LG MultiV 5 / Recommissioning an LG VRF System

แชร์
ฝัง
  • เผยแพร่เมื่อ 5 ม.ค. 2025

ความคิดเห็น • 32

  • @Rodj12341
    @Rodj12341 ปีที่แล้ว +3

    There is a better way of judging the full load operation of the unit. What you need to do is to turn on Dip switch #5 at the ODU, go to "Fdd" mode using the arrow/confirm buttons, and go to "Fd8" for full cooling(or Fd9 for full heating), and then push the confirm button. After a few minutes after it initializes, it should display 6000(countdown from 60 minutes). Also, LG has specific functions in the ODU to measure the charge to let you know how much to add/remove(Fd1-4).

    • @hvacraustralia
      @hvacraustralia  ปีที่แล้ว +1

      Thanks for that mate, great info to know! I had a flick through the service manual the day after and found the section that explains what all the functions do and how to get there haha great timing on my behalf 😂 I’ll know for next time.

  • @rez131
    @rez131 5 หลายเดือนก่อน +1

    Great job, keep up the good work 👍

  • @bradenramsell5848
    @bradenramsell5848 ปีที่แล้ว

    Nice! What do you do refer to work on in terms of ease of work between Mitsubishi, Daikin or LG?

    • @hvacraustralia
      @hvacraustralia  ปีที่แล้ว +1

      They all have their pros and cons. In terms of general work and getting information from the displays on the outdoor, I prefer Daikin. Their 7 segment display is very easy to use. For display and usability on the service tool, Mitsubishi for sure. The layout and information it gives you is the best for me by far. This was my first time working on an LG and it seemed nice. Once I had my heard around what I needed to do it was pretty easy. Shame about the poor access to the service valves. Can’t win them all 😂

  • @DanielYankey-i7m
    @DanielYankey-i7m 4 หลายเดือนก่อน +1

    Please how is the v5 test run done

    • @hvacraustralia
      @hvacraustralia  4 หลายเดือนก่อน +1

      Using the push buttons located on the control PCB use the arrow buttons to find “Fdd” then click the circle button to enter that mode. Use the arrow to find either “Fd8” for cooling or “Fd9” for heating. Make sure to hold the button down for 1 seconds d before releasing.

    • @DanielYankey-i7m
      @DanielYankey-i7m 4 หลายเดือนก่อน +1

      @@hvacraustralia good job sir thanks so much

  • @jonnyxcz125
    @jonnyxcz125 10 หลายเดือนก่อน

    The thing you did with the nitrogen when pulling the vac what does that actually do and help with.

    • @hvacraustralia
      @hvacraustralia  10 หลายเดือนก่อน +1

      The idea is to dislodge any tapped moisture in the system by raising the pressure/temperature. I usually do it when my micro reading stalls out.

  • @maheradous9257
    @maheradous9257 7 หลายเดือนก่อน +1

    Good job 👍

  • @Louisyongcool2328
    @Louisyongcool2328 ปีที่แล้ว

    Hi mate, I got a site that the brunch box low,high and liquid pipe all crap reduce pipe size do this reduces the cooling capacity? I think some cowboy doing this. Thanks mate

    • @hvacraustralia
      @hvacraustralia  ปีที่แล้ว +1

      Hey mate. Yeah, absolutely. Due to less volume being present there will be less refrigerant at the indoors, resulting in less capacity.

    • @Louisyongcool2328
      @Louisyongcool2328 ปีที่แล้ว

      @@hvacraustralia thanks what would you do if in this situation? Check gas pressure and add some more gas to increase the cooling ?

    • @hvacraustralia
      @hvacraustralia  ปีที่แล้ว +1

      Adding more refrigerant won’t solve the problem. That’s a tough one, is it a recent install? If so the installer would need to come back and install the correct pipe sizes. If it’s older, could always suggest installing the new pipe sizes.

    • @Louisyongcool2328
      @Louisyongcool2328 ปีที่แล้ว

      @@hvacraustralia is a school it been install around 2 year I think school only have 1 year warranty, that a tough one and I don't do LG much, so properly need to reconnect to right pipe size and recover all gas out and check if any leak. If I add some gas it won't do any cooling right? Thanka

  • @bradroesler7072
    @bradroesler7072 ปีที่แล้ว

    Seeing you're a refrigeration technician, do you work on exhaust or ventilation systems? I know this has nothing to do with this video.

    • @hvacraustralia
      @hvacraustralia  ปีที่แล้ว

      We do look after the exhaust fans, fresh air fans etc on most of our sites. They’re usually just a single or three phase direct drive motor so nothing fancy.

    • @bradroesler7072
      @bradroesler7072 ปีที่แล้ว +1

      Can you please make some videos on maintaining exhaust fans, especially bathroom/toilet ones?

  • @J_D_Begins
    @J_D_Begins ปีที่แล้ว

    How long did vacc take mate?

    • @hvacraustralia
      @hvacraustralia  ปีที่แล้ว +1

      I think it was vacc for around 4h. It was really dragging with the 1/4 straws I was trying to pull through 😂

  • @NiiosaMensah-jo1ol
    @NiiosaMensah-jo1ol 8 หลายเดือนก่อน

    Good job

  • @HVACR_VINYLS
    @HVACR_VINYLS ปีที่แล้ว

    My tool arived, now waiting for that rainy day i get an lg problem

    • @hvacraustralia
      @hvacraustralia  ปีที่แล้ว +1

      It’s a tool that might get used every 1-2 years 😂 I don’t see many MultiV, but when we do we’re ready!

    • @HVACR_VINYLS
      @HVACR_VINYLS ปีที่แล้ว

      @@hvacraustralia 100% broski

  • @HVACR_VINYLS
    @HVACR_VINYLS ปีที่แล้ว

    👑

  • @carlosrobertolainez8594
    @carlosrobertolainez8594 หลายเดือนก่อน

    manual says 24 hours microns test buddy

    • @hvacraustralia
      @hvacraustralia  หลายเดือนก่อน

      Mitsubishi Electric’s manual says 1h for their YNW HR units. In the end, I do what I can with what time I’m given.