100A SWITCH FUSE ISOLATOR INSTALL

แชร์
ฝัง
  • เผยแพร่เมื่อ 15 ธ.ค. 2024

ความคิดเห็น • 133

  • @fire_stick
    @fire_stick 10 หลายเดือนก่อน +1

    DNO fuse is to protect the installation as a whole metering etc, the additional fuse is required to protect the cabling to the CU. Not required if CU is closer.

    • @JasperJanssen
      @JasperJanssen 2 หลายเดือนก่อน

      Wouldn’t a heavy duty MCB be a better component? Fits in a smaller box, doubles up the switch and protection functions, etc.

    • @Bestofthebest383
      @Bestofthebest383 หลายเดือนก่อน

      😅

  • @abdoaiman
    @abdoaiman 2 ปีที่แล้ว +5

    Leaving extra length of the armoured would make the job easier i believe .. Well done sparky 👍

  • @sergiofernandez3725
    @sergiofernandez3725 2 ปีที่แล้ว +6

    Why was it not an 80amp fuse upstream of the 100amp main cutout? Descrimination/ Selectivity and what not

    • @kittsdiy
      @kittsdiy 2 ปีที่แล้ว +3

      +1 .. now it's the strongest fuse who will not pop :p 50/50 chance the DNO one will trip :p

  • @ru8y1987
    @ru8y1987 2 ปีที่แล้ว +22

    Assuming the DNO puts a 100a in... your fuse needs to be max 80a. Selectivity and all that 👍

    • @Emin3m1986
      @Emin3m1986 2 ปีที่แล้ว +8

      No, you don`t... because there is no need for selectivity there.

    • @ru8y1987
      @ru8y1987 2 ปีที่แล้ว +1

      @@Emin3m1986 who says?

    • @Danxr-k4j
      @Danxr-k4j 11 หลายเดือนก่อน +3

      DNO will only fit 80a fuse in cutout. Your 100a fuse pointless. Really needs to be 63a to allow for discrimination between household circuit and DNO supply.

    • @robtmcL12
      @robtmcL12 9 หลายเดือนก่อน +3

      I'm DNO and can confirm we have recently had instruction to fit an 80 amp in the 100 amp cutout. The reason being it will allow 120 amp + for a few hours. The time/current curve for the BS88 will confirm this.
      As for discrimination, you don't need to bother. It's 50/50 which one will fail first and if it's the DNO one that gives up first, they will respond within 2 hours anyway. In some instances ( flats with submains ) we use a red fuse link in the flat as there's already fuse protection in the Distribution board ( eg Bemco/Rapell/Schnieder boards ).

    • @JohnSmith-ws7fq
      @JohnSmith-ws7fq 3 หลายเดือนก่อน +2

      @@robtmcL12 "50/50 which one will fail first" - which sort of begs the question why these second fuses are fitted in the first place? Seems like its just some box ticking exercise.

  • @tomlloyd9372
    @tomlloyd9372 2 ปีที่แล้ว +5

    Nice. FYI, its the meter operator (eon, british gas etc) who will install the meter. DNO own up to the cutout before the meter, so will not install that

  • @JordanSpencer906
    @JordanSpencer906 2 วันที่ผ่านมา

    Great help thankyou so much Ryan youre the best

  • @cvarsani2190
    @cvarsani2190 ปีที่แล้ว +2

    I've done a couple of these, it's easier to curl the wires at both lod and supply side. I always leave length on cables just in case and it looks just as tidy. Not sure why earth nut or banjo wasn installed from source side as less likely to get tampered or disconnected 🤔

    • @sebastiannielsen
      @sebastiannielsen ปีที่แล้ว

      Tampering with Earth or Neutral won't in any way get you free electricity, it will just make the life more dangerous. So putting them on "consumer side" is actually preferred, since then if the consumer or any electrician needs to make a measurement on for example earth or neutral, you usually need to separate these (NOTE: Very dangerous, should be done with isolated supply) and then you can measure, for example, track down cheater earths (cheater earths are when you make a fake earth out of the neutral on a socket - super dangerous!) - this by connecting a beeper transmitter on the now disconnected earth, and then making sure every socket beeps. If a socket doesn't beep, its a sign that the earth in that socket is fake.
      Disconnected neutrals and earths also have other usages, measuring resistance to find out cable lengths and impedance, tracing broken earths and neutrals and lots of other uses, and it would be a pity to have to call DNO or meter company just to do some troubleshooting on earth or neutral.
      So always leave earth and neutral easily accessible on consumer side.

  • @daveenglish2031
    @daveenglish2031 10 หลายเดือนก่อน

    great vid. Ive got to do one this week. what's the general thoughts on running the swa up the cavity?? If i cant get it up the cavity then I'm going to have to chase it into the block behind the dot and dab :/

  • @therealdojj
    @therealdojj 2 ปีที่แล้ว +2

    So is it purely because of the distance then?
    I think a saw another video about the same thing earlier today

  • @henrytwigger2245
    @henrytwigger2245 ปีที่แล้ว +1

    The supply companies use to insist that no consumer apparatus be installed in meter cabinets, has that changed ?

    • @kobirelf97
      @kobirelf97 ปีที่แล้ว

      This is technically not true in this case when a consumer unit is more than 3 m away from the main head there has to be an isolator of some kind

    • @treehouse7861
      @treehouse7861 2 หลายเดือนก่อน

      @@kobirelf97 yes and it is fitted the by the meter company (same time as meter), source= my job

  • @chrischris3551
    @chrischris3551 ปีที่แล้ว +2

    Great job,quick question, what’s the point of using a 100A isolator when the mains got a 100A alright supporting it?

    • @mcoys1029
      @mcoys1029 6 หลายเดือนก่อน +1

      If the tails are longer than 3 metres away from the consumer unit you have to put in a fused mains switch due to regs

  • @ilincaflorentin6639
    @ilincaflorentin6639 15 วันที่ผ่านมา

    Thanks man very helpful i will definitely do the same ❤❤❤

  • @aclarke0100
    @aclarke0100 2 ปีที่แล้ว +1

    What grips did you use please

  • @brunogina3329
    @brunogina3329 8 วันที่ผ่านมา

    How many mm2 of cable is that please

  • @tim4182
    @tim4182 ปีที่แล้ว

    22/58 100a fuse is an European style industrial fuse NOT a domestic 22/57 house service type. Any short circuit fault would blow the DNO fuse and not the one in the switch fuse,I've seen this happen before,these fuses have a much higher watts loss and pre arcing values are higher

  • @abcd-by6rw
    @abcd-by6rw ปีที่แล้ว

    Curious if its recommended putting some kind of terminal on the bare conductor? or if this does not matter, cheers!

    • @abcd-by6rw
      @abcd-by6rw ปีที่แล้ว

      i.e. crimp or other

  • @ascorpio1
    @ascorpio1 ปีที่แล้ว +1

    Why 25mm SWA and not 16mm?

    • @temp06j723-pmeighttq
      @temp06j723-pmeighttq ปีที่แล้ว

      Why not 25mm² ?
      Why not 35mm² ??

    • @ascorpio1
      @ascorpio1 ปีที่แล้ว

      @@temp06j723-pmeighttq Because my understanding is that the cable size and fuse should match the setup. The DNO fuse is 100 amps. The tails are 25mm which support amps of over that size of use or thereabouts. If you then are going to build a distribution network then the DNO then expects you to go lower in cable size and fuse to protect their fuse. A 25mm cable matches the tails which isn’t the correct way to build a distribution network hence the question. I think the distribution network needs to be lower cable and fuse so that if there was an issue on it then it would protect the DNOs fuse and setup but I’m not qualified and learning so if you know the answer I’d be glad to hear it.

    • @temp06j723-pmeighttq
      @temp06j723-pmeighttq ปีที่แล้ว

      DNO's cabling protection is another complex story.
      CutOut is to protect Meter Tails etc.
      When given a 100A service Cut Out, you wouldn't be fitting a 16mm² Tails unless you Downsize the Switch-fused Isolator + fuse to a 80A then it will be fine.
      But then it will be a waste, considering the ability the DNO to Service up to 100A yet we downgrade our PERMANENT Cabling(meter tails) to a lower size that Forever is Binded/capped to 80A in the future (with using of 16mm²).
      Hope it makes sense.

  • @mrutubeuk
    @mrutubeuk 2 ปีที่แล้ว +1

    Did you run the swa through the cavity if so how much of it?

    • @JonNelson90WBN
      @JonNelson90WBN ปีที่แล้ว +1

      Didn’t he say the consumer unit was roughly 12mtr away?

  • @Ibrahim-vt2tz
    @Ibrahim-vt2tz 2 หลายเดือนก่อน

    Nice clean job
    Brilliant ❤❤

  • @corbs07
    @corbs07 2 ปีที่แล้ว +1

    Any reason why you didn’t use a stuffer instead of a swa gland as it’s earth distro end ?

    • @RDavisElectrical
      @RDavisElectrical  2 ปีที่แล้ว +2

      Nah no reason mate

    • @mikethemask1525
      @mikethemask1525 2 ปีที่แล้ว +2

      I've used these once, personally I prefer the metal swa glands feels better even if
      it's just my excuse to get grips out and show off 😂

    • @jameshansing5396
      @jameshansing5396 หลายเดือนก่อน

      Because it would be shit?

  • @lisabarton22
    @lisabarton22 ปีที่แล้ว

    Is it possible for the switch to go off but not blow fuse?

  • @ArtypNk
    @ArtypNk หลายเดือนก่อน

    The city had my service cut out replaced a week ago, and then yesterday it literally caught fire. Was arcing and there were flames and burning and very loud thuds that spat fire into my bedroom, smoke everywhere, fire alarms blaring.... They came in and made a temporary replacement connection to my neighbors power. Now I'm just freaked out about it, what if it does it again, what if it does it while I'm asleep, or worse yet, what if it does it while I'm at work and I come back to a smoldering ruin of a house.
    Went from never thinking about electricity to just being paranoid over it being in my damn house....

    • @Dooguk
      @Dooguk หลายเดือนก่อน

      Why was the first cut out replaced?

    • @ArtypNk
      @ArtypNk หลายเดือนก่อน

      @@Dooguk
      I had one of those "semi yearly inspections" and the electrition, after checking all the fuses and outlets and all the circuit breakers told me that the reading on it is 1.22, when legally it can be 0.80 max, hence the replacement.
      I know now that what happened is, I had one of those old paper insulated wires going into the cutout, and when the electricians were replacing the box they bothered the wire and the old paper insulation enough for it to short and ark and cause that fire. And best thing is, the electricians who finalized the job actually didn't connect the live wire from cutout into meter, they just sort of shoved it in there and it was slowly slipping out every time a car went by outside the house, had to call them again and watched as the new guy touched the wire and it came out of the box with minimal effort. He could not explain to me why they wouldn't secure the live wire properly.

    • @Dooguk
      @Dooguk หลายเดือนก่อน

      @@ArtypNk It sounds to me like they never tightened the screw(s) in the meter. There should have been two guys for the first call, is that correct? They should have replaced the cables with double insulated ones when they fitted the new cutout anyway. I'm sure The guy who put it right would have made sure everything was ok before he left.

    • @ArtypNk
      @ArtypNk หลายเดือนก่อน +1

      @@Dooguk
      There were 2 guys on the first call, and then 2 guys were temporary fixing it with the "wire through the window", plus the 4 guys who dug the ground/cut the wire.
      Then 4 more when they did the proper fix, and out of those four not one decided to tighten the live wire into the meter screw.
      The final guy was just him, but then all he had to do is remove the fuse, screw in the wire, and put the fuse back in.
      Looking back at it, yea, it should have been looked at by the first 2 guys and they should have said "This wire is not safe, needs to be replaced".

    • @Dooguk
      @Dooguk หลายเดือนก่อน

      @@ArtypNk Quite right, the first two should have. I asked if it was two guys because you can't work on live cables on your own for obvious safety reason. The guy on his own who worked on the meter can pull a fuse out to make thing safe. It all sounds like a right comedy of errors though.

  • @JJ-lf4er
    @JJ-lf4er 2 ปีที่แล้ว +1

    Do you not usually use the grey for the earth and black for neutral or doesn’t it matter as long as it’s sleeved?

    • @RDavisElectrical
      @RDavisElectrical  2 ปีที่แล้ว +18

      No mate, black for CPC always 👍🏻

    • @NickGirnius
      @NickGirnius 2 ปีที่แล้ว +15

      Deneutralization of black means it will always be CPC and grey will be the neutral mate

    • @mikethemask1525
      @mikethemask1525 2 ปีที่แล้ว +7

      Denuetralize the black always grey is neutral and should be sleeved blue.

    • @_eusty
      @_eusty 2 ปีที่แล้ว +3

      I do the same, but really there are no regs, as long as they are identified correctly.

    • @Riggersa
      @Riggersa 2 ปีที่แล้ว +3

      @@_eusty there are regs for it, if you look in the regs book where it lists the colours, now black should never be used as as a neutral with new colours

  • @Lordmarkstuckey4161
    @Lordmarkstuckey4161 5 หลายเดือนก่อน

    Why are Meters now fitted on the outside of the house?

    • @23lnp
      @23lnp 5 หลายเดือนก่อน +1

      So the powers that be can gain access to it without you needing to be home.
      They cant enter your home by law unless you let them in.
      If you build a metal cage around your outdoor meter then they cant gain access and if they break it to get to the meter its classed as criminal damage.

  • @michaeltye8853
    @michaeltye8853 2 ปีที่แล้ว +2

    Pay slightly more and you can have colour coded SWA ….BROWN..BLUE …GREEN/YELLOW ..worth the extra .

    • @RDavisElectrical
      @RDavisElectrical  2 ปีที่แล้ว +2

      It’s really no time at all to put the heat shrink on, plus the heat gun kept my hands warm 😂

    • @kittsdiy
      @kittsdiy 2 ปีที่แล้ว +1

      +1 i really don't get this .. seems every UK elektrician buys the SWA for industrial 3 phase use with black/brown/grey . And changes the colors . Here in Belgium this is not really allowed as it is confusing .
      Using a black conductor for PE etc .. just buy the correct cable for domestic .. and it seemes UK is 99% single fase in houses .. should be no problem to find correct cable .( in Belgium we call this 3G16 / 3G25 . The G tells there is a ground wire( CPC yellow green in ) and 2 wires for current blue and brown(or black ) .

    • @_eusty
      @_eusty 2 ปีที่แล้ว

      @@kittsdiy That's because 3 core SWA is generally used on 3 phase systems....

    • @kittsdiy
      @kittsdiy 2 ปีที่แล้ว

      @@_eusty yep for 3x400V industrial use the colors are correct .. and NO neutral wire . And CPC is run seperate .. So domestic elektricians just buy the wrong cable and relabel it .. Would not pass inspection here official . the color has to be the same for whole cable ( so recoloring black to green/yellow is not ok here ) . But i think in UK after installation no external company needs to inspect the electricians work and aprove .. i have seen many do it on youube .. so i guess it's allowed in UK ..

    • @seano452
      @seano452 2 ปีที่แล้ว +1

      Hence the sleeving….
      If the sleeving is blue or green or brown, then that states what the conductor is. 👍🏻

  • @marcwilliams3921
    @marcwilliams3921 2 ปีที่แล้ว +1

    That neutral on the load side must of been a right pig

  • @supersparks9466
    @supersparks9466 2 ปีที่แล้ว +1

    Those switch fuses are pants, just no room in there. I always buy the Wylex ones ,plenty of room in them.

    • @Liam-nr1nd
      @Liam-nr1nd 3 หลายเดือนก่อน

      Wish I’d seen this comment before, fitted a niglon yesterday, fuck all space in there.

  • @olegbirfon-ss3fs
    @olegbirfon-ss3fs 7 หลายเดือนก่อน

    hi, anybody could explain when we could place 63amp, or 80amp or 100amp? after installed smart meter it increased the bill cost, burn off extractor, washing machine, hair drier, thank you have a nice day

  • @philbennett806
    @philbennett806 2 ปีที่แล้ว

    I installed one for a meter move, wrestled with the 25mm 3core only for the DNO to put in cable that was no bigger than my thumb! What’s that all about?!

  • @Emin3m1986
    @Emin3m1986 2 ปีที่แล้ว

    Mate, I`m curious how did you manage to put back the front of the Fused Switch Panel... I guess that you know what I mean.

  • @stevenredmond7455
    @stevenredmond7455 2 ปีที่แล้ว

    The meter box isn’t your’s so how do you get away with using it for your sw fuse. I’ve always had to put it either inside property of 2nd box.

    • @RDavisElectrical
      @RDavisElectrical  2 ปีที่แล้ว +1

      You can’t be serious?

    • @stevenredmond7455
      @stevenredmond7455 2 ปีที่แล้ว +3

      @@RDavisElectrical Yes i am serious. Maybe you require more experience. Different area’s i suppose have different rules. In Cambridgeshire we had to use a separate meter box for sw fuse. We were not allowed to fit anything in with the head & meter.

    • @persona250
      @persona250 ปีที่แล้ว +2

      The meter box is property of the homeowner.

    • @stevenredmond7455
      @stevenredmond7455 ปีที่แล้ว +1

      @@persona250 The box is but not what goes in it.

    • @Dexedus
      @Dexedus ปีที่แล้ว

      @@stevenredmond7455 Nah steve sw fuse can go in meter box!

  • @ljtr2112
    @ljtr2112 2 ปีที่แล้ว +1

    Great work mate… the guy from the DNO will appreciate the work too. Not understanding the ball ache you had leaving plenty of room for the meter 👍

    • @RDavisElectrical
      @RDavisElectrical  2 ปีที่แล้ว

      Cheers mate. He better appreciate it 😂😂

    • @benYMSB
      @benYMSB 10 หลายเดือนก่อน

      The meter provider won’t touch it. They don’t connect to a de-energised supply and on the basis there’s no room for an isolator, they’d walk away.

  • @whitey4909
    @whitey4909 2 ปีที่แล้ว +1

    Should you be fitting a 100a switch fuse?

    • @kittsdiy
      @kittsdiy 2 ปีที่แล้ว

      that would probably trip faster then DNO (melt) fuse. I would go for this approach i think.

  • @tomturner4590
    @tomturner4590 2 ปีที่แล้ว +2

    Just curious as to what is the need for another fuse next to the main fuse?

    • @RDavisElectrical
      @RDavisElectrical  2 ปีที่แล้ว +1

      We aren’t allowed to touch the main fuse 😅

    • @RDavisElectrical
      @RDavisElectrical  2 ปีที่แล้ว +1

      Without ringing the DNO anyway

    • @kittsdiy
      @kittsdiy 2 ปีที่แล้ว +2

      Also i hope the extra one is faster then the one from the DNO 🙂
      Seems a bit useless 2 100A melt fuses after eachother .. if the new one trips first your lucky .. you can replace it .
      If the DNO ones trips you have to call DNO or break the seal . ( kinda funny in uk they do'nt have automatic fuses from the DNO .. proably because melt fuses are cheaper )

    • @neil6438
      @neil6438 2 ปีที่แล้ว

      @@kittsdiy I thought that....

    • @darrenplant1428
      @darrenplant1428 2 ปีที่แล้ว

      It’s because the cable is over the recommended distance. And runs in the fabric of the building.

  • @andrewjames3908
    @andrewjames3908 ปีที่แล้ว

    Whats the limit on how long the cable run can be in this situation?

    • @peterigrenyi9176
      @peterigrenyi9176 ปีที่แล้ว

      No limit really. But you have to size cable correctly for voltage drop. (And i do not mean limitless as in 1 million miles... )

  • @jonte7582
    @jonte7582 ปีที่แล้ว

    how come the cables dont come with the right colour? Brown, Blue, Earth

    • @StuartJ
      @StuartJ ปีที่แล้ว

      Because the cable used was 3 phase + armoured (earth). Not sure why you wouldn't use 2 core, plus armoured.

    • @Dexedus
      @Dexedus ปีที่แล้ว

      @@StuartJ Having Earth as a wire in the cable from meter to the unit is more reliable than relying on the armour

    • @StuartJ
      @StuartJ ปีที่แล้ว +1

      @@Dexedus I don't see how. So long as the armour is correctly terminated.

    • @TronicUK
      @TronicUK หลายเดือนก่อน

      @@StuartJ the armour is not of sufficient size in this scenario .

  • @johnwaby4321
    @johnwaby4321 ปีที่แล้ว

    I would have put the tails gland above the main switch they would have gone straight in ..
    And fit an earthing nut on the swa gland .

  • @GRANTY960
    @GRANTY960 2 ปีที่แล้ว +1

    Don’t suppose you had to move the new enclosure about 3mm to the left to get the cover on did you 👀🤣

    • @RDavisElectrical
      @RDavisElectrical  2 ปีที่แล้ว +1

      Nope, went on, just 😬😅😂

    • @GRANTY960
      @GRANTY960 2 ปีที่แล้ว +1

      @@RDavisElectrical the squeaky bum when you remember the cover over laps 😂

    • @philtaylor3184
      @philtaylor3184 ปีที่แล้ว

      ​@@GRANTY960and the bonding strap for the front cover isn't fitted

  • @stevedebbiemoore
    @stevedebbiemoore ปีที่แล้ว

    Is there room for a smart meter🤔

  • @ElectricianTV
    @ElectricianTV 2 ปีที่แล้ว

    Nice one Ryan that is always a bitch of a job. Even if you do armours every day.its still shit. You made it look easy keep up the good work. The only thing I do different is I take the grommet out of the gland and put it back in, so the 2 25 mm holes are at the back.

    • @RDavisElectrical
      @RDavisElectrical  2 ปีที่แล้ว +1

      Cheers Andrew, appreciate it, yeah it’s a git of a job.

  • @MrBeats44
    @MrBeats44 2 หลายเดือนก่อน

    You won't be getting a smart meter in there, the meter fitter can't check for tightness on your tail going from iso into the meter

  • @tomcollinson5433
    @tomcollinson5433 2 ปีที่แล้ว +1

    Bet getting the cover on was a nightmare😂

    • @gavinnoname1424
      @gavinnoname1424 2 ปีที่แล้ว

      Pretty sure the each connection for the lid is on the right hand side too

  • @chrisinedgey
    @chrisinedgey หลายเดือนก่อน

    Surely you have now cut the available power to the house by 20%.

  • @avreclaim6469
    @avreclaim6469 2 ปีที่แล้ว +1

    Bin the banjo, Use Earth Nuts - It is 2022!! 🙂
    Also you have left that WRONG, the Isolator should kill the fuse, not a slick mod!
    Probably a job for CW, NOT a BW Gland as well....

    • @Dexedus
      @Dexedus ปีที่แล้ว

      yeah have to say this wasn't a great job on this video

  • @shiamjad
    @shiamjad ปีที่แล้ว

    very helpful video....

  • @connormelia2926
    @connormelia2926 ปีที่แล้ว

    Top stuff

  • @ELECTRICLIFE4U
    @ELECTRICLIFE4U 2 ปีที่แล้ว

    👍👍👍👍👍

  • @JC-sd3vh
    @JC-sd3vh ปีที่แล้ว

    Fuse switch

  • @rossdavis6837
    @rossdavis6837 2 ปีที่แล้ว

    Looks like agg bro😂

  • @BK-jc7ik
    @BK-jc7ik ปีที่แล้ว

    😁✋✋

  • @BlackDragonSP
    @BlackDragonSP 2 ปีที่แล้ว

    Хм, запасика у нуля нету

  • @aclarke0100
    @aclarke0100 2 ปีที่แล้ว

    What grips did you use please