Earth pit resistance testing with Kusam Meco KM-2030 tester by FOP method.

แชร์
ฝัง

ความคิดเห็น • 6

  • @30mAkills
    @30mAkills  ปีที่แล้ว

    Caution Note: For energized services first check the earth electrode voltage with connections as shown in video. If its more than 10V don't proceed. (E terminal=dummy, P to Potential spike (Yellow), C to Current spike (Red) and V to earth electrode (Green) under test. Turn rotary knob to Earth Voltage position. Now voltage present will be displayed. No need to press test button. If display shows 10V or more Deenergize the earthing system carefully and then proceed.
    During resistance checking pull out green probe from V terminal and inset it into E terminal. ie leave V terminal dummy.

    • @abdulazeez4930
      @abdulazeez4930 ปีที่แล้ว

      If the anloage meter test ,how to measure earth electrod voltage

    • @30mAkills
      @30mAkills  ปีที่แล้ว

      @@abdulazeez4930 same method.

    • @abdulazeez4930
      @abdulazeez4930 ปีที่แล้ว

      Analoge means hand rotate earth tester sir ,how to measure earth electrod voltage

    • @30mAkills
      @30mAkills  ปีที่แล้ว

      @@abdulazeez4930 it should have that feature.

    • @abdulazeez4930
      @abdulazeez4930 ปีที่แล้ว

      Ok sir