    How can we factory reset the permanently coded devices. To erase the actuator data

    • @SICKSensors
      @SICKSensors  2 หลายเดือนก่อน

      Hello and thank you for your question. It’s not possible to erase the actuator data. If high coding is required, but not only one-time teaching, we’d recommend to use the uniquely coded versions. Unlike the permanently coded devices, they allow re-teaching the actuator up to 8 times (e.g. if the actuator got lost or broken). The permanently coded devices allow only one-time teaching, if the actuator is lost, the sensor has to be replaced as well, no reset is possible.