Sir Ji Hatsoff Awesome Video With Depth Knowledge About Refrigerator....God Make U More & More Successful As U Expected More Than That.....sir Ji am a R&AC Faculty Buy am following u......
Sir, Thank you! Bahut acha laga. But aap se ek request hai ki aap full details me vacuum karne ka tarika bata dejiye. It would be a great favour by you.
Sir nice video sir thanks sir Ac N Hvac me bahut help mili smjhne m apke videos se sir ab refrigerator ka v videos late rahe sir ap plz 💖💖 N congrates for silver play button sir😘😘😘
Hi ser main aapka bahut big fan hu Mere ko aapki videos se bahuy kuch sikhne ko milta hai Or ser meri help kardo plese ser mere pressure gauge ki reading kese dekhte hai mere ko pata ni ser plese app 1 video bnaa do pressure gauge pe ...... megapixel.psi.kese check karte hai reading plese ser I waiting ......by ser
Aap nay sahi kaha sir Manay ek three phase ki machine r22 gass ki charging zyda kar dii thii or compressor pe bahut swating aaa rahi thii compressor bahut zyda awaz kar kar raha tha Zyda karnay ka reezan tha manifoult gaze hamara khrab tha mujhe pata nahi chala
Sir, I found that if the system is overcharged then there is frost on the return line also the filter drier is cool to the touch and the last 2 or 3 tubes of the condenser are also cool.
@@inderjeetsingh7770 Sir, what Professor Girish Shinde is doing for bringing up Indian HVAC unprofessional and professional technicians you have absolutely no idea. In order to appreciate and admire his work, you should have started refrigeration in 1978 like me. What he omitted is negligible to what he GIVES so lovingly to the public.
Hi sir mai meraj mai ye chah ta hu ki aap expention device jo hamare ductable unit ya package unit me lag a. Rahata hai uske kaam operi g rectify ko thoda details se samjhaye
Sir , refrigerator k freezer ka jo pipe compressor ki suction pipe me laga hota h use vha se hta kr compressor ki charging pipe me laga de or compressor k suction pipe me ko refrigerant charge kr de to kya hoga ??
Good night sir. I am Irshad ali Mere pass chiller de frider hai start hote hi sweating aa jata hai to kya problem ho sakta hai comprasser ke terminal tak ice aane lagta hai
Hi ser aapne 1 video bnayi , refrigeration fault finding per ser usme appne btaayia refrigertion gas jiyada charge karne se compreesor. Condenser.evaporater me fault aata hai ser is video me jo aapne advice di vo frize k uper btaayia .... ager chiller me refrigiration jiayda charge hoje toh ser usme bhi j same problem aayegi
1.In a refrigeration cycle the flow of refrigerant is controlled by ___ 2.which parts of the vapour compression refrigeration cycle, produces the refrigeration effect ,_____ 3.the refrigerant is generally in the form of fairly wet vapour at entry to _____. Pls sir answer these questions.
#sawal . Sir main 20 ltr ka water cooler bana raha hu compressor THk 9410 Ycg laga raha hu or condenssor 3 Raw ka lagaya hai 10"/10" or cand fan 1500 Rpm ka lagaya hai or cooling coil 1/4 " ki 38fit dali hai ish main capilary kitne fit dalu or suction pressor kitna rakhu ki cooling acchi mile🙏🙏🙏🙏🙏
hello sir i have seen your all videos is it possible for you to make a video on 3 phase wiring diagram for 3 phase units including main electrical components.......?
Dx is direct expansion system in which refrigerant is directly feed in evaporator in chilled water system, water is cooled by refrigerant in chiller and the chilled water is circulated in cooling coil
Sir discharge line me liquid refrigerant and suction side vapour charge karana raheta usaka please tell you reason either to make to video proper understand me.
Compressor jis refrigerant ke liye bana hai wahi refrigerant charge karna hota hai. Hum 134a ki jagah hydrocarbon use nahi kar sakte. Amp main jada farak nahi padta.
sir System me over charge karate hai to standing pressure up hota hai lekin Jo apana service cylinder hai usame satanding pressure me different kyu nahi ata?
4.5 tr ca rotry compressor hitachi logicool me jiska liquid 300 se 350 ho jata hai suction pipe me chilled hai but trip kar jata hai guage se cheak kiya tha to uski sui thoda hill rahi thi kya ho sakta hai
Gas dischrge kr do or capplry & dryer change krke full vacum krke gas chaging kar do aapki problam soul ho jayegi agar phir bi problam aati h to compressor check kar le
cooling kam kar rha hai baar baar compressor trip hone par thodi gas nikal di thi par pahle sahi chal rha tha gas nikalne ke baad comp.par sweating aai
सर आप बहोत महान हो सर बहोत बढीया
Thanks
Good job excellent video
Thanks
Good teaching sir jay gurudev
Sir maza agya boht deeply samjhaya h aap ne boht zbrdast Sir 👍
Thanks
Jabardast
Very good keep it up
Thanks
Very nice explained
Thanks
Sir Ji Hatsoff
Awesome Video With Depth Knowledge About Refrigerator....God Make U More & More Successful As U Expected More Than That.....sir Ji am a R&AC Faculty Buy am following u......
Thank you very much Sir
Very good sir . keep it up
Sir,
Thank you!
Bahut acha laga. But aap se ek request hai ki aap full details me vacuum karne ka tarika bata dejiye.
It would be a great favour by you.
Sir nice video sir thanks sir Ac N Hvac me bahut help mili smjhne m apke videos se sir ab refrigerator ka v videos late rahe sir ap plz 💖💖
N congrates for silver play button sir😘😘😘
Welcome
thankyou sir ...aage ki video ...pumping down,oilchoking,parcel choking ....k banaye aap
Sir G good one please make a video on Refrigerant construction and types and characteristic
Ok
Hi ser main aapka bahut big fan hu
Mere ko aapki videos se bahuy kuch sikhne ko milta hai
Or ser meri help kardo plese ser mere pressure gauge ki reading kese dekhte hai mere ko pata ni ser plese app 1 video bnaa do pressure gauge pe ...... megapixel.psi.kese check karte hai reading plese ser
I waiting ......by ser
Pressure gauge pe already video hai aap channel pe check kijiye
Very nice video sir
Thanks
Sir ac ke fault finding ke bare main videos banaye plz
Nice video sir thanks....
Welcome
I r my favourite teacher
Pressor switch ke bare me video banaiye with connections
Pressure switch kon sa bellow type or Electronic
Agar posible ho to dono banaiye please
Happy diwali sir mery taraf se sirf aapke liye pecialy
Happy Diwali
TQ for your guidance
Welcome
Too good sir thank u
Welcome
Aap nay sahi kaha sir
Manay ek three phase ki machine r22 gass ki charging zyda kar dii thii or compressor pe bahut swating aaa rahi thii compressor bahut zyda awaz kar kar raha tha
Zyda karnay ka reezan tha manifoult gaze hamara khrab tha mujhe pata nahi chala
Yes
@@girishshinde sir aap ka email id kiya hai
Email id pe aap bata saktay hai
Sir air conditioner se sambandhit koi achhi book btao jisme jayda knowledge bde
sir AC me starting capasiter kese lagaye compresser ke liye uska wiring diagram pe video bnaye plz
Nice video sir thank you
बहुत अच्छा सर जी
Sir Aap ka number v dalye sir
Thanks
Good Explen Sir
Osm explained sir
Thanks
Sir water cooler ka suction pressor kitna rakh sakte hai 165 waat ka compressor THK9410ycg lagaya hai to.🙏🙏
Good sahi ja rahe
Sir deep freezer R134a refrjent sucion pressure kitna rahta hai sir ispar video bnaiye
Sir pls explain abt walking chiller and freezer
SIR ...INVERTER FREEZE ME DEFROSTING. ..PROBLEM & COMPRESSOR. .& CIRKET TESTING. ....PAR VEDEO BANAYE. ...SIR
Ok
Thanks💖💖
Nice video👌👌👌
Nice sir👌👌👌
Domestic air conditioner me capallary hata Kar automatic expansion valve ka use Kar sakate hai?
Sir, I found that if the system is overcharged then there is frost on the return line also the filter drier is cool to the touch and the last 2 or 3 tubes of the condenser are also cool.
Possible
@@inderjeetsingh7770 Sir, what Professor Girish Shinde is doing for bringing up Indian HVAC unprofessional and professional technicians you have absolutely no idea.
In order to appreciate and admire his work, you should have started refrigeration in 1978 like me. What he omitted is negligible to what he GIVES
so lovingly to the public.
Sar a.c. split reparar ke bare m video banaye
Ok
Sir godrej inv refrigeration ka compressor pcb ke jagah me hum ptcr relay use kar sakte hai ki nahi
Nahi
Oh nhi sir
Sir, a.c ka errors ke bara ma videos banayea, plzzzz
Hi sir mai meraj mai ye chah ta hu ki aap expention device jo hamare ductable unit ya package unit me lag a. Rahata hai uske kaam operi g rectify ko thoda details se samjhaye
Ok
Sir , refrigerator k freezer ka jo pipe compressor ki suction pipe me laga hota h use vha se hta kr compressor ki charging pipe me laga de or compressor k suction pipe me ko refrigerant charge kr de to kya hoga ??
P t chart ka use karke raise system me fault finding Ki ya Bata hay ?
Good bless you sir
Sir, can you please make a video on hvac estimation..........
Compressor me jo lubricant numiral oil hota hai wo agar nahi rhe to compressor head pressure bhagta hai kya
Oil nahi hone se compressor karab hota hai discharge pressure pe koi asar nahi hota
@@girishshinde compressor over heat nahi होगी
Good morning sir
Please tell me as a engineering label which topic of hvac is most applicable in execution and Installation
thanku so much sir 👍
Welcome
Sir agar chhilar sidaun ho Jaye to ham pehale kya check kare
sir competition class k nots ki tyaari krvavo na Jese dmrc, isro , railway apni trade ki Kahi class nahi hoti plzz plzz plzz ,🙏🙏🙏🙏🙏🙏🙏🙏🙏🙏🙏🙏🙏🙏🙏🙏🙏🙏
Sir hame btye ki freeze me kitne oms ka sensor lagta he
Sir Automatic Expansion valve and Thermostatic expansion valve working Kya he pleases video uploaded
Thermostaitic Works Only On Temperature Supported By Sensor Which Had (Volatile Or Refrigerant Init)
Sir Mera blue star 110 ton ka chiller h usme low amp. no start ka alarm aata h kya problem Hoga
Great
Thanks
@@girishshinde you are welcome
Good night sir.
I am Irshad ali
Mere pass chiller de frider hai start hote hi sweating aa jata hai to kya problem ho sakta hai comprasser ke terminal tak ice aane lagta hai
सर् क्या पम्पिंग down होगी तो भी यही नतीजे दिख सकते है क्या
sir these parameters are same in chiller plant lp , hp , satnding pressure , section pressure etc
Yes
@@girishshinde thank u sir
PLEASE MAKE VIDEOS ON LIFT AND STAIRCASE PRESSURISATION.
Nice topic
THANK YOU SIR! EAGERLY WAITING FOR NEXT VIDEO.
Hi ser aapne 1 video bnayi , refrigeration fault finding per ser usme appne btaayia refrigertion gas jiyada charge karne se compreesor. Condenser.evaporater me fault aata hai ser is video me jo aapne advice di vo frize k uper btaayia .... ager chiller me refrigiration jiayda charge hoje toh ser usme bhi j same problem aayegi
Chiller main agar liquid receiver hai tho over charging se problem nahi aati agar receiver nahi hai tho same problem ho sakti hai
Hi sir, sir can you please make about Ammonia Refrigeration system
Sukriya sir
Good
1.In a refrigeration cycle the flow of refrigerant is controlled by ___
2.which parts of the vapour compression refrigeration cycle, produces the refrigeration effect ,_____
3.the refrigerant is generally in the form of fairly wet vapour at entry to _____.
Pls sir answer these questions.
Nice sir
Thanks
Thank you sir
Welcome
Thanks,sir...
Verynice
Sir
vvvvv thanks
#sawal .
Sir main 20 ltr ka water cooler bana raha hu compressor THk 9410 Ycg laga raha hu or condenssor 3 Raw ka lagaya hai 10"/10" or cand fan 1500 Rpm ka lagaya hai or cooling coil 1/4 " ki 38fit dali hai ish main capilary kitne fit dalu or suction pressor kitna rakhu ki cooling acchi mile🙏🙏🙏🙏🙏
Exacuter valve kya h or kha lga hota h sir
Sir plate heat exchanger water chiller ke liye milk chiller ke liye batao ji
Sir please upload air cooled chillers
Bhai coldstoreka R22 eska suction pressure kitna he
Cold storage kitne temperature ki liye design hai.
Aur sir refrigeration main modulating se kya hai...??
Sir Discharge pressor kaise cheque karen
Sir, pls make a video on Superheat calculation And subcooling calculation, how can we calculate this.
hello sir i have seen your all videos is it possible for you to make a video on 3 phase wiring diagram for 3 phase units including main electrical components.......?
Yes but it may take time
Sir refrigerator me candensir ka pressure kase check kare
R410 ka discharge pressure & suction pressure Kiya hoga please reply
Suction 117 Psig, Discharge 375 psig
After one hour operation of whirlpool double door refrigerator RCCB is tripping. What may be the reason.
Sir can you explain
What is a different between dx and chiller
Dx is direct expansion system in which refrigerant is directly feed in evaporator in chilled water system, water is cooled by refrigerant in chiller and the chilled water is circulated in cooling coil
Sir 6 psi on Suction side is cut out point of refrigeration cycle?
Normally for R 22 air conditioning system low pressure cut out set on 35 psig
Sir discharge line me liquid refrigerant and suction side vapour charge karana raheta usaka please tell you reason either to make to video proper understand me.
Nice video
Thanks
Welcome
Hydrocarbon charge krne se amp kyu kom hota hay???
Compressor jis refrigerant ke liye bana hai wahi refrigerant charge karna hota hai. Hum 134a ki jagah hydrocarbon use nahi kar sakte. Amp main jada farak nahi padta.
Sir which is best ...over charge or normal
Normal
@@girishshinde thanks sir
Sir 1 question hai .....
R 600a refrigerant main silica based filter kyon nhi use ker sakte .
Plzzzzz sir reply
Sir online HVAC Padna hai aap se kya kare kaise aap se baat hogi
Sir aap ka kahi institute hai
Kaise kaam karta hai usko set kaise karte hai bataye plsplspls
Hello Sir freezer compssor ka all compani model no ka vara ma vata old or new thnku #
sir System me over charge karate hai to standing pressure up hota hai lekin Jo apana service cylinder hai usame satanding pressure me different kyu nahi ata?
How to decide compressor size
4.5 tr ca rotry compressor hitachi logicool me jiska liquid 300 se 350 ho jata hai suction pipe me chilled hai but trip kar jata hai guage se cheak kiya tha to uski sui thoda hill rahi thi kya ho sakta hai
Refrigerant kon sa use ho raha hai, aur 300 se 350 Discharge pressure hai kay? Sath main standing pressure bhi check karo.
@@girishshinde satnding 150
R 22
Bataye pls
Gas dischrge kr do or capplry & dryer change krke full vacum krke gas chaging kar do aapki problam soul ho jayegi agar phir bi problam aati h to compressor check kar le
sir air conditioner ya water chiler me gas kam hone par compressor sweating aati he kya
cooling kam kar rha hai baar baar compressor trip hone par thodi gas nikal di thi
par pahle sahi chal rha tha gas nikalne ke baad comp.par sweating aai
Nahi
Why are not using A in r134a
Sir refrigerant vapour charge krna chya ?????
Liquid charge krna chya??
Vapour low side se aur liquid high side se charge karte hai
Refrigerator r ac ke suction line se vapour charge krna chya????
Hello Sir,
HVAC system mai Discharge Temperature, suction pressure, Discharge Pressure minimum and maximum kitna hona chahiye ??
Please tell me Sir
Us topic pe video bana raha hu
He made HVAC easy
Thanks