  • @PatrickJeon-os5vg
    @PatrickJeon-os5vg 11 หลายเดือนก่อน +11

    This was an exact replacement for the old one that lasted about 10 years. th-cam.com/users/postUgkx7yWIKcrbA9KMHkGSfcgxW2lsjHT6B8Sh The top of my mitigation tube by my roofline was just a 90 elbow which allowed too much debris to fall down into the fan, eventually ruining it. Without this issue, I bet it would have kept running another 10 years. When I replaced this fan, I added an extra elbow joint so the top tube now it does a 180, which should solve that problem. The radon guys around here wanted to charge me a $300 diagnostic fee, then parts/labor (probably close to $600 total). I installed this all by myself in about an hour for the cost of the fan; it would probably be even easier/faster with two people. FYI the manufacturer's warranty greatly differs depending on whether you install it yourself (1 yr warranty) or have a licensed installer do it (10 yrs).

  • @tommytmt
    @tommytmt 3 ปีที่แล้ว +11

    Good install! But just a warning to you or anyone else looking to embark on this journey of installing a tankless water heater yourself; if you’re not a professional plumber you will get ZERO warranty support from the manufacturer. I installed my Navien myself in 2019 and it’s been perfect, but just keep that in mind.

    • @kevinvarma5603
      @kevinvarma5603 3 ปีที่แล้ว

      What were those products called he applied? My navien went bad n I'm getting a replacement today

    • @tommytmt
      @tommytmt 3 ปีที่แล้ว

      @@kevinvarma5603 Just soapy water.

    • @ko6128
      @ko6128 ปีที่แล้ว +2

      I saw that same info on Navien but my local plumbing supply place said it’s not true that they provide parts for warranty repair on Navien tankless and no proof that the install was by a licensed plumber is required.

  • @fortmcmurtry
    @fortmcmurtry ปีที่แล้ว +5

    The manufacturer recommends you do a combustion analysis on these units followed by an adjustment of the gas valve or different orifice used if needed. This is one of the advantages of having a professional install

    • @ko6128
      @ko6128 ปีที่แล้ว +1

      Where do you see that info? I don’t see it in the NPN-180U installation manual/user guide.

    • @failingdisciple938
      @failingdisciple938 ปีที่แล้ว +1

      A disadvantage of a professional install would be the cost.

    • @jimimcintosh7796
      @jimimcintosh7796 14 วันที่ผ่านมา

      What are you babbling about. This unit is completely automated and adjusts every parameter instantly.
      As long as you have sufficient gas service and water pressure you walk away

  • @RawDawg760
    @RawDawg760 10 หลายเดือนก่อน +3

    I’m learning how to install, just wondering if a check valve go before the expansion tank?

  • @technicalfacilities5295
    @technicalfacilities5295 7 หลายเดือนก่อน

    might it have been easier to install the valve set , while off the wall, up side down ?

  • @JP-ce8ix
    @JP-ce8ix 2 ปีที่แล้ว +1

    How's it holding up?

  • @poconnor2000
    @poconnor2000 11 หลายเดือนก่อน +1

    The plumber jut installed a Navien gas - does it not require a "metal double wall exhaust flue" as this exhaust is HOT ?? thank you ! nice viedo !

    • @joshuamoore4410
      @joshuamoore4410 10 หลายเดือนก่อน +1

      Not on high efficiency units just like furnaces.

    • @jimimcintosh7796
      @jimimcintosh7796 14 วันที่ผ่านมา

      Exhaust gases are so low because they reuse the heat and expel lower temperatures. Pvc all day long

  • @lancewilson59
    @lancewilson59 2 ปีที่แล้ว +1

    My Navien takes around 40 seconds to ignite, is that what your seeing?
    Thanks Lance

    • @fortunatedad7695
      @fortunatedad7695 ปีที่แล้ว +1

      Sounds like you may have a low water pressure making it tough for the unit to detect flow to start up the unit 🤔

    • @bmack2938
      @bmack2938 ปีที่แล้ว

      @@fortunatedad7695 does it require 80 PSI?

  • @brianarant5932
    @brianarant5932 9 หลายเดือนก่อน

    He shouldn't be using dwv PVC fittings. Only PVC Sch 40 to match the pipe. Many of the dwv PVC fittings are made of a thinner PVC. Navien mentions this in their install manual.

  • @fishchess
    @fishchess ปีที่แล้ว +1

    Is there a maintenance schedule for the condensate neutralizer? Does it need to be changed periodically?

    • @fortunatedad7695
      @fortunatedad7695 ปีที่แล้ว

      It's recommended to replace the crystals yearly

    • @jackc8120
      @jackc8120 ปีที่แล้ว +2

      ​@@fortunatedad7695 what crystals?

    • @billbright1755
      @billbright1755 4 หลายเดือนก่อน

      Manufacturing locations in Southern Korea .

  • @jboi1323
    @jboi1323 ปีที่แล้ว

    Should have put all fittings on before hanging on wall.

  • @idealplumbingservice7943
    @idealplumbingservice7943 3 หลายเดือนก่อน

    You have absolutely got to use pvc solidcore pipe! You cannot use regular pvc dwv piping!!!!! It’s a condensating tankless unit and that vent pipe is not rated for a Navien!! Read your manual!!!

  • @wera1971
    @wera1971 2 ปีที่แล้ว +2

    The video is very good. One question. I see more Videos of these because some use an expansion tank and others don't.

    • @g00fyscientist
      @g00fyscientist 2 ปีที่แล้ว +1

      They probably should if they are running a recirc line. The IPC does not require one, but even then most new tankless units have a buffer tank and that creates high system pressure so it never hurts to install an expansion tank.

    • @grahamludlow7001
      @grahamludlow7001 ปีที่แล้ว

      IPC/ upc requires expansion tank if a PRV is installed on the water delivery line... also with simple knowledge of the plumbing system any pro would put on in.

  • @caymaneller5648
    @caymaneller5648 3 ปีที่แล้ว

    I'm installing a navien at my house. My hot and cold fittings were loose, just this the in the video @5:58, is that normal?

    • @JMald62
      @JMald62 3 ปีที่แล้ว

      Yes

  • @charlesjohnson7222
    @charlesjohnson7222 2 ปีที่แล้ว +2

    What was the clear cylinder with all the pebbles in it?

    • @ringodingo
      @ringodingo 2 ปีที่แล้ว +4

      I believe it neutralizes the condensate fluid's acidity.

    • @brandonTHEshiados
      @brandonTHEshiados ปีที่แล้ว

      @@ringodingo yes it's a condensate neutralizer

  • @wastedtimeagain3816
    @wastedtimeagain3816 ปีที่แล้ว

    No flares?

  • @evaristoveracruz9001
    @evaristoveracruz9001 2 ปีที่แล้ว +3

    I just can’t believe that people still use sea PVC pipe. Worst thing that was ever invented.

    • @sykedem_yt6254
      @sykedem_yt6254 2 ปีที่แล้ว

      Its so common in here in FL. I hate it...

    • @mickeyromero9233
      @mickeyromero9233 2 ปีที่แล้ว +1

      What are your issues with it?
      C-pvc*

    • @jackc8120
      @jackc8120 ปีที่แล้ว +1

      ​@@mickeyromero9233 there are no issues, pvc is the only option

  • @nsbconstruction9698
    @nsbconstruction9698 2 ปีที่แล้ว +2

    That condensate filter is plumbed all wrong.

  • @robertsplawn4200
    @robertsplawn4200 2 ปีที่แล้ว

    What was the extra tank for and I didn’t understand the hookup of the filter?

    • @sykedem_yt6254
      @sykedem_yt6254 2 ปีที่แล้ว

      That extra tank is a safety measure for units that are hooked up to a "city water" connection. Sometimes the water company turns their pumps on and off for whatever reason, and the initial start of their pumps going may cause a very high pressure flow that can possibly damage residential plumbing. So that tank is installed to take the load of that pressure if an event like that were to ever occur.

  • @gregvitkow521
    @gregvitkow521 9 หลายเดือนก่อน

    Where is this and who uses cpvc anymore? Well water? Use a tank. You'd have to flush that thing every 3 months with a filter having well water.

  • @Shadi2
    @Shadi2 2 ปีที่แล้ว +2

    This is a video on how to fail inspection.

    • @OMassenat
      @OMassenat 2 ปีที่แล้ว +1

      Idk I’m assuming you not getting it inspected since you doing it yourself?

  • @BKMDano17
    @BKMDano17 3 ปีที่แล้ว +3

    Sprinkler pipe? 40 plus years in the biz and I have never seen that. Use copper or hire a real plumber that does.

    • @go-diy
      @go-diy  3 ปีที่แล้ว

      😂😂😂!

    • @jasonsmith6408
      @jasonsmith6408 2 ปีที่แล้ว

      Cpvc is rated for potable water. Says it right on it. Or are you talking about the black iron? That would be the gas supply.
      CPVC may be acceptable install per code but I will never use it on new work again. Turns brittle after a couple years.

    • @g00fyscientist
      @g00fyscientist 2 ปีที่แล้ว +2

      @@jasonsmith6408 Dan is an old-timer, and that's okay. There's a reason copper is being installed in homes less and less everyday. Just ignore him. CPVC is actually junk and it really does go brittle relatively quickly. I personally would have used PEX, much cleaner look, and doubling the benefits of copper and others.

    • @jeffreyplumber1975
      @jeffreyplumber1975 2 ปีที่แล้ว +2

      @@g00fyscientist Nothing looks worse than Pex Cpvc definately looks cleaner but Neither Pex nor CPVC is as good as copper in my book PEX might be better than cpvc though

    • @g00fyscientist
      @g00fyscientist 2 ปีที่แล้ว +5

      @@jeffreyplumber1975 PEX has more beneficial advantages than all other applicable potable water lines. Copper has a nice look to it, but that's about it. A big one being time, since in this trade time is money and although it doesn't take a whole lot of time to sweat the joints, I can still clear a whole house replumb with PEX way faster than you can with copper.

  • @andrewdanjumbo7584
    @andrewdanjumbo7584 11 หลายเดือนก่อน

    Speak…!

  • @edgargee408
    @edgargee408 ปีที่แล้ว +1

    Neutralizer is not set up correctly