  • @willernst8376
    @willernst8376 ปีที่แล้ว +100

    Hey, a note on capacitor tests. Normally, when caps are higher than their ratings, they are not "over achievers", they are leaky. This means there is dc leakage across the capacitor. Most cap testers test the ac time constant of the caps to get a value. This is thrown off higher if the capacitor has dc leakage. This requires a special tester to test, esr and normal capacitor meters will not test this. So if it is high, just replace it, nothing ever goes up in caps. They always degrade.

    • @TheMatsushitaMan
      @TheMatsushitaMan ปีที่แล้ว +2

      Thanks for the info! I learned something too.

    • @Premier-Media-Group
      @Premier-Media-Group ปีที่แล้ว +5

      Mr. Carlson's Lab explains this in detail, as well as how to make a DIY cap tester.

    • @w5cdt
      @w5cdt ปีที่แล้ว +1

      Leakage can be checked in OHMS mode after waiting for the cap to fully charge to the meter’s ohms test voltage.

    • @willernst8376
      @willernst8376 ปีที่แล้ว +1

      @w5cdt maybe, but there is a problem with that testing method, as the meters testing voltage is only a couple of volts. So naturally, the leakage at that voltage compared to the operating voltage of several hundred volts will be very different. If you are seeing leakage at a couple of volts it is definatley bad. But it is not really a good way to test as there are not really datasheet leakage numbers for that voltage range. Not to mention, with large caps, it will just charge and never get a steady reading. An lcr meter or a high voltage capacitor leakage tester is really needed. You could run your own high voltage and use your meter to measure current. Though, that is a cumbersome setup and not really worth the trouble. I have a cheap lcr meter, and it will tell me all sorts of stuff like impedance, esr, q, capacitance and also accurately measures low resistances for motor windings.

    • @willernst8376
      @willernst8376 ปีที่แล้ว +2

      @w5cdt also are you a ham? That looks like a call sign

  • @MoraFermi
    @MoraFermi ปีที่แล้ว +20

    An important note on measuring capacitance: Your tool is measuring how long it takes for the capacitor to charge to a specific voltage using a specific current and calculates the capacity from that.
    Therefore, if the capacitor's internal isolation is bad (and leaks current through) or it develops internal resistance (making the resistor charge slower), the meter will read high.

  • @dillonmcdowell2
    @dillonmcdowell2 ปีที่แล้ว +22

    Dude I watch your videos as a jr food service technician, and I am amazed by the deep troubleshooting you do on a regular basis

  • @EkremOncirak
    @EkremOncirak ปีที่แล้ว +49

    As a starting technician, your videos make me more comfortable and familiar with some situations. Much Thanks from Türkiye 🇹🇷

  • @norbertoreyna8579
    @norbertoreyna8579 ปีที่แล้ว +1

    No one is perfect. I watch a lot of videos from different techs. I'm new to the trade and always take some from everyone. I appreciate all of you taking time out to explain the procedures you guys go through. One thing I don't like are call backs

  • @Arides2010
    @Arides2010 ปีที่แล้ว +6

    Had a blown fuse situation, where I fell back on your ‚mantra‘. I later found out, that the compressor I was troubleshooting had - as build by the manufacturer - additional fuses on L1 and L3. And there I was - freezing my behind off - wrecking my head why the only disconnect switch that had blown was L2.
    Oh the compressor was mechanically locked up, btw.

  • @electroimpex8897
    @electroimpex8897 ปีที่แล้ว +8

    Greets from Germany

  • @brettbuck7362
    @brettbuck7362 ปีที่แล้ว +7

    Caps tend to read high if they are getting leaky, the extra resistance adds to the apparent capacitance.

  • @derrickenbuenosaires
    @derrickenbuenosaires ปีที่แล้ว +5

    Oversized compressors will have stronger suction because of the larger compressor displacement. Your compressor is practically suctioning more than what the TXV can feed it.
    Back pressure should rise though once the ambient gets warmer.

  • @1mrhamel
    @1mrhamel ปีที่แล้ว +3

    Glad I wasn't crazy about using VFD's or inverter compressors. Thank you for answering my question!

    • @prodigy3xtc389
      @prodigy3xtc389 ปีที่แล้ว

      Addison hvac units have vfd for scroll compressors they are out of Florida

  • @tphvac87
    @tphvac87 ปีที่แล้ว +2

    Don’t apologize you do an outstanding job and we all make mistakes we’re human, but to stress again you are a very good technician man kudos!

  • @prodigy3xtc389
    @prodigy3xtc389 ปีที่แล้ว

    You are a very thorough technician and you pay close attention to detail, you don’t just fix what’s broken in front of you, you take the extra time to prevent the next failure! that plays a huge roll in any troubleshooting process I like that!

  • @9ohfiver
    @9ohfiver ปีที่แล้ว +3

    Love these videos. Best hvacr content on TH-cam

  • @michaellingenfelter2929
    @michaellingenfelter2929 ปีที่แล้ว +5

    Good job Chris. Love the videos. Really teaching me a lot. Experienced hot side tech getting back into hvac/r after a 30 yr absence.

  • @alimuh007
    @alimuh007 ปีที่แล้ว +4

    A cheese omelet, a cold brew coffee and a walk-in freezer down! Good morning!

  • @jayfowler4747
    @jayfowler4747 ปีที่แล้ว +2

    First test on any electrical fault should be insulation test before you move anything..... but I always dive in and disconnect things then realise my error... a tip for you is to lock your meter on test and go wiggle and jiggle stuff.. on more complex electronic systems its amazing what weird faults are caused by insulation leaks..and I have to say my ocd gets triggered when you say a fuse went bad, it's not gone bad, it did its job perfectly if anything it went well and is just unusable after doing its job, perhaps the fuse has opened or triggered the fuse may be usable phrases....... End of ocd ramblings...... Keep the vids coming I love to watch....

  • @stevencossaboon3237
    @stevencossaboon3237 ปีที่แล้ว +2

    Another great video Chris. Thank you for the knowledge.

  • @Demy26
    @Demy26 ปีที่แล้ว +2

    Amazing instructor

  • @youtubeonly7541
    @youtubeonly7541 ปีที่แล้ว +9

    Hi Chris, the meter charges the capacitor with a low voltage and continuously integrates the current flow until it drops to 0-ish. Based on the accumulated current it does some math and approximates how many farads a good cap would have.
    If the capacitor has failed with low internal resistance, it draws more current. This is why bad caps show higher than normal capacitance.
    More sophisticated measuring tools exist of course, but it's not common to see in a handheld multi meter.

    • @stevetech7335
      @stevetech7335 ปีที่แล้ว +3

      This is it, but to rephrase it, the caps can fail in multiple ways. One is the loss of capacitance, another is becoming leaky. The meter approximates capacitance by measuring how long it takes for the cap to fully charge. If the cap is leaky, it takes a bit longer to fully charge because it's leaking as it's being charged. This results in a false higher capacitance reading.

    • @HVACRVIDEOS
      @HVACRVIDEOS  ปีที่แล้ว +3

      Right on thanks for the info!!

    • @patrickdougherty2777
      @patrickdougherty2777 ปีที่แล้ว +3

      Never knew that. Thank you for the education.

    •  ปีที่แล้ว +1

      Therefore, only sure way of testing capacitor is by measuring its current and voltage.

  • @thephantom1492
    @thephantom1492 ปีที่แล้ว +3

    As for why the capacitor is up in value, it can be that the paper insulator inside was slightly thinner than normal. The capacitance is determined by both the surface area and the distance between the two plates. If the paper is thinner then it get closer, which make the capacitance goes up. The downside is that the voltage insulation goes down. But as long as the insulation is high enough and the capacitace is within specs then they declare it good.

  • @PhillipFrischman-vo8gm
    @PhillipFrischman-vo8gm 3 หลายเดือนก่อน +1

    Bro u did a great job.. and you explained everything to...

  • @DanO181919
    @DanO181919 ปีที่แล้ว +3

    Same here with the Wago’s. I wish the lever would snap in when you would close them. Other than that I love Wago’s.

  • @samuelgilbert9734
    @samuelgilbert9734 ปีที่แล้ว +4

    29:00 The high capacitance might be that the capacitor is electrically leaky (acting like a resistor instead of a capacitor). The meter measures the capacitance by timing how long it takes to charge with a given voltage. If the capacitor lets some current flow, the meter will measure that as higher capacitance although it's not actually the case.

  • @peeyushchauhan2189
    @peeyushchauhan2189 ปีที่แล้ว +3

    Quite interesting how you explains every problem..

  • @davidlong1786
    @davidlong1786 ปีที่แล้ว +5

    Perhaps that capacitor measuring higher than normal is a sign that it's ESR (Equivalent Series Resistance) is too high and the cap is about to fail. I do know that in audio components (receivers/tuners/amplifiers) that electrolytic caps that measure higher than normal is a good sign that they are out of spec and they are becoming more of a resistor (ESR) than a cap.

  • @stormeagle28
    @stormeagle28 ปีที่แล้ว +1

    High inrush currents are no problem for the motor (you can overload them 5..10 times their normal rating for a short period of time and it will not damage them), only for connectors, connections and especially for contactors.

  • @alejandromedina2138
    @alejandromedina2138 ปีที่แล้ว

    Keep up the great work, I enjoy watching. Explaining everything, its really helpful.

  • @NewPowerlifter
    @NewPowerlifter ปีที่แล้ว +1

    Awesome video! Thanks for taking the time to walk us through these problems and how you walk from symptom to big picture problem

  • @Monkeh616
    @Monkeh616 ปีที่แล้ว +1

    The trouble with Wagos in an application like that is, apart from the lever issue, if they're not fixed in place along with the wires, they can vibrate loose.
    The lever issue is pretty easily resolved by using the push-in types (2273), so long as your wire is sufficiently stiff or you fit ferrules. They're still removable, you just twist while pulling. Even with vibration concerns, there's less chance of error fitting them than a wirenut, especially working in awkward spaces like that.

  • @glennschlorf1285
    @glennschlorf1285 ปีที่แล้ว +1

    Ramble on brother..... always learning while watching... good stuff

  • @cactuscamo9685
    @cactuscamo9685 ปีที่แล้ว +4

    I love your videos but at 0:41 when you said this is my rack i had a good chuckle. Keep up the good work!

  • @hvac01453
    @hvac01453 ปีที่แล้ว +1

    just a note from my experiences over the years when I see amp draws higher than another from the exact same motor, other than capacitors.... check the blade. many times someone has replaced it with a different blade, 4 wing to a 3 wing, or 17 degreee to a 23 degree pitch, then also the blade insertion depth. These are variables. as long as the amperage is under the nameplate rating you should be OK. The other thing to check is handshaking of the motor shaft of both in question. This can be done with the blade on too. Just my two cents.

  • @grudd61
    @grudd61 ปีที่แล้ว +1

    Another great video!!! Always looking forward to the next!

  • @misterhat5823
    @misterhat5823 ปีที่แล้ว +1

    A lot of capacitance meters don't expect leakage or excessive ESR. Both can make a capacitor read high. The capacitance isn't high, and it's defective in some other way.

  • @Pendrige
    @Pendrige ปีที่แล้ว +3

    That compressor sounds surprisingly good, given how bad the head looks.

  • @sharkey086
    @sharkey086 ปีที่แล้ว +1

    Always enjoy the videos, even though I'm not a HVAC guy. I do especially appreciate your choice in smartwatch case/band. Used Supcase for years!

  • @lwilton
    @lwilton ปีที่แล้ว +2

    Depending on how your capacitance meter works, there is a possibility that a cap reading high may be leaky, that is, have a resistance between the terminals as well as a capacitance. You can switch over to Ohms and clip onto the cap and see if it goes open circuit or not. You will probably have to let it sit a couple of minutes to get a good reading.

  • @vali7443
    @vali7443 ปีที่แล้ว +1

    Thank you for the videos really helpful

  • @zekenzy6486
    @zekenzy6486 ปีที่แล้ว +1

    Great Video. Thank you for sharing

  • @dalemarr70
    @dalemarr70 ปีที่แล้ว +1

    I had a unit that was popping the 50A main breaker. 50 + year old Federal. Replaced it, everything seemed fine. Popped the new one, after some time. (I was gone) Turns out it was the condenser fan motor getting hot, seizing after some time. Then the compressor would overheat & pop the breaker.

  • @garenharutyunyan4275
    @garenharutyunyan4275 ปีที่แล้ว +1

    Good job Chris...Great video Thank you

  • @Dunhambulance
    @Dunhambulance ปีที่แล้ว +1

    Thanks for another great video. Great job, always appreciate your take on troubleshooting.

  • @Ronnocbot
    @Ronnocbot ปีที่แล้ว +1

    29:10 the way he yeets that capacitor 😂

  • @thesilentonevictor
    @thesilentonevictor ปีที่แล้ว +1

    Great job Chris

  • @scott5654
    @scott5654 ปีที่แล้ว +1

    Excellent 👍🏻
    Thanks ‼️

  • @805HVACR
    @805HVACR ปีที่แล้ว +1

    May also see scrolls with internal unloaders too possibly

  • @flowmaster802
    @flowmaster802 ปีที่แล้ว +1

    I've been watching your videos for a long time and barely subscribed to your channel didn't realize I wasn't subscribed but I've learned so much from you and I don't even work on these but them going love them

    • @HVACRVIDEOS
      @HVACRVIDEOS  ปีที่แล้ว

      Thanks bud glad you enjoy the videos

  • @christophergonzales1321
    @christophergonzales1321 ปีที่แล้ว +2

    Sunday mornings with Chris

  • @hmrody
    @hmrody 11 หลายเดือนก่อน

    I learn so much from your videos. You do such a great job and your troubleshooting skills with the explanation of both how and why are awesome. I appreciate your hard work putting these videos together... It takes a lot of hard work... Chris did state that a 10 µF testing at testing 10.57 µF was odd and did indeed replace the capacitor. As the specification for a MARS 12008 is ± 6% as shown, it was iffy in my . I personally think there will be manufacturing variation, but as it was close to testing out of spec., and to prevent a callback, replacement of a ~$6 capacitor is prudent. Regarding Mr. Carlson's lab DIY capacitor tester, yes, he does amazing work. Have an awesome day!

  • @Telewaifus
    @Telewaifus ปีที่แล้ว +1

    When capacitors are higher than expected is due the ESR value screwed up. Replace them for safety, but usually are more a problem in low signal application

  • @JFirn86Q
    @JFirn86Q ปีที่แล้ว +2

    That capacitor could be leaky (electrically), which would cause your meter to read a higher capacitance. Fairly rare to see a capacitor be that high over rating after being in service for a long while.
    The reason being leaky causes this is that your meter is timing how long it takes to charge it up, and deriving capacitance that way. If your capacitor is leaky, it will take longer to charge - thus higher capacitance read by the meter (but it actually isn't higher).

  • @timer51309
    @timer51309 ปีที่แล้ว +1

    Have you tried the new inline Wago connectors? I use them to connect to my meter leads when I do a voltage reading.

    • @HVACRVIDEOS
      @HVACRVIDEOS  ปีที่แล้ว

      No I haven't tried them yet

  • @coryevangelista310
    @coryevangelista310 ปีที่แล้ว +1

    We’ve been taking all the walk in systems off our old racks when they go kaput. How have y’all been handling leaks in evaporators and condensers with units on the rack ?

    • @HVACRVIDEOS
      @HVACRVIDEOS  ปีที่แล้ว

      I will discuss this on my Livestream this evening 3/6/23 @ 5:PM (pacific) come over and check it out
      th-cam.com/users/liveoD5k3jZQfb0

  • @idontneedaname85
    @idontneedaname85 ปีที่แล้ว +1

    That rack looks like it lived its life in the ocean!

  • @Goldstacker1972-kp2bh
    @Goldstacker1972-kp2bh 8 หลายเดือนก่อน +1

    I use a laser light because after 40 years of this work I don't have much feeling left in my hands.

  • @jazbell7
    @jazbell7 ปีที่แล้ว +1

    When capacitors age they may get electrically leaky. This will cause the typical capacitance meter to read high. When capacitors get leaky, they usually have higher ESR (Equivilent Serias Resistance) which will make your motor require more current.

  • @juliodorothal5120
    @juliodorothal5120 ปีที่แล้ว +1

    Greate video,
    I work at a site that has 17 daikin variable compressor units.
    They do work nice, but to much sensors 😂

  • @sherwinalvarez7365
    @sherwinalvarez7365 ปีที่แล้ว +1

    Great video

  • @heavydiesel
    @heavydiesel ปีที่แล้ว +1

    If the compressor has a lot of liquid refrigerant condensed in it that can cause a low megger ohm reading, keep meaning to make a vid and see what exact effects it has.

  • @rwoodenselisdor
    @rwoodenselisdor ปีที่แล้ว +1

    good content

  • @qwpz
    @qwpz ปีที่แล้ว +1

    Coming here from IT field, after this kind of failure we would be talking about setting up some monitoring (with automated notifications) so we get an early warning (like idk, for constantly increased compressor temperature or something). Is that possible for AC? Or you just rely on customer notifying you and preventive maintenance?

  •  ปีที่แล้ว +1

    Does anyone knew where to find, or who is making, ratcheting wrenches for king/rotalock valves stem nut??? I have been working with them in one company which I work for earlier in my life, but I am not able to source them now!

  • @tracysellman1562
    @tracysellman1562 ปีที่แล้ว +1

    Hey Chris, to fallow up on your tangent as you say, I am old school and retired in 2013, but what ever happened to two Stage scroll compressors with a loader un-loarder, why haven't I heard more about these ? I know bigger chillers and 100 and 200 ton systems have something silular. Was just wondering why manufacturers for smaller commercial and residential A/C systems have not inbraced this? PS: Good video brother. :)

  • @Chris_In_Texas
    @Chris_In_Texas ปีที่แล้ว +1

    24:35 Man that fan motor is really digging into the coil there! Seems like it needs to be adjusted a bit higher! 🤦‍♂🤷‍♂

  • @joeywest
    @joeywest ปีที่แล้ว +1

    Wrong type of fuse for the condenser fan motor. The ccmr (green) is what it needs like the other fuses. The yellow ones get weaker and weaker every time the motor kicks on and eventually blow.

  • @sarah1390
    @sarah1390 ปีที่แล้ว +1

    The Capacitor going up in value is totally possible. I have been watching Vintage Tube Radio videos from Mr. Carlson's lab I have heard him in multiple videos saying that Old Capacitors (Ex. Made in the 1950's) to a capacitance tester (which your multimeter just measures capacitance) can look like an overachiever with higher than tolerance capacity. Though when placed on a capacitor Leakage tester (Very dangerous as it can deliver thousands of Volts) it is shown to be Electrically Leaky. Therefore capacitors when they go bad can turn into a Resistor and look like they have a higher capacitance to your multimeter when in fact they are BAD!!!! I know that Mr. Carlson's lab has built himself a low voltage capacitor leakage protector but unsure of what it's limits are for testing as it was built for Audio capacitor testing but because HVAC doesn't require nearly the same tolerances as what audio requires, then it may work but it is a build it yourself device that is available through his patreon so that is not a go to solution but he does put out some good videos explaining Capacitor Electrical leakage.

  • @jpcallan97225
    @jpcallan97225 ปีที่แล้ว +1

    While clearly not the problem in this case, if a fuse is a time-delay type, older fuses can get what I call "Fuse Fatigue". I've seen it on single phase residential A-C compressors. In time-delay fuses the fuseable link is packed in special sand within the fuse that keeps it in place and prevents the fuseable link metal from falling into molten blobs. After many hard starts (high inrush amp draw) the fuseable link will have partly melted then re solidified over and over. Eventually the fuseable link is so compromised by the repeated partial melting cycles that it lets go. Cut an inexplicably failed one open and do a necropsy on it.

    • @Monkeh616
      @Monkeh616 ปีที่แล้ว +1

      You can also suffer from fatigue with open wire fuses. High temperatures during inrush and prolonged load with exposure to oxygen and moisture causes corrosion until they finally let go on a rough inrush like motors - vacuums are a good trigger. Not a common problem these days.

    • @quattrohead
      @quattrohead ปีที่แล้ว

      Higher current fuses rarely blow for no reason, but low ma rated fuses often do. With open and glass fuses, you can tell if they just got tired or blew because of overload.

  • @bubbakushingtonIII
    @bubbakushingtonIII ปีที่แล้ว +1

    This is how you make money. You have to work and you'll have to leave at times you don't want.

  • @LongTrout
    @LongTrout ปีที่แล้ว +3

    No one can afford to pay the well-trained competent 24/hr a day on call Tech what they are really worth.

  • @chaseherigstad8576
    @chaseherigstad8576 11 หลายเดือนก่อน +1

    Jeez those motors are just sitting on the condensers, major vibration leak point

  • @LongTrout
    @LongTrout ปีที่แล้ว +6

    I always got up when the call came. I was never paid to be on call all those years and was certainly no paid well enough to stop doing my wife and go into work. I got the shankleg. I hope you paid proper. No one wants to do this stuff anymore because you don't get paid what you should even though your boss gets paid just fine.

    • @HoundDiggityDog13
      @HoundDiggityDog13 ปีที่แล้ว +1

      Underpaid, over worked for sure. Theives

    • @LongTrout
      @LongTrout ปีที่แล้ว +3

      @@HoundDiggityDog13many who worked the business got robbed by shady bosses. Use to be a man could support his family on the wages of a tech. No longer though. In Lansing Michigan maybe 17.00 to start and sure ain't gonna a nickle overtime unless already over 40 hrs no matter the time of night you go out. Some companies like the one I left even want to shank you drive time in the morning to first Job. They sure don't hourly to be on 24/7 call. We all know the deal.

  • @markae0
    @markae0 ปีที่แล้ว +1

    The leaks at 31:09 in the video was crazy!

  • @WS-gw5ms
    @WS-gw5ms ปีที่แล้ว

    Can't agree more you need to tape down those levers. They can absolutely open up.

  • @awyeh1234
    @awyeh1234 ปีที่แล้ว +1

    BX Wire hsd s specific copnnector, romex connectors arent approved

  • @codykeith876
    @codykeith876 ปีที่แล้ว +2

    What brand of gloves are those?

  • @ahmedalyami1014
    @ahmedalyami1014 ปีที่แล้ว +1

    Hvac ❤️❤️

  • @faintsmile3279
    @faintsmile3279 ปีที่แล้ว +2

    doesnt that 10-20% written on capacitors mean that the capacitance is somewhere between that range from the advertised capacitance when its manufactured?
    earlier on when i had just started working with single phase motors i thought that was the range which is acceptable for the capacitor to operate but when i did some more digging i remember finding out that had nothing to do with it and it was just the same thing as the + - 5grams on products weight.

    • @RachelMant
      @RachelMant ปีที่แล้ว +8

      In electronics the tolerance on a capacitor is both the allowed tolerance when manufactured *and* the allowed value tolerance during service life.
      Any 10% value tolerance capacitor reading more than 10% under the rated value when out of circuit, is a bad/dead capacitor that is no longer fit for purpose.

    • @faintsmile3279
      @faintsmile3279 ปีที่แล้ว +2

      @@RachelMant so its actually both good to know

  • @KoScosss
    @KoScosss ปีที่แล้ว +1

    Nice mountains

  • @kennethlobo4420
    @kennethlobo4420 ปีที่แล้ว +1

    Great video. What make is your insulation resistant tester?

    • @HVACRVIDEOS
      @HVACRVIDEOS  ปีที่แล้ว

      This one was a Klein Insulation tester, I actually just gave it to my apprentice . I Keep a Fancy fluke one on my truck

    • @kennethlobo4420
      @kennethlobo4420 ปีที่แล้ว

      @@HVACRVIDEOS very Generous and thoughtful of you.

  • @joec.thurman5856
    @joec.thurman5856 ปีที่แล้ว

    As a life long field service technician, PLEASE stop talking. you are doing a great job.

  • @josevillanueva5140
    @josevillanueva5140 ปีที่แล้ว +1

    I like ur videos bro 😀😀

  • @nickcastillo8511
    @nickcastillo8511 ปีที่แล้ว +1

    If I have 200 ft of piping, would I still charge the receiver 3/4?

    • @HVACRVIDEOS
      @HVACRVIDEOS  ปีที่แล้ว

      with long lineset runs the reciever needs to be sized usually bigger so it can still hold the entire charge, so you need to find out if it has enough storage capacity

    • @nickcastillo8511
      @nickcastillo8511 ปีที่แล้ว

      @@HVACRVIDEOS perfect, it is also water cooled!

    • @HVACRVIDEOS
      @HVACRVIDEOS  ปีที่แล้ว

      I will discuss this on my Livestream this evening 3/6/23 @ 5:PM (pacific) come over and check it out
      th-cam.com/users/liveoD5k3jZQfb0

    • @nickcastillo8511
      @nickcastillo8511 ปีที่แล้ว

      @@HVACRVIDEOS hell yeah!

  • @mathewahrens4475
    @mathewahrens4475 ปีที่แล้ว +1

    I prefer using plumber’s tape to secure my caps.

    • @HVACRVIDEOS
      @HVACRVIDEOS  ปีที่แล้ว

      I will discuss this on my Livestream this evening 3/6/23 @ 5:PM (pacific) come over and check it out
      th-cam.com/users/liveoD5k3jZQfb0

  • @prashanshan7125
    @prashanshan7125 ปีที่แล้ว +3

    Good work..! Can u make separate video about Liquid injection Valve and Head pressure valve diagnostic..? Thanks.

  • @whitestripe1547
    @whitestripe1547 ปีที่แล้ว

    What is the life expectancy on a system like this?

  • @supertip777
    @supertip777 ปีที่แล้ว +3

    American machine and wire, a complete mess, in Europe is the standard much safer and organised inside with label's and normal route.

  • @jagdtigger
    @jagdtigger ปีที่แล้ว +1

    29:10 those multimeters are pretty bad at measuring capacitors when it comes to accuracy.

  • @SmallKittyPaw
    @SmallKittyPaw ปีที่แล้ว +1

    I would guess that paint won't go off the head just during one day. As far I can tell it also got quite rusty. So whole theory of it being bad just for one day is probably a miss

  • @NazNazFrigoriste
    @NazNazFrigoriste ปีที่แล้ว +1

    Adding refregirant without finding and repairing the leak before ??

    • @HVACRVIDEOS
      @HVACRVIDEOS  ปีที่แล้ว +1

      I will discuss this on my Livestream this evening 3/6/23 @ 5:PM (pacific) come over and check it out
      th-cam.com/users/liveoD5k3jZQfb0

    • @davejohnsonnola1536
      @davejohnsonnola1536 ปีที่แล้ว

      Sometimes you have to save product if location does not have backup storage

    • @NazNazFrigoriste
      @NazNazFrigoriste ปีที่แล้ว

      @@davejohnsonnola1536 The fluid regulations are less harsh in your area in this case...

  • @HarryHafsak
    @HarryHafsak ปีที่แล้ว +1

    Lol "rack". It's a doghouse. All the circuits are separate.

    • @HVACRVIDEOS
      @HVACRVIDEOS  ปีที่แล้ว

      I will discuss this on my livestream on TH-cam this evening 4/24/23 @ 5:PM (pacific) come on over and check it out th-cam.com/users/liveg7_emG3FE1E

  • @shaneevans8963
    @shaneevans8963 ปีที่แล้ว +1

    I have to agree that your body is a tool. My wife calls me one all the time, now I know why.

  • @carlyleworkman1928
    @carlyleworkman1928 9 หลายเดือนก่อน +1

    👍🏿

  • @shine-cg9uf
    @shine-cg9uf ปีที่แล้ว +2

    👍💪❄️🇺🇸 nice work thanks

  • @marcosgraells1820
    @marcosgraells1820 ปีที่แล้ว +1

    Hvacr God!!

  • @FrNMGuy
    @FrNMGuy ปีที่แล้ว +1

    Squirrel brain in the middle there. Troubleshooting, oh pretty mountains, troubleshooting

  • @marjones69
    @marjones69 ปีที่แล้ว +1

    The wagos are kinda trash...there's is another brand that holds way stronger

  • @FishyCanada
    @FishyCanada ปีที่แล้ว +1

    "Heat producing device"

  • @TravisDoesGames
    @TravisDoesGames ปีที่แล้ว +1

    🏔😍

  • @steveblake8766
    @steveblake8766 ปีที่แล้ว +1

    553 Thumbs uP

  • @gregdennis3523
    @gregdennis3523 ปีที่แล้ว +1

    Feels like you are always triaging these systems. Multiple problems and systems.