I have explained this topic in detail video watch this one and ask question in comment section th-cam.com/video/UJXbBqc1bDg/w-d-xo.htmlsi=OresJzHxiP2a9dmZ
Water chemistry k bare m bataiye sir kitna ph, iron, turbidity, TDS conductivity maintain karte hai dm water m. Lightup k time water chemistry kiya maitain karte hai, CPU kab line m lete hai, function of CPU, COC of cooling tower kitna maintain karte hai or kyu?
Sir for C elev voted second condution Feeder c service and CD elevation oil gun in service and 110v ac power failure. Is feeder c service necessary for acting C voted. If feederC not in service and (Cd gun service and 110V AC fail) then also C should voted?
Nice explanation sir thank you
Jai ho 🎉❤🎉❤🎉❤🎉
Sir kindly explain about DO and Ph @ stator water and cupric oxide also explains
Ok
Sir make a live video class for governing system
So that we can clear our doubts in live
For improving flame intensity what ahould command given in SADC.
IS ryt approach to closed bofa
I have explained this topic in detail video watch this one and ask question in comment section th-cam.com/video/UJXbBqc1bDg/w-d-xo.htmlsi=OresJzHxiP2a9dmZ
Sir ek vedio interview questions list par banaiye please
Ok, next live will be about it.
G.n sir
Water chemistry k bare m bataiye sir kitna ph, iron, turbidity, TDS conductivity maintain karte hai dm water m. Lightup k time water chemistry kiya maitain karte hai, CPU kab line m lete hai, function of CPU, COC of cooling tower kitna maintain karte hai or kyu?
Ok, will explain
Sir please make video for Boiler and Turbine Emergency Handling
Live stream already available on my channel
Sir for C elev voted second condution
Feeder c service and CD elevation oil gun in service and 110v ac power failure.
Is feeder c service necessary for acting C voted.
If feederC not in service and (Cd gun service and 110V AC fail) then also C should voted?
Feeder C should proven for more than 2 second to arm NO FLAME VOTING CONDITION
Sir If One Vacuum pump in Permit and at that time other running Vacuum is Trip then what will be action taken at that time.
If there is only two vacuum pump then immediately reduce load to save unit corresponding to vacuum.
Load reduced 40 percent
@@kpatelbla
Sir i think unit will be trip on high vaccum in case of vaccum pump tripped
@vikaskumar-fq4uy if this is for more than 15 minute.
@@kpatelbla sir but vaccum will drop very fast, I don't think that it will take 15 minutes
Sir
Hotv me kitna volt supply hota hai
Aur
Lonv m kitna volt supply hota hi
LOTV 220 v DC., LONV 110 Volt AC
Why lovt hotv220 Dc and lonv and honv 110v ac sir
@abhishekmishra-nv3lf it is to initiate MFT in case of 110 Volt AC failuire
Sir why hotv lotv has 220v DC power not 110v AC power?
Yes 220V DC