Condenser not running, defrost board not passing voltage to contactor. Charging in Superheat.

แชร์
ฝัง
  • เผยแพร่เมื่อ 29 ส.ค. 2024
  • Called out for no cooling, found the defrost board not passing voltage on to contactor. I bypassed board, and charged system. Also I show a terribly designed air handler. #hvac #hvaclife #fieldpiece #makita #aspen

ความคิดเห็น • 37

  • @coltes007
    @coltes007 2 หลายเดือนก่อน

    Thank you so much your video saved me a service call and God knows how much they wouldve tried to charge me

  • @luckybeltz3892
    @luckybeltz3892 2 ปีที่แล้ว +1

    Once again complete troubleshooting no wasted steps !!!

  • @acrservicesmathewr7565
    @acrservicesmathewr7565 2 ปีที่แล้ว

    Only thing better then a goodman is a greatman. Great video.

  • @W4AX
    @W4AX 2 ปีที่แล้ว

    Great detective work!

  • @Bryan-Hensley
    @Bryan-Hensley 2 ปีที่แล้ว

    I didn't watch all of this yet but I wanted to add my experience before I forget. I've changed a couple or 3 of these boards only to find out the low pressure switch wires have worn through somewhere. (Which can knock the board out) I've had one pressure switch to open permanently. If that wire is open or grounded it will not turn on the contactor. You might have already figured it out since I didn't have time to watch the whole video

  • @bryansimon4072
    @bryansimon4072 2 ปีที่แล้ว

    Good fix

  • @lancelawrence3259
    @lancelawrence3259 2 ปีที่แล้ว

    Nice work

  • @carlossaenz4075
    @carlossaenz4075 2 ปีที่แล้ว

    Great video

  • @caru3257
    @caru3257 2 ปีที่แล้ว +1

    I really liked my Mantooth probes because I could add refrigerant if needed unfortunately the charging port broke. Fieldpiece and Testo if you are listening... I carry this board as a replacement 47D01U-843 Universal Heat Pump

    • @HVACGUY
      @HVACGUY  2 ปีที่แล้ว

      I used to use a swivel T with my suction probe, but for some reason it charged extremely slow.

  • @picklerix6162
    @picklerix6162 2 ปีที่แล้ว

    Those defrost boards seem to have a high failure rate. I believe Aspen Mfg is based in Humble, TX and has been making HVAC coils for a long time. Those Aspen coils were quite popular in Houston for replacement jobs when I was in the HVAC business back in the 80’s. Those coils were dirt cheap back in those days.

  • @seangriffon6502
    @seangriffon6502 2 ปีที่แล้ว

    Those Goodman defrost boards fail alot. Also this unit is got a bunch of garbage around it. Since it's a heat pump it needs to be sitting on risers so it can drain properly when it defrosts.

  • @cutum
    @cutum 2 ปีที่แล้ว

    Rock on!

  • @coltes007
    @coltes007 2 หลายเดือนก่อน

    Mine says 30, 60, 90 then the 2 pin test. I moved the cover up one and the red light on board turned off. I plugged fuse back in an it kicked right on

  • @realestateservicessaleshea99
    @realestateservicessaleshea99 2 ปีที่แล้ว

    That looks like another unstoppable Goodman. 😆
    I saw the first utuber with an OXBOX by the trane people . 😃
    Thanks for the video!
    🍺🍺🍺🥃🥃🍿🎯
    Stay safe.
    Retired (werk'n)keyboard super tech. Wear your safety glasses!

    • @HVACGUY
      @HVACGUY  2 ปีที่แล้ว +1

      I had to google oxbox, I don’t think I’ve heard of them before

    • @picklerix6162
      @picklerix6162 2 ปีที่แล้ว

      I believe that you can buy Oxbox equipment online. I hear that Oxbox is made in China.

  • @Eddy63
    @Eddy63 2 ปีที่แล้ว

    Good vid ... Thx ...

  • @nikkid4798
    @nikkid4798 6 หลายเดือนก่อน

    So the defrost board has a high and low pressure cut-off switch. Will the board stop the voltage for any other reason if it is working properly, or are those the only two things that will stop the voltage?

  • @justinbelleville1392
    @justinbelleville1392 2 ปีที่แล้ว

    How come the 2nd pressure switch was getting 0 volts as closed? Wouldn’t it be 24 volts? I assumed that if it was zero there would be no power running to it. Can you please explain. Thanks!

  • @GonzDez-sh7vx
    @GonzDez-sh7vx ปีที่แล้ว

    I hate how close the housing is to the liquid port on goodmans

  • @stephwaylonwells3218
    @stephwaylonwells3218 2 ปีที่แล้ว

    👍

  • @seadeas
    @seadeas 2 ปีที่แล้ว

    Because you’ve worked very hard, and I think very smart, just to be an hourly worker…

  • @DRAggIN123
    @DRAggIN123 2 ปีที่แล้ว +1

    I would braze in some flair nuts that's a really bad design

    • @HVACGUY
      @HVACGUY  2 ปีที่แล้ว +2

      That’s a good idea. Measurements would have to be perfect though.

    • @DRAggIN123
      @DRAggIN123 2 ปีที่แล้ว

      Yes for sure they would have to be

  • @melissachartres3219
    @melissachartres3219 2 ปีที่แล้ว

    Okay... I'm confused. 09:28 I thought that the suction line WAS the liquid line and that the discharge line was the gas line. What am i missing?

    • @HVACGUY
      @HVACGUY  2 ปีที่แล้ว +1

      On a heat pump the small line is always the liquid line, hot gas comes from the compressor, so in cooling it goes to condenser to become liquid m and in heating it goes out the big line to evaporator to become liquid. So big line can be suction or hot gas depending on the season.

    • @melissachartres3219
      @melissachartres3219 2 ปีที่แล้ว

      @@HVACGUY ah. right. thanks kindly for that.

    • @edwardgarza5104
      @edwardgarza5104 2 ปีที่แล้ว

      @@HVACGUY so the big line is always a high pressure vapor or low pressure vapor on heat pump. Small line will always be a high pressure liquid?

  • @CHRISDOESHVAC24
    @CHRISDOESHVAC24 ปีที่แล้ว

    Ban aspen for that design 😂

  • @seadeas
    @seadeas 2 ปีที่แล้ว

    I’ve watched several of your videos, and I’m thinking this is your own company!?!?

    • @HVACGUY
      @HVACGUY  2 ปีที่แล้ว

      Yes, it is.

  • @YukonHawk1
    @YukonHawk1 2 ปีที่แล้ว

    Poor design having that line set where it is 🤬

    • @HVACGUY
      @HVACGUY  2 ปีที่แล้ว +1

      Horrible.