngine
      @DelticEngine 3 หลายเดือนก่อน

      @@pigalex A very simple and cheap diagnostic tool that doesn't need batteries. It would need to be LED and AC rated up to around maybe 30 volts to account for anomalies. The key objective is minimal loading on the test circuit while being a useful indicator.

  • @Jason-wc3fh
    @Jason-wc3fh 3 หลายเดือนก่อน

    There are several videos from other HVAC guys who show in detail how to they free up the accurators on these evaporator headers. I've done it myself with total success. The labor is still going to be high for the work involved, but it can be done without having to completely change out the evaporator. Some even have TXV's kits available and you can ditch the accurators alltogether.

  • @Android_Warrior
    @Android_Warrior 3 หลายเดือนก่อน +6

    Chris, leave California and come to Texas!!!!!!!!! 💪💪💪💪

    • @Android_Warrior
      @Android_Warrior 3 หลายเดือนก่อน +1

      And if you do I will work for you!!!. Just finished my HVAC School.

  • @jrsmyth9761
    @jrsmyth9761 3 หลายเดือนก่อน +1

    I think you may have said similar, but with Y1 & Y2 both on one terminal and not separate inputs to each CLO there was nothing to activate the CLO to lock out when no amperage was sensed on the CLO. (thinking as I am typing)
    Freeze alarm may have cleared with the door off by the time you got to the clear alarm section.

  • @BEASTWRANGLER
    @BEASTWRANGLER 3 หลายเดือนก่อน +61

    It's not just restaurants it's every places mechanical /electrical rooms. They can't stand the thought of all that space
    And not one phase monitor to be seen

    • @Thesecret101-te1lm
      @Thesecret101-te1lm 3 หลายเดือนก่อน +6

      The solution is to have the electrical panels in a place where it's impractical to store stuff, like say in a hallway.
      That might be against code though.

    • @BEASTWRANGLER
      @BEASTWRANGLER 3 หลายเดือนก่อน +4

      @@Thesecret101-te1lm it generally is. Locked restricted access to unauthorized personnel etc space

    • @jeffmelcher2908
      @jeffmelcher2908 3 หลายเดือนก่อน +4

      @@BEASTWRANGLER I’m with you on the phase monitors missing. My Engineered Air unit has one and it did its job a week ago when we lost a leg during a storm.. Are they uncommon?

    • @orcus79orca5
      @orcus79orca5 3 หลายเดือนก่อน +2

      @@jeffmelcher2908 they are, I look after 14 buildings and none have any phase monitoring that I know of, some newer buildings have surge protectors but no phase monitoring, unless there is a stand by generator.

    • @THEBRAINANAYTOR
      @THEBRAINANAYTOR 3 หลายเดือนก่อน +2

      I remodel Publix as an electrician, and I can confirm. THEY ALL put racks and bins infront of panels and storage in electrical room even though there’s a big sign that says “NO STORAGE PERMITTED”

  • @raysolovic3629
    @raysolovic3629 3 หลายเดือนก่อน +5

    I just seen where your blue wire shorted at. On your video at 24:54 look at the door.

    • @russellhltn1396
      @russellhltn1396 3 หลายเดือนก่อน

      Sure looks like something happened!

    • @markbeiser
      @markbeiser 3 หลายเดือนก่อน +1

      Certainly looks like something ⚡, but looks too high on the panel, I think the cover over the controls section would be directly behind there.

  • @krisrosvold5007
    @krisrosvold5007 3 หลายเดือนก่อน +1

    Kapton Tape is really handy for insulating cable sets, especially in the carrier units. Any electrical supply should have it.

  • @ShukenFlash
    @ShukenFlash 3 หลายเดือนก่อน +4

    I suppose they could always Ship of Theseus it if replacing it is too much hassle. Just replace every component for new so it's still a "repair."

  • @ehsnils
    @ehsnils 3 หลายเดือนก่อน +2

    At 4:31 I see that the blown fuse is also discolored, which to me seems like it has been running hot for a long time and not just a quick overload.
    It could be the fuse itself that was the faulty item. That actually happens!

  • @leroygreen1877
    @leroygreen1877 3 หลายเดือนก่อน +8

    When I see those thermal fuses blow its normally resistance issue in the disconnect.

    • @JantjeVloet
      @JantjeVloet 3 หลายเดือนก่อน +2

      Yea but the breaker tripping also sounds more like a random short. I wonder when he talked about the second time he went there for a blown fuse if the breaker was tripped again.

    • @russellhltn1396
      @russellhltn1396 3 หลายเดือนก่อน

      @@JantjeVloet Maybe the breaker tripped due to single-phasing?

    • @leroygreen1877
      @leroygreen1877 3 หลายเดือนก่อน +1

      @@JantjeVloet Thermal trips are a pain
      to diag.

  • @joselanda8316
    @joselanda8316 3 หลายเดือนก่อน +4

    Tech - "Sir im going to have to recommend that you replace the whole system"
    Customer - Why is that?
    Tech - "Its got gremlins"

  • @DamagedF0X
    @DamagedF0X 3 หลายเดือนก่อน +1

    I don't work on hvac, but some of the electrical lessons/examples help me in the electrical forklift world.

  • @mikefrom3089
    @mikefrom3089 3 หลายเดือนก่อน +1

    First thing you said it short cycled the the compressor I knew it was an economizer. I bypassed one two days ago that was randomly cycling the compressor 2-10 times in a a mater of seconds. I had never seen that and the boards don’t lock out because it’s not a safety it’s the control that’s doing it

  • @paulravitsky2898
    @paulravitsky2898 3 หลายเดือนก่อน +3

    Before I was retired I was on the safety committee and we inspected for 3' clearance around all electrical. Someone would have been written up for failing to keep the area clear. Heaven forbid someone needs to kill power quickly.

  • @makinbac0n
    @makinbac0n 3 หลายเดือนก่อน +2

    Those disconnect switches are serviceable. Those knives just pull out and you can clean them.

  • @ninnghhizziddha
    @ninnghhizziddha 3 หลายเดือนก่อน +1

    Love your videos Chris.

    • @HVACRVIDEOS
      @HVACRVIDEOS  3 หลายเดือนก่อน

      Thanks bud

  • @jamestoy426
    @jamestoy426 3 หลายเดือนก่อน +3

    Worked for a home warranty customer was low on Freon we only use 407c I told the customer he said go ahead 2 weeks later he has a bad compressor I

  • @colormaker5070
    @colormaker5070 3 หลายเดือนก่อน

    i see you have one of my favorite Simpson multimeter in your office. This was my goto meter before we went digital.

  • @Duracellmumus
    @Duracellmumus 3 หลายเดือนก่อน +1

    Whend i faced so many trouble in unit like this case, i going to do some mechanical integrity checking.
    If its low the whole unit is going to down often, because the components has disturbed and no chance to do their jobs well and it always causes non-critical isues that way. But when these isues are comeing and going the components gets stressed by eachother and its going to fall most non predictable ways.
    This is can not be slow down effectivly without get an aceptable mechanical isolation inbetween the problem-sources, to get find them in the usual easy-to-understand work OR not work states.
    When is achived they going to act as an old component, and start to do their jobs realy well.
    In this case is lot of effort but take mutch less time compared to fight the seemly “not critical issues”.

    • @vandalhero
      @vandalhero 2 หลายเดือนก่อน

      i had a stroke reading this.

  • @andrewgilbreath1331
    @andrewgilbreath1331 3 หลายเดือนก่อน +1

    Bro I don't like 407c personally for 22 replacement, I've had really good luck with 422b and MO99 both work with mineral oil, no oil change is much easier to deal with.

  • @ernestrollins383
    @ernestrollins383 2 หลายเดือนก่อน +1

    10:00 I think something is bent causing excessive vibration and that is rubbing the wires

  • @blackfirehd884
    @blackfirehd884 3 หลายเดือนก่อน +5

    9:22 im sorry im too immature 😂

  • @sphinxios
    @sphinxios 3 หลายเดือนก่อน +1

    heat up the caps and se if those change value, on the bad ones values will change quite a bit

  • @lildrastly5512
    @lildrastly5512 3 หลายเดือนก่อน +1

    Love the videos 👍

  • @Bigman0_0
    @Bigman0_0 2 หลายเดือนก่อน +1

    God I love the way you troubleshoot. Out of context question, what is that app you use called?

  • @Roctrin
    @Roctrin 3 หลายเดือนก่อน +1

    22:30
    mechanical electrical joints like wire nuts arent designed for the kind of vibration seen here.
    Lots of poor design in wire routing and termination shown in this unit. Really cool stuff, thanks for your content.

  • @_iLLuSiv3_
    @_iLLuSiv3_ 3 หลายเดือนก่อน +1

    I needed some 409A, now I am converting seals and oil over instead... wow.

  • @HappilyHomicidalHooligan
    @HappilyHomicidalHooligan 3 หลายเดือนก่อน

    If the 2nd fuse to blow was the same one that blew before and was the disconnect knife that's making a poor connection, then the fuse likely blew because the bad knife connection is causing it to heat up and if it gets too hot, the fuse will blow thinking it's passing too much current...
    Fuses are micro-heaters at heart, the more current they pass, the hotter the fusable link inside them gets and when they get too hot (because they're passing too much current), they melt and a spring pulls the two halves apart breaking the circuit, too much heat in a nearby component (such as the knife blade half an inch above the fuse) will also cause the link to melt, blowing the fuse...
    When the fuse blew, cutting only 1 of the 3 Phases, it likely caused enough of an Imbalance in the Main Breaker to cause it to trip...
    In addition to that, I suspect you also have a failing (or outright failed) Jade Module and/or Compressor Lock-Out Board...
    That's my Theory, though I admit, 3-Phase Equipment, Breakers and Fuses are not my Specialty as an Electrician, my Training and Experience has always been in Residential Wiring...

  • @sparkytech8787
    @sparkytech8787 3 หลายเดือนก่อน +1

    the blue wire ruby duby looked clean thou

  • @fredlendzian7082
    @fredlendzian7082 3 หลายเดือนก่อน +3

    you got me saying 123 please don't blow up I like it

  • @Nba19980
    @Nba19980 3 หลายเดือนก่อน

    Great stuff

  • @trevorphillips7233
    @trevorphillips7233 3 หลายเดือนก่อน +1

    Gas stations look like that too

  • @LewisSmith-he6gu
    @LewisSmith-he6gu 3 หลายเดือนก่อน +1

    hello from Poole in Dorset

  • @crazyedo9979
    @crazyedo9979 3 หลายเดือนก่อน +1

    An investigation with a thermal camera would be nice to see if there are any resistance related electrical problems.😁

  • @dumptrks
    @dumptrks 3 หลายเดือนก่อน +1

    Another great video bro..keep slamming them out

  • @sirraident
    @sirraident 3 หลายเดือนก่อน +2

    Quick question regarding oil's and what you stated at the end. Would M099 not be compatible with R22 regarding the oils? If not, then would it be a good idea to flush the lines or blow out the lines with nitrogen or just change the compressor?
    I just want to know what's best practice, thanks you.
    I have learned a lot from your channel and I greatly appreciate all that you do!

    • @HVACRVIDEOS
      @HVACRVIDEOS  3 หลายเดือนก่อน +1

      Good question, I'm going to try and discuss this further on Monday nights live stream

  • @MelodyMan69
    @MelodyMan69 3 หลายเดือนก่อน +1

    I would like to see some VRF/VRV AC System diagnostics.

    • @HVACRVIDEOS
      @HVACRVIDEOS  3 หลายเดือนก่อน

      I'll see what I can do

  • @markae0
    @markae0 3 หลายเดือนก่อน +1

    Nine minute in if you can't wait. Great Video!!!!

  • @elcrazy8017
    @elcrazy8017 3 หลายเดือนก่อน +3

    That restaurant needs a PM contract on those units. They are not taken care of

    • @HVACRVIDEOS
      @HVACRVIDEOS  3 หลายเดือนก่อน +1

      So very true

  • @ritchieortiz5610
    @ritchieortiz5610 3 หลายเดือนก่อน +1

    I’ve had an issue with the same kind of unit it was a 2003 or 2004. They had the unit jumped out on running both stages. I ended up cycling the 2nd stage. It was just running for too much for too long. To the amperage would like slowly but surely.
    I’m here in the Coachella valley so you know the weather I deal with.

    • @HVACRVIDEOS
      @HVACRVIDEOS  3 หลายเดือนก่อน +1

      Yeah it’s hot out there I only have one customer out that way so I’m hardly ever there anymore

  • @AllTheOne219
    @AllTheOne219 3 หลายเดือนก่อน +3

    im early to the non member release

  • @Pyro4100
    @Pyro4100 3 หลายเดือนก่อน +1

    If the compressors are three-phase and one fuse blows they would start to single phase and at some point will trip the breaker because of the single phasing had the same issue with air compressors that are three-phase one fuse blows and then eventually it trips the breaker

  • @gabrielmendoza9165
    @gabrielmendoza9165 3 หลายเดือนก่อน +1

    19:42 *Tstat gets power from terminal board

  • @Spencer1609751
    @Spencer1609751 3 หลายเดือนก่อน +9

    That Gap in the disconnect switch knife, Like throwing Hot Dog Down the Hallway!

    • @misterhat5823
      @misterhat5823 3 หลายเดือนก่อน +1

      I've heard something similar about dropping a hot dog down a man hole...

  • @colinclingan8246
    @colinclingan8246 3 หลายเดือนก่อน +2

    That unit is two years older than me😂. Good grief.

  • @rickygammon3522
    @rickygammon3522 3 หลายเดือนก่อน +1

    Hey bud I absolutely appreciate your videos I’m also a hvac/r technician for over 25 years. Just wanted to ask what kind of issues are you having when you use the 407c in the old carrier units. Just curious I have a few customers that still have those turd units lol. Anyway I know you’re busy but if you get a chance I am just curious. Thanks for all your videos and I’m gonna get one of your hats

    • @HVACRVIDEOS
      @HVACRVIDEOS  3 หลายเดือนก่อน +1

      Hey Bud, good question- I'll discuss this a bit further in my next live stream Monday afternoon

  • @HappilyHomicidalHooligan
    @HappilyHomicidalHooligan 3 หลายเดือนก่อน +2

    Thank you for going back to this Video Intro. Please don't use the music again, it was excessively loud and even more annoying than it was loud.

  • @HfJax
    @HfJax หลายเดือนก่อน +1

    Can you do a video about the economizers and how to troubleshoot them

  • @bashaaksema94
    @bashaaksema94 3 หลายเดือนก่อน +2

    I will never understand why they use blank wires in america. Here we would definitly use cables and also have to secure them way better.

  • @kennethmoore117
    @kennethmoore117 3 หลายเดือนก่อน +1

    Flex loom for the wire like vehicle

  • @gamingwithmr.fregles8802
    @gamingwithmr.fregles8802 3 หลายเดือนก่อน +2

    2:39 anyone notice that chopped wire?

  • @whoisderf
    @whoisderf 3 หลายเดือนก่อน +5

    1:22 and hit pause. Ladies and gentleman…..that panel highlights why impact drills are NOT for the average service tech…..
    Gotta love the entire roll of E-tape around the caps. Hacks.

    • @markbeiser
      @markbeiser 3 หลายเดือนก่อน

      My company has a tech that I don't think ever figured out that the trigger on his impact drill is variable...
      I've had equipment I worked on for 20 years without stripping a screw, he touches it once and half the screws are falling out on their own next time I'm there.🙄
      I don't think I've ever used an impact for panel screws except when I don't have a charged battery for my regular driver.

    • @whoisderf
      @whoisderf 3 หลายเดือนก่อน

      @@markbeiser my favorite is when someone uses their rattle gun on the stainless Philips screws on Greenheck exhaust fans, instantly stripping them to nothing….so the next guy has to bring his Vise Grips and waste time fighting the screws.
      My rattle guns remain on the truck unless I’m breaking into a large centrifugal chiller. Outside of that, large boilers and Victaulic fittings are the only other times it comes out. On a small package unit, literally zero times in 26 years; completely unnecessary tool for the job at hand.

    • @thomasmann3560
      @thomasmann3560 3 หลายเดือนก่อน

      After every storm I run around town fixing panels laying on the ground cause of stripped screws lol

  • @Harry1s
    @Harry1s 3 หลายเดือนก่อน +1

    The blower wheel was very dirty.

  • @tundra1017
    @tundra1017 3 หลายเดือนก่อน +1

    Probably would have shut that door before turning the power on 😅 especially thinking it might blow up

  • @thesilentonevictor
    @thesilentonevictor 3 หลายเดือนก่อน +1

    Big picture diagnosis