Magnetic Flow Meter Explained | Working Principles

แชร์
ฝัง
  • เผยแพร่เมื่อ 29 ม.ค. 2025

ความคิดเห็น • 84

  • @jeromemorgan4928
    @jeromemorgan4928 2 ปีที่แล้ว +12

    That is very informative, helpful. I am a operations manager for a mechanical engineering company. I just had this mag valve assembly installed with a valuable client. Utilizing these methods of measuring is critical to any system that transfers abrasive liquid materials.

    • @realpars
      @realpars  2 ปีที่แล้ว +1

      Thanks fo ryour support, Jerome! We are happy to hear that.

    • @sbuiiipodcast142
      @sbuiiipodcast142 2 ปีที่แล้ว

      definitely very important theoretical insight

  • @TheDrewbe3
    @TheDrewbe3 2 ปีที่แล้ว +1

    About to install a big 12'' magnetic flow meter on a river water intake that will communicate over Ethernet/IP, this video is a good refresher on the working principles behind the meter.

    • @realpars
      @realpars  2 ปีที่แล้ว

      Glad to hear that!

  • @davebennett5069
    @davebennett5069 2 ปีที่แล้ว +2

    This is fantastic information. There are so many different flow meter technologies. It would be GREAT to see a video on the various different kinds. Especially those used for gas, since the natural gas industry is growing so fast and expanding into other areas where gas extraction is becoming economical - like landfills and manure digesters.

    • @realpars
      @realpars  2 ปีที่แล้ว

      Thanks for your support, Dave! I will happily forward your suggestion to our course developers.
      Thanks again for sharing and happy learning!

    • @mohangraj2445
      @mohangraj2445 ปีที่แล้ว

      @@realpars Need to design Electro magnetic flow I need some support

    • @maxwellmakamba5112
      @maxwellmakamba5112 10 หลายเดือนก่อน

      Can I calibrate using a prover tank

  • @kiranchoudhari4717
    @kiranchoudhari4717 2 ปีที่แล้ว +2

    I was working in cable plant. And i saw this flowmeter in petroleum Jelly pipe line. As a filling material in cable tube,
    It is a big support by realpars to grow up in Automation field

  • @InstrumentCalibration
    @InstrumentCalibration ปีที่แล้ว

    Great Graphics for the video

    • @realpars
      @realpars  ปีที่แล้ว +1

      Glad you like them!

  • @riocruz4988
    @riocruz4988 4 หลายเดือนก่อน

    Thank you very much for this very informative video.

    • @realpars
      @realpars  4 หลายเดือนก่อน

      Glad it was helpful!

  • @syufrijal
    @syufrijal 2 ปีที่แล้ว

    Amazing explanation of magnetic flow meter...very helpful

    • @realpars
      @realpars  2 ปีที่แล้ว

      Thank you so much, we're happy to hear that!

  • @IngDzib
    @IngDzib 2 ปีที่แล้ว +1

    I enjoyed this video, so helpful

    • @realpars
      @realpars  2 ปีที่แล้ว

      Glad it was helpful!

  • @kiranchoudhari4717
    @kiranchoudhari4717 2 ปีที่แล้ว

    Excellent 💯💯💯 realpars

    • @realpars
      @realpars  2 ปีที่แล้ว

      Thank you, Kiran!

  • @noname-g8e
    @noname-g8e 2 หลายเดือนก่อน

    What math formula do you use to calculate the flow rate in GPM if emf is known? How do you figure out the values of K,B,V, and D to get the EMF in Faraday's Law ?

    • @realpars
      @realpars  หลายเดือนก่อน

      Hello, @noname-g8e, and thank you for your question! If you’re studying electrical engineering, you’ll likely encounter these topics as part of your education. In our video, we’ve simplified these concepts to make them easier to understand. For detailed information about K, B, V, and D, we recommend referring to the user manual of your flow meter device, which provides comprehensive answers and practical applications for their features.
      To help you get started, here’s some additional information on Faraday’s law of induction: en.wikipedia.org/wiki/Faraday%27s_law_of_induction

  • @robertocardenosa493
    @robertocardenosa493 10 หลายเดือนก่อน +1

    Can you explain how Faraday's law can lead to that formula at 04:12? I know it as E = -dΦ/dt, and if I understood it properly, the magnetic field B = Φ/A is held constant, and hence E would be zero. What am I missing?

    • @robertocardenosa493
      @robertocardenosa493 10 หลายเดือนก่อน

      Nevermind. I managed to see the light. Hehehe

    • @realpars
      @realpars  10 หลายเดือนก่อน

      Glad to hear that, Roberto! Happy learning

  • @MrWaalkman
    @MrWaalkman 2 ปีที่แล้ว +1

    So I was tasked to figure out why the flowmeters in the paint mix room at Spring Hill, all of the meters (47 of them!) showed "Empty Pipe?". Turns out that you need your material (in this case, paint and solvent) to be conductive. Ours wasn't.
    And the previous guy had them all installed without checking conductivity, so, darn.
    One of the characteristics of a Mag meter or "Wafer Mag" as they are also known, is that they don't have the same requirements as just about every other flowmeter out there in that they don't need the 10x entrance and the 5x exit of straight pipe to settle the flow down to make accurate measurements. This rule means that the pipe leading up to the meter needs to have 10 times the pipe diameter in straight pipe entering into the flowmeter, and 5 times the diameter of the flowmeter in straight pipe exiting the flowmeter. So for a 2" meter you would need 20" leading up to the flowmeter, and 10" exiting the meter (these values are considered as a bare minimum, for complex bends you will need to increase these distances).
    This is all application specific stuff from here on out.
    We didn't have the space, the budget, or time, for redesigning the piping so the flowmeters were pretty inaccurate. Which because of our application was just fine since we really needed to know when things were circulating. The main thing was not introducing "dirt" (or gunk) into the paint that would go on to cause problems with the robots or the product itself. The thermal meters were excellent for this since the interior of the meter is nothing more than a smooth piece of pipe. The old meters had to be hot cleaned with a caustic solution from time to time. These meters certainly did not add to the problem.
    One of the other things that you want to avoid when circulating paint is to reduce the amount of "shear" which degrades the paint leading to a poor paint job. Since the meter was just another piece of pipe in the system, the new meters did not add anything to increase the amount of shear already in the system. They probably had a tiny bit better flow than the Wafer Mags, but it couldn't have been by much. But compared to almost all of the rest of the meters out there, they were vastly superior.

  • @praveenkumarpalanivelu6492
    @praveenkumarpalanivelu6492 2 ปีที่แล้ว

    Thanks for the video, its very helpful

    • @realpars
      @realpars  2 ปีที่แล้ว

      Glad to hear that! You're very welcome

  • @farhannaseer5667
    @farhannaseer5667 2 ปีที่แล้ว

    Thank you sir. Great video.

    • @realpars
      @realpars  2 ปีที่แล้ว

      Glad it was helpful!

  • @tilahuntsegaye7962
    @tilahuntsegaye7962 ปีที่แล้ว +1

    Good 👍

    • @realpars
      @realpars  ปีที่แล้ว

      Thank you!

  • @Jozsef-u1p
    @Jozsef-u1p หลายเดือนก่อน

    Could you show the difference if Inlet and outlet diameters are different. What would change. Thank you.

  • @roytutorialchannel2761
    @roytutorialchannel2761 ปีที่แล้ว

    I very like this video my friend

    • @realpars
      @realpars  ปีที่แล้ว +1

      Thank you very much!

  • @hermannnani7680
    @hermannnani7680 2 ปีที่แล้ว

    Great video
    I want to understand something about the mag meter : our mag meter is always going on and off when the fluid is passing the pipe. What can be the problem

    • @InstrumentCalibration
      @InstrumentCalibration ปีที่แล้ว

      You can try testing the sensors by manual sensor test just to make sure the sensors are working properly.

  • @JKTCGMV13
    @JKTCGMV13 2 ปีที่แล้ว

    Love you guys and I love magnets

  • @mahdikazemi2388
    @mahdikazemi2388 2 ปีที่แล้ว

    Nice job. well done.

    • @realpars
      @realpars  2 ปีที่แล้ว

      Thank you very much, Mahdi!

  • @b.b.n._kz
    @b.b.n._kz 2 ปีที่แล้ว +1

    👏👏👍from Kazakhstan

  • @meeder78
    @meeder78 2 ปีที่แล้ว +2

    Magmeters usually do not use permanent magnets but rather use a coil to generate a alternating magnetic field.

    • @littlechicago7482
      @littlechicago7482 ปีที่แล้ว +2

      Being involved with mags for over 40 years I've never seen one with permanent magnets

  • @cck0728
    @cck0728 2 ปีที่แล้ว

    Good video... Why pressure transmitters are grounded but Temperature transmitter are not grounded?
    Thanks.

    • @realpars
      @realpars  2 ปีที่แล้ว +1

      The accepted wiring method for all transmitter types is to use a shielded twisted pair cable, with the shield grounded only at one end, usually at the PLC or DCS I/O cabinet.

    • @cck0728
      @cck0728 2 ปีที่แล้ว

      @@realpars Thanks for your kind clarification.... Keep it up...

  • @pearlsimelane9415
    @pearlsimelane9415 ปีที่แล้ว +1

    Hi what can cause the Totalizer to reverse?

    • @realpars
      @realpars  ปีที่แล้ว

      Thank you for reaching out with your question. The resolution might vary based on the installation method and setup. I recommend reviewing the installation manual and engineering design specifications for guidance. Alternatively, reaching out to your vendor can provide specific insights into potential issues. Wishing you successful troubleshooting and learning from RealPars!

    • @maxwellmakamba5112
      @maxwellmakamba5112 10 หลายเดือนก่อน

      Can I calibrate these using a prover tank if so please tell me how

  • @maxwellmakamba5112
    @maxwellmakamba5112 10 หลายเดือนก่อน

    Can i calibrate an ele tromagnetic floe meter using a prover tank

  • @akaikangaroo
    @akaikangaroo 9 หลายเดือนก่อน

    As far as I know those flow meters actually use coils instead of permanent magnets, because coils make it possible to reverse magnetic field which helps to avoid electrolysis on the electrodes

  • @idiotic0tom
    @idiotic0tom 2 ปีที่แล้ว

    Can this measure water flow or does a fluid needs to be ferromagnetic?

    • @realpars
      @realpars  2 ปีที่แล้ว

      The fluid needs to have a conductivity of greater than 10 us/cm. Distilled or purified water have conductivities less than 10 us/cm. Therefore, a magnetic flow meter is not suitable for these fluids. Tap water typically has greater than 10 us/cm conductivity and can be measured by a magnetic flow meter. Wehn in doubt, look up the conductivity of your liquid stream using an internet search or ask your magnetic flow meter vendor for the data.

  • @nipunmadushan5320
    @nipunmadushan5320 ปีที่แล้ว

    Superb

    • @realpars
      @realpars  ปีที่แล้ว

      Thank you very much!

  • @samuelsungstabtu7527
    @samuelsungstabtu7527 7 หลายเดือนก่อน

    Dont the electrodes need to be in direct contact with the flowing conductive fluid? How do you protect the electrodes from corrosion?

    • @realpars
      @realpars  6 หลายเดือนก่อน

      Hi Samuel, thank you for your question! In many industries, some sensors are designed to measure fluids without ever coming into contact with them, as they are placed outside the tube. If you're interested in learning more about how these sensors work and their applications, please check out the link provided www.omega.com/en-us/
      Additionally, there are numerous vendors offering these types of sensors. For more in-depth information, you can sign up for our platform to explore more about sensors.
      Happy learning!

  • @dhaneshvnair2304
    @dhaneshvnair2304 2 ปีที่แล้ว

    Is this suitable for metal pipe?

    • @realpars
      @realpars  2 ปีที่แล้ว

      Yes, metal pipe is preferred for the installation of magnetic flowmeters.

  • @ajaykumarjalagam8870
    @ajaykumarjalagam8870 ปีที่แล้ว

    What is the difference between DP transmitter and flowmeter?

    • @realpars
      @realpars  ปีที่แล้ว

      Thanks for your comment, and topic suggestion! I will go ahead and forward this to our course developers, hopefully we can create a course lesson answering that.

  • @paulrinehart5557
    @paulrinehart5557 2 ปีที่แล้ว

    I definitely like magmeters over paddle wheel sensors. I never knew that they were dependent on conductivity of the fluid, so thanks for that info.

    • @meeder78
      @meeder78 2 ปีที่แล้ว +3

      If the conductivity is to low you can't measure anything with it. The modern magmeters can achieve measurements in liquids as low as 1 to 5 uS/cm with certain limitations.
      If it is really low and you need high accuracy than your best option is coriolis mass flow. Otherwise you can also use vortex or ultrasonic flowmeters in liquids with low conductivity.

  • @microflowmeter
    @microflowmeter 7 หลายเดือนก่อน

    👍great~~

    • @realpars
      @realpars  7 หลายเดือนก่อน

      Thank you!

  • @cck0728
    @cck0728 2 ปีที่แล้ว +1

    Excellent video.... What type of flowmeter to be used for DM water or fluids with less than 10 us/cm conductivity?
    Thanks.

    • @MrWaalkman
      @MrWaalkman 2 ปีที่แล้ว +1

      Just about any of the rest. De-Mineralized water shouldn't present any problems with the material that the flowmeter is made of (unlike DI water). Without knowing your application, I can say that ultrasonic is not a good choice, too finicky in my opinion.
      And some that should be okay - depending:
      Thermal meters also present no obstructions, so it makes a good choice for media such as paints that tend to "gunk up" inside the pipe.
      Coriolis is great, but expensive.
      Positive displacement is an option, but will wear over time, making them eventually inaccurate.
      Differential Pressure is the "normal" choice, and would probably work fine for you.
      Vortex should be fine.
      There are other options out there, this is just off of the top of my head.
      The bottom line is that without knowing your application (so what's your Reynolds number anyway?), it is impossible to give you a definitive answer. So contact a flowmeter specialist and have them take a look at your application.

    • @realpars
      @realpars  2 ปีที่แล้ว +2

      Mr Waalkman gave a good response to this question. I find that vortex flow meters give a good balance of performance, ease of installation, almost zero maintenance, and applicable over a broad range of Reynolds numbers.

    • @cck0728
      @cck0728 2 ปีที่แล้ว

      @@MrWaalkman Thanks for your such a detailed response.... Appreciate!

    • @MrWaalkman
      @MrWaalkman 2 ปีที่แล้ว

      ​@@cck0728 You're welcome. :)

  • @khaledbarca7786
    @khaledbarca7786 2 ปีที่แล้ว

    Best video

    • @realpars
      @realpars  2 ปีที่แล้ว +1

      Thank you!

  • @김재진-x9o
    @김재진-x9o ปีที่แล้ว

    굿
    Good

  • @hosamyousef7368
    @hosamyousef7368 2 ปีที่แล้ว

    GOOD

  • @Yash13101994
    @Yash13101994 ปีที่แล้ว

    How can water be the conductor ?
    We need ferromagnetic conductor

    • @realpars
      @realpars  ปีที่แล้ว +1

      Tap water or process water contains minerals and other dissolved solids that are conductive. We just need a fluid with a minimum conductivity in order to use a magnetic flow meter effectively.

  • @dyakoazad7766
    @dyakoazad7766 ปีที่แล้ว

    ❤❤❤❤❤❤❤❤❤

  • @mzia854
    @mzia854 ปีที่แล้ว

    ❤❤❤❤❤❤❤❤❤❤❤

  • @ahmednor5806
    @ahmednor5806 2 ปีที่แล้ว

    🙏🌹🌹🌹

  • @OfirAviv1994
    @OfirAviv1994 4 หลายเดือนก่อน

    How it generates DC? should be AC.

    • @realpars
      @realpars  4 หลายเดือนก่อน

      Hi @OfirAviv1994. Thank you for your question. The flow meter must be powered by an external device like a power supply. Its electronics sense the signals, convert them to 4-20ma DC volts, and send them to a controller like a PLC or other controller board for monitoring or automation.

  • @polycmike5052
    @polycmike5052 2 ปีที่แล้ว

    Could that be also a solution for Ex-Areas?

    • @andreasiracusano488
      @andreasiracusano488 2 ปีที่แล้ว +2

      sure . there are magmeters also for EX areas

    • @realpars
      @realpars  2 ปีที่แล้ว +1

      When selecting a flow meter for installation in a hazardous area, you need to ensure that the meter is approved for operation in the specific classification of installation. This may affect which manufacturer/model number you use and the method of installation, including wiring. And yes, there are magnetic flowmeters which are rated for installation in electrically classified areas.