Differential Protection of Power Transformer Webinar

แชร์
ฝัง
  • เผยแพร่เมื่อ 4 ม.ค. 2025

ความคิดเห็น • 3

  • @ImranKhan-nu6xw
    @ImranKhan-nu6xw 2 ปีที่แล้ว

    Thanks for sharing such a informative vedio

  • @rjshtk
    @rjshtk ปีที่แล้ว

    At 30:20, are you sure that you need to have an interposing CT of YNd5??? I think it is wrong. If the Differential relay is inserted at the position shown as in the diagram, you need an ICT of YNd1 and not YNd5 to cancel out the phase shift of +30 degrees introduced on the secondary winding of the transformer.!! Correct me if I am wrong please!!

  • @3c_miftahulhakim40
    @3c_miftahulhakim40 ปีที่แล้ว

    excuse sir, can i get manual book from this presentation? thanks