Growatt SPF5000 ES workaround grid bypass

แชร์
ฝัง
  • เผยแพร่เมื่อ 14 ต.ค. 2024
  • In this video I try to explain how to install a workaround for the unreliable grid bypass switch in almost all modes of the growatt. Especially the SBU mode causes often these issues. With my workaround this issue seems to be gone. If you have questions use the comments and of course I would be happy if you give a thumbs up and a subscribe...

ความคิดเห็น • 43

  • @controld333
    @controld333 10 หลายเดือนก่อน +1

    Thanks for taking the time to do the video. That's exactly what damaged my AGM batteries.

    • @kirkdis
      @kirkdis  9 หลายเดือนก่อน

      sad... repoet this case to Growatt and ask to take over the costs for the batteries.

  • @ElJasperino
    @ElJasperino 11 หลายเดือนก่อน +1

    Thank you for doing this in English too. 🙏

  • @BackboneNF
    @BackboneNF ปีที่แล้ว +2

    I had the same problem before. I made a firmware update, so the sbu mode works as expected. And the fans are quiter!

    • @kirkdis
      @kirkdis  ปีที่แล้ว +1

      Hi, are you sure that the firmware solves the issue? I have the F4 A.27 installed which changes the fan noise but never heard or found a confirmation from Growatt that the Grid bypass issue is solved.

    • @BackboneNF
      @BackboneNF ปีที่แล้ว +1

      Yes f4 a.27 solved the problem for me

  • @GreekSIMRACING
    @GreekSIMRACING ปีที่แล้ว +1

    Thanks for making this in English.According to manual each unit requires 50A fuse on input AC and output,you have one relay 63A which automatic enables your AC input correct,is this enough?Nice thought dry contact.Also i think 🤔 the proper setting is SOL or SBU not utility as you have this dry contact control as i understand your BMS kills the inverter which is All-in 1 and does not communicate with growatts (jk BMS) you need to set growatts cut off on higher value from inverter and lower on JK if solar is not present with low battery the jk bms will shutdown the inverter as it draws 50 watt you need to start the utility to prevent this.But on previous videos you build DIY Semplos BMS,im a bit confused 😅.

    • @kirkdis
      @kirkdis  ปีที่แล้ว

      sorry a lot of questions in one post which confuses me also. let' s start with the ac in fuse, I of course have a ACIn fuse which is in my main cabinet and counts 32A. the fuse is more for protecting your power cable and if the fuse is smaller is disconnects in an error case earlier. so 32A are fine and never shut down my system. next topic: while breaking the connection via dry contact sol, uti and sub seem not to make much difference by functionality. when your battery soc hits the low value, grid will be connected and starts to take over. there are minor differences between the modes but utility was the best choice for my setup by now. all my bms communicate with the inverter. my former pylontech battery did that as well as the seplos bms of my EEL cases. you can also change the growatts to judge based on voltages of the battery which is not accurate and doesn't give you an idea on which state of charge it is. why the jk is shutting down the inverter? maybe you mixing things up

  • @AlinA-vg5ud
    @AlinA-vg5ud 11 วันที่ผ่านมา

    Hi I have problem body I’m trying to change my battery from the grid but i see the voltage from the grid Rich 250v when I try to change is switching my fuse and gos back on the battery mode do you think the power from the grid is to high ? Thank you 🙏🏻

    • @kirkdis
      @kirkdis  10 วันที่ผ่านมา

      Sorry I´m not clear what you issue is with your explanation...

  • @raafe4
    @raafe4 9 หลายเดือนก่อน +1

    Thank you.

  • @BackboneNF
    @BackboneNF ปีที่แล้ว +1

    Thanks for the video!

  • @NhuBaSy9B
    @NhuBaSy9B ปีที่แล้ว

    Hi. Can you post the detailed connection diagrams for this dry contact connection? Im stuck with AC by pass in SBU mode, which is exactly as yours. Im using SPF 6000 ES PLUS

  • @Passco666
    @Passco666 ปีที่แล้ว

    Did you measured the power consuption of idle Bypass? When Bypas is on its drain app. 1,4 Amps.. which is around 300 Watts.. Which is crazy consuption!

    • @kirkdis
      @kirkdis  ปีที่แล้ว

      yes, self consumption is bad with the SPF inverters.

  • @showme360
    @showme360 ปีที่แล้ว

    What is the time delay between the change over from DC supply to AC mains supply? Plus what happens if the Growatt is under load durring this change over like 60 %- 80% load?

    • @kirkdis
      @kirkdis  ปีที่แล้ว

      with this contactor workaround the time delay is around 30seconds. The reason for this is that the inverter starts a phase synch process as soon the grid is connected and then switches over to the AC source. This time delay isn't an issue as the whole process happens when your battery still has charge left. I recommend to set the switch back to grid (P12) around 20% SoC. While switching over to AC I haven't had any issues in the past even the inverters are under load.

  • @berndbuhring4003
    @berndbuhring4003 ปีที่แล้ว

    Hallo, habe den Stick zum laufen gebracht. auf Shine Phone App kommt zwar im oberen Bereich die aktuellen Daten. Aber im unteren Bereich sehe ich keine Batterie usw.
    Auf Seite 2 sehe ich den Datenlogger. Wenn ich Ihn zuordnen will, bricht er aber die Konfig. aber immer ab. Was mache ich falsch`? gruß Bernd

  • @JustaCuriousity
    @JustaCuriousity ปีที่แล้ว

    Hi, did you connect Neutral or Hot wire line to the dry contact?

    • @kirkdis
      @kirkdis  ปีที่แล้ว

      I propose to use the phase/line or hot wire as you call it.

  • @angelkm2599
    @angelkm2599 5 หลายเดือนก่อน

    hello, I have an identical installation with 3 inverters 5 kW mounted in parallel with a total single-phase output of 15 kw but I have a three-phase public network subscription of 15A per phase, I would like to know if it is possible to make the network injection of the 3 phases with one phase per inverter

    • @kirkdis
      @kirkdis  5 หลายเดือนก่อน

      3x5kW is not 45kW? I´m not really understanding what you mean with these values. You are of course able to set the inverters into 3phase mode and provide 5kW in each phase.

    • @angelkm2599
      @angelkm2599 5 หลายเดือนก่อน

      @@kirkdis Hello, I have a solar installation with 3 inverters 5 kW mounted in parallel with a total single-phase output of 15 kw but I have a three-phase public network subscription of 15A per phase, I would like to know if it is possible to make the network injection of the 3 phases with a phase by inverter on the prallèle mono?

    • @kirkdis
      @kirkdis  5 หลายเดือนก่อน

      Never tried this but I doubt your setup will work as the inverters check the input phase sync and will give an error when the input phase is not correct. In the worst case the inverter switches to bypass and makes a direct phase connection which might cause to open a wormhole or other things you might not want to consider.

  • @drhatemhadi1
    @drhatemhadi1 ปีที่แล้ว

    Can I specifying ac charge current to limit utility taking and substitute d from battery storage

    • @kirkdis
      @kirkdis  ปีที่แล้ว +1

      you can set the max ac charge current in the parameters

  • @isaknel6888
    @isaknel6888 ปีที่แล้ว

    Hi it Isak my growat 5kw inveter not switched to utility, after I connect the dry contact please help me.

    • @kirkdis
      @kirkdis  ปีที่แล้ว

      which firmware do you have? upgrading to a newer firmware seems to solve the issues without using the dry contact

  • @josefthomas2942
    @josefthomas2942 ปีที่แล้ว

    Lässt sich beim Growatt spf 5000 das Display ausschalten, oder leuchtet es dauerhaft.

    • @kirkdis
      @kirkdis  ปีที่แล้ว

      man kann es ausschalten.

  • @hekamteam
    @hekamteam หลายเดือนก่อน +1

    6000ES have the same problem

  • @Swenser
    @Swenser ปีที่แล้ว

    Anybody have info on error102 growatt? Besides basic CPU data mismatch description

    • @kirkdis
      @kirkdis  8 หลายเดือนก่อน

      th-cam.com/video/8B56MCRPFMw/w-d-xo.html different model but maybe same reason...

  • @berndbuhring4003
    @berndbuhring4003 ปีที่แล้ว

    Hallo, könntest Du ein Video über den Wifi stick und das Monitoring machen. Ich verzweifle schier!!! Danke

    • @kirkdis
      @kirkdis  ปีที่แล้ว

      was genau willst du denn dazu wissen?

    • @berndbuhring4003
      @berndbuhring4003 ปีที่แล้ว

      @@kirkdis danke für die schnelle Reaktion. Ich bekomm das Monitoring nicht hin. Habe nen growatt spf 3500es WiFi f (blond)

    • @kirkdis
      @kirkdis  ปีที่แล้ว

      @@berndbuhring4003 ist der stick im Wlan und scheibt schon daten ins webportal oder an was haperts denn?

    • @berndbuhring4003
      @berndbuhring4003 ปีที่แล้ว

      @@kirkdis ich logge mich in den Hotspot ein, ändere die Zugangsdaten speichere die Änderungen. danach verlangt die App ein Neues Setup
      Ich scanne den Code gehe auf Setup er zeigt meine Fritzbox an ich gebe nochmals das Passwort ein für den Log in und erzeigt das er verbunden ist.
      LED Leuchtet grün ( nicht blau) ? ins web Portal schreibt er nichts. Habe den PC mal an den SPF gehängt bekomme aber auch da keine Info Danke

  • @BackboneNF
    @BackboneNF ปีที่แล้ว +4

    Growatt has NO Support 😂

  • @coreyellisart6877
    @coreyellisart6877 ปีที่แล้ว

    Has anybody else experienced their SPF consuming roughly 200 watts per inverter on idle mode. No matter what if I'm in solar batteries or grid I'm consuming about 200 extra W power inverter I'm running 3 inverters

    • @kirkdis
      @kirkdis  ปีที่แล้ว

      These SPF inverters have a high consumption but 200W on each is way too high. How did you calculated/measured this number?

    • @coreyellisart6877
      @coreyellisart6877 ปีที่แล้ว

      @@kirkdis I simply put my amp meter on the grid input and measure the output with all the breakers off. I'm using to step up three wire Auto Transformers to balance my load out with 240 volt to 120 volt. Even with those turned off I'm still consuming about 200 watts each

    • @aymanbenothman9641
      @aymanbenothman9641 หลายเดือนก่อน

      I have the same issue😢.. have you figured out?​@@coreyellisart6877