Allah Pak apko Salamat rkhay. Ameen. Ek video MC ya MCO pay Bhi bna dein.. complete guide agr meter lag Gaya hai MC ya MCO Ka kesy pta chlayga k wo krwana h ya hgya hai
Brother Batteries b install karay sath aap. Beshak zada heavy na lagwai bus 48V poray karday. Is taraha aapka system off nhai hoga. Load Shedding mai backup b mil jai ga.
Yai positive mai he show hota hai agar import hogi tab be positive agar export hogi tab be positive,low voltage 180 per set karain aor high 270 ya 80 per
6mm cable of good quality in ac like pakistan cables or universal or fast is more than enogh for ac output. 4 pole dc breaker of himel 1000v should be used . 4 pole himel dc breaker 16 amps 1000volts easily available on website power house express. In market ususlly copy is available of renowned breaker like hager or scheider...so better to use himel or chint...himel breaker are availble under flagship of clipsal pakistan . For dc 4mm or 6mm cable tinned coated and xlpo insulated to be used which is better since xlpo cables are fire resistant and uv reaiatant. Dc tin coated xlpo of universal ,fast and pakistan cablea are best.
Mere installer ny b mujy ac breaker 25 amp or dc breaker 20 amp py forcefully insist kiya hai baqi koi b installer or shopkeepers is pay mutafiq nai thay
Ac k leyai 7/52 jes nai be kaha hai belkul ghalat kaha hai,7/52 DC k leyai teek hota hai but single input and output walai inverters k leyai,aapka inverter dual input and output wala hai esmai load ek wire per nahi hota,
Jo wire aap nai lagwayi hai enough hai, VPD aapko wahi voltage and amps dekayaiga jo aap import ya export karogai,agar zyada export karogai tho zyada voltage and amp dekayaiga agar kam karogai tho kam dekayaiga,wo main DB wala sirf jo wapda sai aaraha hai wahi dekayaiga,aapko yai main DB wala nahi lagana chaheyai ta..
GM pakistan cable 6mm ya 7/44 1 he bat hai ap 7/44 he lagi rehne den its more than enough for your system center waly jo tomzn changeover hai apka wo copy han Dc Breakers of solar system apko change krna he honge 125A nahi thek UA breakers bhi wrong choice hai apki
Dear Brother, After reviewing your entire setup, particularly the protection devices, I have a few observations for you to consider. It appears that the SPD (Surge Protection Device), which ideally contains Metal Oxide Varistors (MOVs), is missing from your distribution boxes. These are ceramic-based components that adjust their resistance based on the voltage applied to them. As the voltage increases, their resistance decreases. Typically, these devices have a small window or indicator that is green, showing that the device is functional. They are directly connected to your AC/DC ground earthing. I didn’t notice these in any part of your setup, either next to your nitrox inverter or in the main house DB box, which recently burnt out and was replaced. Please take this matter seriously for the safety of your home and solar system by ensuring that both AC and DC SPDs are installed.What I observed in all your DB boxes are breakers and changeovers, but not SPDs. This could likely have been the reason for your recent electrical fire. A heavy surge from the grid can only be managed by an AC SPD, while a surge from the solar system requires a DC SPD. Furthermore, if you install AC and DC fuses together with the SPDs, it would offer comprehensive protection for your system and home appliances.Your voltage and current protection device (MORA) is adequate for additional protection. However, I strongly recommend installing both AC and DC SPDs with individual ground earthing, along with AC and DC fuses. I have extensive experience and practical knowledge of solar systems and have assisted people in installing systems not only in Pakistan but also in the Middle East and Australia. Unfortunately, many new or low-cost installers in Pakistan tend to neglect these additional protective measures, but they are critically important. Lastly, 6mm AC is capable of handling a full household load up to 9kw ideally. To give you an idea, note the followings. For a 6mm² copper wire, assuming it handles up to 40 amps and considering a typical 230V AC supply:Power (Watts) = Voltage (Volts) × Current (Amps)Power = 230V × 40A = 9,200 watts (or 9.2 kW).This means a 6mm² copper wire can safely handle an electrical load of up to 9.2 kW under ideal conditions.
What what I want to explain you my installer now told me that these Haeger breakers have already inbuilt SPD so separate spds are not recommended so that's why I have not installed otherwise I might have installed SPD separately but he told me thatthese Haeger breakers have already inbuilt SPD. Vikas these breakers costered me three times of a normal Tomszn breakers so I trusted on the new installer but I don't know exactly of that. If you have a proper knowledge that these Haeger breakers do not have any SPD in built please do let me know. Thanks in advance.
@CityHappyFamily bhai, your Haeger breakers are simply a breaker... SPDs have a difficult look.. they have a small cartridge type look that has a small hole showing green colour (if they are functional). Secondly, if your installer is so-called saying that these breakers have built SPDs, so have you noticed any Earth wire output from the breaker that is connected to your AC Ground earthing? Have you done AC and DC Earth Boring in the ground while installing the system? Usually, SPDs are connected to those Earth Boring, which should be one AC bore and 2 Bore for DC Current , in ideal solar setup. Lastly, according to my knowledge, Haeger breaker doesn't come brand new in Pakistan but often brought used in Lots. So their integrity and efficiency are questionable being used item. Your installer has lied to you for sure about Haeger breaker with inbuilt SPD. Please Google SPD Devices to identify the look of it for comparison. They never have a breaker function. If your haeger breaker has Earth wiring output, which is connected to ground AC Earth bore, then you may call it SPD. But again, it should have a cartridge which burns during high surge...
I have been seeing your vlogs since you installed Nitrox based Solar System, Dukh hota hai itna kharch karny k bad 2 taky, dishonest technical, shopkeeprs kee waja sy apko itna kuch face karna para.. really nuksan apka huwa but i can feel this, Alhamdulillah mai ne apne gar p lgwaya 3kw Nitrox based, sab kuch khud samja, lya, or lagaya b Alhamdulillah Mashallah Acha chal raha hai
@@CityHappyFamily exactly unky lye Allah kafi hai.. Ap toh kher mujsy senior or bary hai I'm 26year old but mai ne complete ek month dekha samja or next month k starting m solar panels, or complete saman even ek ek nut bold k wiser khud lye or lagaya b khud along with my engr mamu with the help of knowledge and skills i gathered watching solar installation yt videos.
@@CityHappyFamily 😇🥰 baki I'll upload a video on my channel ap dekhna kese lagaya hai and last but not least apne jo fan use kya hai wo b theek lekin 12v wala fan use krwn nitrox p phr result dekhen.. mera toh din k time heavy load pr b heat nh hota
اصل میں آج کل ہر کسی نے سولر کا بزنس سٹارٹ کیا ہوا چاہے وہ پلمبر ہو الیکٹریشن ہو انجینیئر ہو اس نے اپنا سیٹ اپ شروع کیا ہوا ہے اپ کو ایک پراپر کمپنی سے سولر سسٹم لگوانا تھا تاکہ وقت کے ساتھ وہ اپ کو مینٹیننس بھی دے سکیں یہ میں آپ کو اس لیے بتا رہا ہوں کہ میں خود بھی ایک سولر کمپنی میں کام کرتا ہوں اور ہم لوگوں کو ایک سال کی مینٹیننس بھی دیتے ہیں
سر اپ کی بات ٹھیک ہے میں نے لاہور کی ایک کمپنی سے کیا تھا لیکن وہ لاہور کی کمپنی کو یہاں پہ جو ہے نا ان کے پانچ سے چھ بندوں کو رکھ کے ان کی اکموٹیشن دینا ہے کھانا دینا یہ سب کچھ ڈفیکلٹ تھا کیونکہ یہاں ہمارے لوکل چھوٹے شہر کے اندر کمپنیاں نہیں ایسی کام کرنے والی لاہور میں یہ ملتان سے بلانا پڑتا اور ان کو یہاں پہ فوڈیشن دو تین دن کی رہائش دینا یہ کافی ڈفیکلٹ ٹاسک تھا اور پھر کوئی مسئلہ مسائل اور لاہور سے یہاں انے کے وہ چارجر سیپریٹ پے کرتے ہیں اس کے لیے میں نے لوکل جو ہے نا بندے سے کام کروایا ہے ورنہ مجھے ائیڈیا تھا میں نے لاہور سے ملتان سے کوٹیشنز وغیرہ لی تھی اس کی۔
جناب کیبل سائز مسلہ نہیں کیونکہ تھری فیز میں کرنٹ ھر فیز پر ڈسٹربیوٹ ھو جاتا ھے ۔ آپ یہ دیکھیے کی چینچ اور کتنے ایمپئر کا تھا اور سب سے اھم بات یہ ھے کہ کیا آپ نے ھر کنکشن ٹرمینل پر تھمبل پراپر پنچنگ ٹول سے لگوائے ھوئے ھیں یا نہیں اگر نہیں تو یہ حادثہ دوبارہ بھی ھو سکتاھے۔ برائے مہربانی اوور سائز کیبل سے اجتناب کیجئے۔
بھائی جان تھمبل تو لگاتے نہیں ہیں ان کو سب سے زیادہ مسئلہ تو یہی لگتا ہے کہ تھمبل لگائیں اگر ہر کنیکشن پہ تو مسئلہ ہی نہ ائے سارے بریکرز ویسے ہی تاریں وہ ٹیڑھی میڈی کر کے لگا دیتے ہیں
bahi main to Labours ki chori our idiocies se tang a kr, Maximum ghr main kam khudi kr leta. Jasy following. All electrical repairs or installations plumbing repairs. to some extent mistary work mechanic etc and results are 100 % better
Bahi koi jan bhch kr kam karb nhi kerta or sub mazdor ya electrician ek jaise nhi hoty. Ap sub ko nhi bolly sub laber ek jaise hu. Log lakho ka saman ly lyty ha per laber dyty hovy jan jatti ha. Main khud electrician hu.
Sorry for your loss. You've taken good measures to replace wiring and breakers which is a big safety hazard otherwise. Good job! If possible kindly share the name of the shop and contact from where you purchased the breakers etc. Stay blessed!
Humaray city mein available nhe thi bro, wrna Fast cable ya pakistan cable he dlawata . Lakin yahan tu locally gharon mein bni huwe cables he milti hein
@@CityHappyFamily my personal experience Pakistan cable say achi koi bhi nahi pure new copper use hota hey is may baki cables may reprocesssd copper hota hey.
@@raobilalahmed872 G suna tu yehe hy baqi Allah malik. Lakin sir GM local made cables sybkafi behtr hy. Pakistan cables ka alternative shayed na ho lakin achi hy . Meine already ju nikle hein cables ussy kafi behtr hy GM
@@CityHappyFamily may nay apna ghar banaya tha to kafi research ki thi cables per Pakistan cable wallun say meeting ki ku k koi shop wala bhi Pakistan cable sale kernay pay khush nahi tha waja Kam profit aur Pakistan may jitni bhi copper import hoti hey uska major part Pakistan cable walay import kertay hain baki used copper ko reprocess kerkay use kertay hain
Aap nay ku k her cheaz best lagaie howi hey isi liye apko may detail say bata raha houn main cheaz cable hey in sub ki safety k liye Naraz mat hoiye ga. JAZAK ALLAH KHARE.
7/44 Pakistan cable istamal Karen baki main ne pichli video main comment kiya he. Main ip65 or ip21 install kar raha hon govt building main. Aap kahan rehty hain mughey nahi pta aghar mughy pta ho to main aap ka free kaam kar k don ap yad Karen ge aap bohat achey hain aap ko acha elect nahi milta.
@@CityHappyFamily xhalin ap dhek lain. comment mi itna samja nai sakta ap ko. ec thra kay changeover 6/7amp taq thek hain.jab ap ka load 5/6 kw chaly ga to changeover ki power say double bji cross kar jay ga. orjab ap ghar na ho inverter 7/8kw export kary ga to.. wo sab ec say ho kay jay ga.. jo almost 20amps say oper hai. ap samaj sakty hain kay kianhota haai. ec naat ko confrim karny kay ley 1 bar apnay kharab changover ko khol kar zara check karin... ap khod kahin gay kay ye kia baywaqoofi ki thi main nay
May Allah keep your family safe and sound .
❤️❤️❤️🥰🥰🥰😍😍
My dear God Bless you and your family Aameen Aameen Aameen Yaa Rabbul Aalameen
JazakAllah Khair bro ❤️❤️❤️❤️❤️
Assalamualaikum dear brother, green meter k leyai Jo display wali device aap nai lagwayi hai wo SPD nahi VPD hai voltage protection device..
W.salam, ues brother you are right.
ya jo ap inverter k pas UA k Breaker dekha rhy ho ya isolator lg rhy hin Breaker ni lg bahrhall rhy ap chack kar lejye ga
G hy tu yay breaker he humaray 1st installer ny apni mrzi sybkia tha G
bhai apko abhi b safety setup ki need hai
and apko tomzn company per jana hoga
Ok
Hager ky breakers lgwae hein , wu 3 to 4 times hein tomszn ki price sy
Dosri baat bro 10no tomzn lene sy behtr hy, I will go for chint
Use original breakers , dnt use DC breaker , use 7/52 wire , use chint breakers from
Diwan , never use local change over ,
G thek hy shukria
I will help you free of charge.
Allah Pak apko Salamat rkhay. Ameen. Ek video MC ya MCO pay Bhi bna dein.. complete guide agr meter lag Gaya hai MC ya MCO Ka kesy pta chlayga k wo krwana h ya hgya hai
Aameen, G zaror insha'Allah
G bna dein. I need it too
@@talalakram7 👍👍👍👍
Brother Batteries b install karay sath aap. Beshak zada heavy na lagwai bus 48V poray karday. Is taraha aapka system off nhai hoga. Load Shedding mai backup b mil jai ga.
G insha'Allah, abi plan mein hein install krren gy
@@CityHappyFamily G behtar hai.
@@Zain24587 👍👍👍
any loose connection will heat up and eventually catch fire.
tight all screws in breaker usually these are loose.
these wires are fine upto 60 deg
Ok, brother thanks
Keep calm and stay strong 💪.
Jazak Allah Khair ❤️❤️❤️
Yai positive mai he show hota hai agar import hogi tab be positive agar export hogi tab be positive,low voltage 180 per set karain aor high 270 ya 80 per
Ok, brother
I agree with you....mentality of labor is very cheap its true....they don't care...
❤️❤️❤️❤️
6mm cable of good quality in ac like pakistan cables or universal or fast is more than enogh for ac output. 4 pole dc breaker of himel 1000v should be used . 4 pole himel dc breaker 16 amps 1000volts easily available on website power house express. In market ususlly copy is available of renowned breaker like hager or scheider...so better to use himel or chint...himel breaker are availble under flagship of clipsal pakistan . For dc 4mm or 6mm cable tinned coated and xlpo insulated to be used which is better since xlpo cables are fire resistant and uv reaiatant. Dc tin coated xlpo of universal ,fast and pakistan cablea are best.
Ok, thank you
Very well explained, Jazak Allah ❤️❤️❤️
Mere installer ny b mujy ac breaker 25 amp or dc breaker 20 amp py forcefully insist kiya hai baqi koi b installer or shopkeepers is pay mutafiq nai thay
😭😭😭😭😭
Is ma SPDs to hn nhi jo ap btaaa rhy
Ac k leyai 7/52 jes nai be kaha hai belkul ghalat kaha hai,7/52 DC k leyai teek hota hai but single input and output walai inverters k leyai,aapka inverter dual input and output wala hai esmai load ek wire per nahi hota,
G buhat shukria Arshad Bhai, jazak Allah ❤️❤️❤️❤️
cable ki hmesha current capacity dekho 7/46 ki current carrying capability km hoti ha
👍👍👍👍👍👍
Bhai ye negative nai dikhaty Q k CT only flow check krti hy usko nahi pata ye import hy ya export.
Acha acha sehe hy ,
Jo wire aap nai lagwayi hai enough hai, VPD aapko wahi voltage and amps dekayaiga jo aap import ya export karogai,agar zyada export karogai tho zyada voltage and amp dekayaiga agar kam karogai tho kam dekayaiga,wo main DB wala sirf jo wapda sai aaraha hai wahi dekayaiga,aapko yai main DB wala nahi lagana chaheyai ta..
Thank you so much brother ❤️❤️❤️❤️
Allah Pak Apko or apki family ko apnay hifzo eman may rakhay Ameen
@@jaaybee4728 aameen
@@jaaybee4728 jazak Allah
Bhai aapane solar ki installation Kisi galat installer se karvaya hai install
G ho skta hy aisa he ho
انورٹر تو ماشاءاللہ اچھا ہے بہت۔۔۔
Ma sha Allah ❤️❤️❤️❤️❤️
Am a local installer in Mian channu jo bhai kehty hn k company zeada acha kaam kr rhi hn wo cmpny k kaam se hmara compare kr lyn
Aap kahan pr hoty hein??
GM pakistan cable
6mm ya 7/44 1 he bat hai
ap 7/44 he lagi rehne den its more than enough for your system
center waly jo tomzn changeover hai apka wo copy han
Dc Breakers of solar system apko change krna he honge 125A nahi thek
UA breakers bhi wrong choice hai apki
Ok, brother. Thank you
Bro Tomzn original tu milte he nhe hein. Issliyie abi France walay Hager hy original lgae hein
Green meter invertor tabahi hai both for invertor and safety, invertor is used on full capacity in green meter
G wu tu hy, lakin aik chese bni hi usky liyie hy usko chalna chaye
Mein ny simple china hybrid invertor lagwaya, koi masla nahi araha, jis ny bhi green meter lagwaya hai, they are at high risk
@@aspire9496 abb tu muje b yehe lgna shuru ho gya hy jbsy green meter lgaya hy kutch na kutch jal he rha hy
Changeover switch manual wo dial wala mora ka he lagwatai tho acha ta yai breaker walai reliable nahi hotai..
G brother ❤️❤️❤️
Assalam Walekum bhai is setup ko Earth Boring for the solar system kar do👍
G thek hy bro
Aap Ka inverter hybrid ha ya grid tie inverter
Ongrid hybrid
ALLAH Pak asaniyan ata farmaye…ameen
Aameen
Dear Brother,
After reviewing your entire setup, particularly the protection devices, I have a few observations for you to consider. It appears that the SPD (Surge Protection Device), which ideally contains Metal Oxide Varistors (MOVs), is missing from your distribution boxes. These are ceramic-based components that adjust their resistance based on the voltage applied to them. As the voltage increases, their resistance decreases. Typically, these devices have a small window or indicator that is green, showing that the device is functional. They are directly connected to your AC/DC ground earthing. I didn’t notice these in any part of your setup, either next to your nitrox inverter or in the main house DB box, which recently burnt out and was replaced.
Please take this matter seriously for the safety of your home and solar system by ensuring that both AC and DC SPDs are installed.What I observed in all your DB boxes are breakers and changeovers, but not SPDs. This could likely have been the reason for your recent electrical fire. A heavy surge from the grid can only be managed by an AC SPD, while a surge from the solar system requires a DC SPD.
Furthermore, if you install AC and DC fuses together with the SPDs, it would offer comprehensive protection for your system and home appliances.Your voltage and current protection device (MORA) is adequate for additional protection. However, I strongly recommend installing both AC and DC SPDs with individual ground earthing, along with AC and DC fuses.
I have extensive experience and practical knowledge of solar systems and have assisted people in installing systems not only in Pakistan but also in the Middle East and Australia. Unfortunately, many new or low-cost installers in Pakistan tend to neglect these additional protective measures, but they are critically important.
Lastly, 6mm AC is capable of handling a full household load up to 9kw ideally. To give you an idea, note the followings. For a 6mm² copper wire, assuming it handles up to 40 amps and considering a typical 230V AC supply:Power (Watts) = Voltage (Volts) × Current (Amps)Power = 230V × 40A = 9,200 watts (or 9.2 kW).This means a 6mm² copper wire can safely handle an electrical load of up to 9.2 kW under ideal conditions.
Thank you so much Fahad bhai for giving detailed reply on my system.
What what I want to explain you my installer now told me that these Haeger breakers have already inbuilt SPD so separate spds are not recommended so that's why I have not installed otherwise I might have installed SPD separately but he told me thatthese Haeger breakers have already inbuilt SPD. Vikas these breakers costered me three times of a normal Tomszn breakers so I trusted on the new installer but I don't know exactly of that. If you have a proper knowledge that these Haeger breakers do not have any SPD in built please do let me know. Thanks in advance.
@CityHappyFamily bhai, your Haeger breakers are simply a breaker... SPDs have a difficult look.. they have a small cartridge type look that has a small hole showing green colour (if they are functional). Secondly, if your installer is so-called saying that these breakers have built SPDs, so have you noticed any Earth wire output from the breaker that is connected to your AC Ground earthing? Have you done AC and DC Earth Boring in the ground while installing the system? Usually, SPDs are connected to those Earth Boring, which should be one AC bore and 2 Bore for DC Current , in ideal solar setup. Lastly, according to my knowledge, Haeger breaker doesn't come brand new in Pakistan but often brought used in Lots. So their integrity and efficiency are questionable being used item. Your installer has lied to you for sure about Haeger breaker with inbuilt SPD. Please Google SPD Devices to identify the look of it for comparison. They never have a breaker function. If your haeger breaker has Earth wiring output, which is connected to ground AC Earth bore, then you may call it SPD. But again, it should have a cartridge which burns during high surge...
@@fahadsaudia Fahad bhai I know SDP I have seen SPD. Ok I got your point thank you
@@fahadsaudia regarding this brand new or used what I found these breakers are original and new one from France
I have been seeing your vlogs since you installed Nitrox based Solar System, Dukh hota hai itna kharch karny k bad 2 taky, dishonest technical, shopkeeprs kee waja sy apko itna kuch face karna para.. really nuksan apka huwa but i can feel this, Alhamdulillah mai ne apne gar p lgwaya 3kw Nitrox based, sab kuch khud samja, lya, or lagaya b Alhamdulillah Mashallah Acha chal raha hai
Ma sha Allah, basa kia kr skty hein
@@CityHappyFamily exactly unky lye Allah kafi hai.. Ap toh kher mujsy senior or bary hai I'm 26year old but mai ne complete ek month dekha samja or next month k starting m solar panels, or complete saman even ek ek nut bold k wiser khud lye or lagaya b khud along with my engr mamu with the help of knowledge and skills i gathered watching solar installation yt videos.
@@MujeebAhmed_110 ❤️❤️❤️❤️❤️❤️❤️❤️❤️❤️👍👍👍👍👍👍
@@CityHappyFamily 😇🥰 baki I'll upload a video on my channel ap dekhna kese lagaya hai and last but not least apne jo fan use kya hai wo b theek lekin 12v wala fan use krwn nitrox p phr result dekhen.. mera toh din k time heavy load pr b heat nh hota
@@MujeebAhmed_110 👍👍👍👍
بھائی آپ کا مسئلہ کیا ہوا تھا۔۔آپ کی ویڈیو دیکھی۔۔لیکن اس میں پتہ ہی نہیں چلا۔۔کہ آپ کا مسئلہ ہوا کیا؟
بھائی جان اپ کل والی ویڈیو دیکھیں میری اس میں سارا بتایا ہوا ہے میں نے کیا مسئلہ ہوا تھا۔
BHAI SYSTEM ALAG SAY INSTALL KARO . ALAG JAGAH RAKHO
G, ok
Good video
Thanks, ducky Bhai 😄😄😄
ALLAH PAK NAY APP KEE FAMILY HO MAHFOOS RAKHA AMEEN
BAKI MALI NUKSHAN TO PHE PURA HO JAYE GA>
G bilkul aisa he hy ❤️❤️❤️❤️
Har koi preshan hai jugarri solar installers se koi proper kam nhi janta na hi inhe pta hota kam ka
🤣🤣🤣😂😂😂
اصل میں آج کل ہر کسی نے سولر کا بزنس سٹارٹ کیا ہوا چاہے وہ پلمبر ہو الیکٹریشن ہو انجینیئر ہو اس نے اپنا سیٹ اپ شروع کیا ہوا ہے اپ کو ایک پراپر کمپنی سے سولر سسٹم لگوانا تھا تاکہ وقت کے ساتھ وہ اپ کو مینٹیننس بھی دے سکیں یہ میں آپ کو اس لیے بتا رہا ہوں کہ میں خود بھی ایک سولر کمپنی میں کام کرتا ہوں اور ہم لوگوں کو ایک سال کی مینٹیننس بھی دیتے ہیں
سر اپ کی بات ٹھیک ہے میں نے لاہور کی ایک کمپنی سے کیا تھا لیکن وہ لاہور کی کمپنی کو یہاں پہ جو ہے نا ان کے پانچ سے چھ بندوں کو رکھ کے ان کی اکموٹیشن دینا ہے کھانا دینا یہ سب کچھ ڈفیکلٹ تھا کیونکہ یہاں ہمارے لوکل چھوٹے شہر کے اندر کمپنیاں نہیں ایسی کام کرنے والی لاہور میں یہ ملتان سے بلانا پڑتا اور ان کو یہاں پہ فوڈیشن دو تین دن کی رہائش دینا یہ کافی ڈفیکلٹ ٹاسک تھا اور پھر کوئی مسئلہ مسائل اور لاہور سے یہاں انے کے وہ چارجر سیپریٹ پے کرتے ہیں اس کے لیے میں نے لوکل جو ہے نا بندے سے کام کروایا ہے ورنہ مجھے ائیڈیا تھا میں نے لاہور سے ملتان سے کوٹیشنز وغیرہ لی تھی اس کی۔
@@CityHappyFamily لاھو یا ملتان والے انجینئر والی تکلیف اٹھا لیتے تو آج کا خرچہ بچ جاتا
اب بھی وقت ھے اچھے انجینئر کو دیکھا دے
@@naeemzong8159 shayed
@@naeemzong8159 ok, G zaror
Bhai Allah aap ko Khush rakhe...
Aameen ❤️❤️❤️❤️
جناب کیبل سائز مسلہ نہیں کیونکہ تھری فیز میں کرنٹ ھر فیز پر ڈسٹربیوٹ ھو جاتا ھے ۔
آپ یہ دیکھیے کی چینچ اور کتنے ایمپئر کا تھا اور سب سے اھم بات یہ ھے کہ کیا آپ نے ھر کنکشن ٹرمینل پر تھمبل پراپر پنچنگ ٹول سے لگوائے ھوئے ھیں یا نہیں اگر نہیں تو یہ حادثہ دوبارہ بھی ھو سکتاھے۔ برائے مہربانی اوور سائز کیبل سے اجتناب کیجئے۔
بھائی جان تھمبل تو لگاتے نہیں ہیں ان کو سب سے زیادہ مسئلہ تو یہی لگتا ہے کہ تھمبل لگائیں اگر ہر کنیکشن پہ تو مسئلہ ہی نہ ائے سارے بریکرز ویسے ہی تاریں وہ ٹیڑھی میڈی کر کے لگا دیتے ہیں
Allah aap key hifazat karee.
Aameen
ایکسپرٹ ہر پیرا میٹر کی سیٹنگ کرے گا خصوصیت کے ساتھ وولٹیج پروٹیکشن ریلےمیں ایمپیئر کی سیٹنگ
👍👍👍❤️❤️❤️
Sorry kal message nai kr saka, Allah pak apko nazer e badd se bachayen
Aameen, jazak Allah Khair brother ❤️❤️❤️❤️❤️
Newage ki wiring kraen
Wu kia hy cables??
انشااللہ اللّه سب ٹھیک کر دیگا
insha'Allah, thanks brother ❤️❤️❤️❤️
cable 10 mm pakistan cables dalee
Ok brother
جب بھی کوئی بھی بریکر لگائیں۔۔
سولر والا بریکر سولر کے کرنٹ کے حساب سے لگے گا۔۔
اور بیٹری والا بیٹری کے حساب سے۔
گریڈ والا گریڈ کے لوڈ کے حساب سے۔۔۔
👍👍👍👍
7/64 cable best
👍👍👍👍👍🤔🤔🤔
Let your wife complete her words, don't cut her off in the middle.
Ok brother.
اللہ کریم بد دیانت دکانداروں اور کاریگروں سے پناہ دے
Aameen
Allah ka karam ho gaya sir bs jis ka pasay lagtay usi ko pata hota logoon ka kya jata logoon ko tu adat ha batay karnay ki
G aisa he hy , thank you so much for showing your care towards us. Allah pak bless you.❤️❤️❤️❤️❤️❤️
bahi main to Labours ki chori our idiocies se tang a kr, Maximum ghr main kam khudi kr leta. Jasy following.
All electrical repairs or installations
plumbing repairs.
to some extent mistary work
mechanic
etc
and results are 100 % better
Aapki baat sy 1000% agree hon bhai
Total Loss --
NON technical Work Solar side
😭😭😭😭😭😭😭😭
Solar lagta hn bhia ki niche hn 😅
Nhe bhai, mera channel family vlog ka hy
😂😂😂😂😂
@@CityHappyFamily You just uploaded a new vlog on Solar again. What a coincidence 😂😅
@@md.tahayousufzai 😂😂😂😂😂
Bahi koi jan bhch kr kam karb nhi kerta or sub mazdor ya electrician ek jaise nhi hoty. Ap sub ko nhi bolly sub laber ek jaise hu. Log lakho ka saman ly lyty ha per laber dyty hovy jan jatti ha. Main khud electrician hu.
Bhai jaan sb ko nhe bola lakin majority aisay he hein
Aapane Kisi proper installer solar se install karvaya hota to yah system aapka naam jalta
Yehe tu sir meine btaya hy ky "proper"kaisay dhonde. Hr banda he proper kehta apny aap ko lakin kaam krwa kr pata chalta hy hy hath ho gya.
Sorry for your loss. You've taken good measures to replace wiring and breakers which is a big safety hazard otherwise. Good job!
If possible kindly share the name of the shop and contact from where you purchased the breakers etc. Stay blessed!
Sir it is best shop in our city with fix prices for all electrical items
Bhai jaan GM cable is normal cable best cable in Pakistan is PAKISTAN cable.
Humaray city mein available nhe thi bro, wrna Fast cable ya pakistan cable he dlawata . Lakin yahan tu locally gharon mein bni huwe cables he milti hein
@@CityHappyFamily my personal experience Pakistan cable say achi koi bhi nahi pure new copper use hota hey is may baki cables may reprocesssd copper hota hey.
@@raobilalahmed872 G suna tu yehe hy baqi Allah malik. Lakin sir GM local made cables sybkafi behtr hy. Pakistan cables ka alternative shayed na ho lakin achi hy . Meine already ju nikle hein cables ussy kafi behtr hy GM
@@CityHappyFamily may nay apna ghar banaya tha to kafi research ki thi cables per Pakistan cable wallun say meeting ki ku k koi shop wala bhi Pakistan cable sale kernay pay khush nahi tha waja Kam profit aur Pakistan may jitni bhi copper import hoti hey uska major part Pakistan cable walay import kertay hain baki used copper ko reprocess kerkay use kertay hain
Aap nay ku k her cheaz best lagaie howi hey isi liye apko may detail say bata raha houn main cheaz cable hey in sub ki safety k liye Naraz mat hoiye ga.
JAZAK ALLAH KHARE.
7/44 Pakistan cable istamal Karen baki main ne pichli video main comment kiya he.
Main ip65 or ip21 install kar raha hon govt building main.
Aap kahan rehty hain mughey nahi pta aghar mughy pta ho to main aap ka free kaam kar k don ap yad Karen ge aap bohat achey hain aap ko acha elect nahi milta.
Bro mein Mian Channu mein rehta hon
ap. ko phaly bhi kha tha. changeover sirf old style wala kamyaab hai. or safe bhi. ap. nay phir say galti ki... khair ap ki apni marzi hai....
Aapki baat late punchi thi bro uswaqat lgg chuka tha
@@CityHappyFamily xhalin ap dhek lain. comment mi itna samja nai sakta ap ko. ec thra kay changeover 6/7amp taq thek hain.jab ap ka load 5/6 kw chaly ga to changeover ki power say double bji cross kar jay ga. orjab ap ghar na ho inverter 7/8kw export kary ga to.. wo sab ec say ho kay jay ga.. jo almost 20amps say oper hai. ap samaj sakty hain kay kianhota haai. ec naat ko confrim karny kay ley 1 bar apnay kharab changover ko khol kar zara check karin... ap khod kahin gay kay ye kia baywaqoofi ki thi main nay
@@ATIFELECTRONIC-np5uf wu wala changeover 63 amp ka tha bro yay 200 plus ka hy, phir be isko observe krein gy
6کلو واٹ کا ان ورٹر ہے اور بریکر 63ایمپیئر کے لگے ہوے ہیں انسٹالر کو 21توپوں کی سلامی۔
😄😄😄😄😄😄